CLIENT: PROJECT :

TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

Center IO Panel MCC 0-2


1 P-W1401A Raw water pumping #1 start command DO MCC0-2 24VDC Q4.0 DO1-QX.0-X11:21
2 P-W1401B Raw water pumping #1 start command DO MCC0-2 24VDC Q4.1 DO1-QX.1-X11:22
Raw Water Cabinet - MCC1-1
1 P-W1101C P-W1101C.Auto Raw water pumping #3 Auto DI MCC1-1 Dry Contact,NO I250.0 DI1-IX.0-,1
P-W1101C P-W1101C.DS Raw water pumping #3 DS DI MCC1-1 Dry Contact,NO I250.1 DI1-IX.1-,2
P-W1101C P-W1101C.Run Raw water pumping #3 Running DI MCC1-1 Dry Contact,NO I250.2 DI1-IX.2-,3
P-W1101C P-W1101C.FAL Raw water pumping #3 Fault DI MCC1-1 Dry Contact,NO I250.3 DI1-IX.3-,4
P-W1101C P-W1101C.Comm Raw water pumping #3 start command DO MCC1-1 24VDC Q150.0 DO1-QX.0-,1
P-W1101C P-W1101C.RET Raw water pumping #3 Reset DO MCC1-1 24VDC Q150.1 DO1-QX.1-,2
P-W1101C P-W1101A.ST Raw water pumping #3 frequency value AI 0-100 % MCC1-1 4-20mA IW280 AI1-IWX,9+,13-
P-W1101C P-W1101C.IT Raw water pumping #3 current value AI 0-143 I MCC1-1 4-20mA IW282 AI1-IWX+2,10+,14-
P-W1101C P-W1101C.SR Raw water pumping #3 frequency Ref AO 0-100 % MCC1-1 4-20mA QW160 AO1-QW0,1+,5-
2 P-W1101B P-W1101D.Run Raw water pumping #4 Auto DI MCC1-1 Dry Contact,NO I250.4 DI1-IX.4-,5
P-W1101B P-W1101D.FAL Raw water pumping #4 DS DI MCC1-1 Dry Contact,NO I250.5 DI1-IX.5-,6
P-W1101B P-W1101D.Comm Raw water pumping #4 Running DI MCC1-1 Dry Contact,NO I250.6 DI1-IX.6-,7
P-W1101B P-W1101D.RET Raw water pumping #4 Fault DI MCC1-1 Dry Contact,NO I250.7 DI1-IX.7-,8
P-W1101B P-W1101C.Comm Raw water pumping #4 start command DO MCC1-1 24VDC Q150.2 DO1-QX.2-,3
P-W1101B P-W1101C.RET Raw water pumping #4 Reset DO MCC1-1 24VDC Q150.3 DO1-QX.3-,4
P-W1101B P-W1101D.ST Raw water pumping #4 frequency value AI 0-100 % MCC1-1 4-20mA IW284 AI1-IWX+4,11+,15-
P-W1101B P-W1101D.IT Raw water pumping #4 current value AI 0-143 I MCC1-1 4-20mA IW286 AI1-IWX+6,12+,16-
P-W1101B P-W1101D.SR Raw water pumping #4 frequency Ref AO 0-100 % MCC1-1 4-20mA QW162 AO1-QW1,2+,6-
3 ATpH-W1101B ATpH-W1101B Raw Water pH Value AI 0-12 pH MCC1-1 4-20mA IW291 AI2-IWX+2,10+,14-
FT-W1101 FT-W1101 Raw Water Flow meter Value AI 0-1500 m3/h MCC1-1 4-20mA IW289 AI2-IWX,9+,13-
4
FT-W1101 FQ-W1101 Raw Water Flow meter totalizer DI MCC1-1 Wet Contact,NO I251.2 DI1-IX+1.2-,11
5 ControlCircuit ControlCircuit ControlCircuit DI MCC1-1 Dry Contact,NO I251.0 DI1-IX+1.0-,9
6 EMS EMS DI MCC1-1 Dry Contact,NO I251.1 DI1-IX+1.1-,10
Filter Panel MCC2-1
1 P-W1203C P-W1203C.Auto Clarifier Sludge pump #1 Auto DI MCC2-1 Dry Contact,NO I255.6 DI2-IX+1.6-,15
P-W1203C P-W1203C.Run Clarifier Sludge pump #1Running DI MCC2-1 Dry Contact,NO I255.7 DI2-IX+1.7-,16
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

P-W1203C P-W1203C.FAL Clarifier Sludge pump #1Tripping DI MCC2-1 Dry Contact,NO I257.6 DI3-IX+1.6-,15
P-W1203C P-W1203C.AC Clarifier Sludge pump #1 Active DO MCC2-1 24VDC Q152.4 DO1-QX.4-,5
2 P-W1203D P-W1203D.Auto Clarifier Sludge pump #2 Auto DI MCC2-1 Dry Contact,NO I257.7 DI3-IX+1.7-,16
P-W1203D P-W1203D.Run Clarifier Sludge pump #2 Running DI MCC2-1 Dry Contact,NO I262.6 DI5-IX+1.6-,15
P-W1203D P-W1203D.FAL Clarifier Sludge pump #2 Tripping DI MCC2-1 Dry Contact,NO I262.7 DI5-IX+1.7-,16
P-W1203D P-W1203D.AC Clarifier Sludge pump #2 Active DO MCC2-1 24VDC Q152.5 DO1-QX.5-,6
3 A-W1201E A-W1201E.Auto Agitator motor #1 Auto DI MCC2-1 Dry Contact,NO I252.0 DI1-IX.0-,1
A-W1201E A-W1201E.Run Agitator motor #1 Running DI MCC2-1 Dry Contact,NO I252.1 DI1-IX.1-,2
A-W1201E A-W1201E.FAL Agitator motor #1Tripping DI MCC2-1 Dry Contact,NO I252.2 DI1-IX.2-,3
A-W1201E A-W1201E.AC Agitator motor #1Active DO MCC2-1 24VDC Q152.0 DO1-QX.0-,1
4 A-W1201F A-W1201F.Auto Agitator motor #2 Auto DI MCC2-1 Dry Contact,NO I252.3 DI1-IX.3-,4
A-W1201F A-W1201F.Run Agitator motor #2 Running DI MCC2-1 Dry Contact,NO I252.4 DI1-IX.4-,5
A-W1201F A-W1201F.FAL Agitator motor #2 Tripping DI MCC2-1 Dry Contact,NO I252.5 DI1-IX.5-,6
A-W1201F A-W1201F.AC Agitator motor #2 Active DO MCC2-1 24VDC Q152.1 DO1-QX.1-,2
5 A-W1201G A-W1201G.Auto Agitator motor #3 Auto DI MCC2-1 Dry Contact,NO I252.6 DI1-IX.6-,7
A-W1201G A-W1201G.Run Agitator motor #3 Running DI MCC2-1 Dry Contact,NO I252.7 DI1-IX.7-,8
A-W1201G A-W1201G.FAL Agitator motor #3 Tripping DI MCC2-1 Dry Contact,NO I253.0 DI1-IX+1.0-,9
A-W1201G A-W1201G.AC Agitator motor #3 Active DO MCC2-1 24VDC Q152.2 DO1-QX.2-,3
6 A-W1201H A-W1201H.Auto Agitator motor #4 Auto DI MCC2-1 Dry Contact,NO I253.1 DI1-IX+1.1-,10
A-W1201H A-W1201H.Run Agitator motor #4 Running DI MCC2-1 Dry Contact,NO I253.2 DI1-IX+1.2-,11
A-W1201H A-W1201H.FAL Agitator motor #4 Tripping DI MCC2-1 Dry Contact,NO I253.3 DI1-IX+1.3-,12
A-W1201H A-W1201H.AC Agitator motor #4 Active DO MCC2-1 24VDC Q152.3 DO1-QX.3-,4
7 ControlCircuit ControlCircuit ControlCircuit DI MCC2-1 Dry Contact,NO I253.4 DI1-IX+1.4-,13
8 EMS EMS DI MCC2-1 Dry Contact,NO I253.5 DI1-IX+1.5-,14
Collecting discharge of the bottom of the
9 LS-W1204B.LL LS-W1204B.LL lamella sedimentation tank and slugde DI MCC2-1 Dry Contact,NO I253.6 DI1-IX+1.6-,15
holding tank Level Switch
10 PumpsInstrument PI PI.AC Pumps Instrument Tubidity Active DO MCC2-1 24VDC Q156.6 DI3-IX.6-,7
PumpsInstrument PI PI.Auto Pumps Instrument Tubidity DI MCC2-1 Dry Contact,NO I253.7 DI1-IX+1.7-,16
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

Flow Switch on pipe of Instrument Tubidity


11 FS1 DI MCC2-1 Dry Contact,NO I272.0 DI6-IX.0-,1
FS1 pump

12 BUT-W1202C.1 BUT-W1202C.1.OPL.SVCollection Sludge Valve #1 Solenoid Valve DO MCC2-1 24VDC Q153.1 DO1-QX+1.1-,10
Collection Sludge Valve #1 Open Limit
BUT-W1202C.1 BUT-W1202C.1.OPL.OPL DI MCC2-1 Dry Contact,NO I254.0 DI2-IX.0-,1
Switch
Collection Sludge Valve #1 Close Limit
BUT-W1202C.1 BUT-W1202C.1.OPL.CLL DI MCC2-1 Dry Contact,NO I254.7 DI2-IX.7-,8
Switch

13 BUT-W1202C.2 BUT-W1202C.2.SV Collection Sludge Valve #2 Solenoid Valve DO MCC2-1 24VDC Q153.2 DO1-QX+1.2-,11
Collection Sludge Valve #2 Open Limit
BUT-W1202C.2 BUT-W1202C.2.OPL DI MCC2-1 Dry Contact,NO I254.1 DI2-IX.1-,2
Switch
Collection Sludge Valve #2 Close Limit
BUT-W1202C.2 BUT-W1202C.2.CLL DI MCC2-1 Dry Contact,NO I255.0 DI2-IX+1.0-,9
Switch

14 BUT-W1202C.3 BUT-W1202C.3.SV Collection Sludge Valve #3 Solenoid Valve DO MCC2-1 24VDC Q153.3 DO1-QX+1.3-,12
Collection Sludge Valve #3 Open Limit
BUT-W1202C.3 BUT-W1202C.3.OPL DI MCC2-1 Dry Contact,NO I254.2 DI2-IX.2-,3
Switch
Collection Sludge Valve #3 Close Limit
BUT-W1202C.3 BUT-W1202C.3.CLL DI MCC2-1 Dry Contact,NO I255.1 DI2-IX+1.1-,10
Switch

15 BUT-W1202C.4 BUT-W1202C.4.SV Collection Sludge Valve #4 Solenoid Valve DO MCC2-1 24VDC Q153.4 DO1-QX+1.4-,13
Collection Sludge Valve #4 Open Limit
BUT-W1202C.4 BUT-W1202C.4.OPL DI MCC2-1 Dry Contact,NO I254.3 DI2-IX.3-,4
Switch
Collection Sludge Valve #4 Close Limit
BUT-W1202C.4 BUT-W1202C.4.CLL DI MCC2-1 Dry Contact,NO I255.2 DI2-IX+1.2-,11
Switch

16 BUT-W1202C.5 BUT-W1202C.5.SV Collection Sludge Valve #5 Solenoid Valve DO MCC2-1 24VDC Q153.5 DO1-QX+1.5-,14
Collection Sludge Valve #5 Open Limit
BUT-W1202C.5 BUT-W1202C.5.OPL DI MCC2-1 Dry Contact,NO I254.4 DI2-IX.4-,5
Switch
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

Collection Sludge Valve #5 Close Limit


BUT-W1202C.5 BUT-W1202C.5.CLL DI MCC2-1 Dry Contact,NO I255.3 DI2-IX+1.3-,12
Switch

17 BUT-W1202C.6 BUT-W1202C.6.SV Collection Sludge Valve #6 Solenoid Valve DO MCC2-1 24VDC Q153.6 DO1-QX+1.6-,15
Collection Sludge Valve #6 Open Limit
BUT-W1202C.6 BUT-W1202C.6.OPL DI MCC2-1 Dry Contact,NO I254.5 DI2-IX.5-,6
Switch
Collection Sludge Valve #6 Close Limit
BUT-W1202C.6 BUT-W1202C.6.CLL DI MCC2-1 Dry Contact,NO I255.4 DI2-IX+1.3-,13
Switch

18 BUT-W1202C.7 BUT-W1202C.7.SV Collection Sludge Valve #7 Solenoid Valve DO MCC2-1 24VDC Q153.7 DO1-QX+1.7-,16
Collection Sludge Valve #7 Open Limit
BUT-W1202C.7 BUT-W1202C.7.OPL DI MCC2-1 Dry Contact,NO I254.6 DI2-IX.6-,7
Switch
Collection Sludge Valve #7 Close Limit
BUT-W1202C.7 BUT-W1202C.7.CLL DI MCC2-1 Dry Contact,NO I255.5 DI2-IX+1.5-,14
Switch

19 BUT-W1202D.1 BUT-W1202D.1.SV Collection Sludge Valve #8 Solenoid Valve DO MCC2-1 24VDC Q154.0 DO2-QX.0-,1
Collection Sludge Valve #8 Open Limit
BUT-W1202D.1 BUT-W1202D.1.OPL DI MCC2-1 Dry Contact,NO I256.0 DI3-IX.0-,1
Switch
Collection Sludge Valve #8 Close Limit
BUT-W1202D.1 BUT-W1202D.1.CLL DI MCC2-1 Dry Contact,NO I256.7 DI3-IX.7-,8
Switch

20 BUT-W1202D.2 BUT-W1202D.2.SV Collection Sludge Valve #9 Solenoid Valve DO MCC2-1 24VDC Q154.1 DO2-QX.1-,2
Collection Sludge Valve #9 Open Limit
BUT-W1202D.2 BUT-W1202D.2.OPL DI MCC2-1 Dry Contact,NO I256.1 DI3-IX.1-,2
Switch
Collection Sludge Valve #9 Close Limit
BUT-W1202D.2 BUT-W1202D.2.CLL DI MCC2-1 Dry Contact,NO I257.0 DI3-IX+1.0-,9
Switch

21 BUT-W1202D.3 BUT-W1202D.3.SV Collection Sludge Valve #10 Solenoid Valve DO MCC2-1 24VDC Q154.2 DO2-QX.2-,3
Collection Sludge Valve #10 Open Limit
BUT-W1202D.3 BUT-W1202D.3.OPL DI MCC2-1 Dry Contact,NO I256.2 DI3-IX.2-,3
Switch
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

Collection Sludge Valve #10 Close Limit


BUT-W1202D.3 BUT-W1202D.3.CLL DI MCC2-1 Dry Contact,NO I257.1 DI3-IX+1.1-,10
Switch

22 BUT-W1202D.4 BUT-W1202D.4.SV Collection Sludge Valve #11 Solenoid Valve DO MCC2-1 24VDC Q154.3 DO2-QX.3-,4
Collection Sludge Valve #11 Open Limit
BUT-W1202D.4 BUT-W1202D.4.OPL DI MCC2-1 Dry Contact,NO I256.3 DI3-IX.3-,4
Switch
Collection Sludge Valve #11 Close Limit
BUT-W1202D.4 BUT-W1202D.4.CLL DI MCC2-1 Dry Contact,NO I257.2 DI3-IX+1.2-,11
Switch

23 BUT-W1202D.5 BUT-W1202D.5.SV Collection Sludge Valve #12 Solenoid Valve DO MCC2-1 24VDC Q154.4 DO2-QX.4-,5
Collection Sludge Valve #12 Open Limit
BUT-W1202D.5 BUT-W1202D.5.OPL DI MCC2-1 Dry Contact,NO I256.4 DI3-IX.4-,5
Switch
Collection Sludge Valve #12 Close Limit
BUT-W1202D.5 BUT-W1202D.5.CLL DI MCC2-1 Dry Contact,NO I257.3 DI3-IX+1.3-,12
Switch

24 BUT-W1202D.6 BUT-W1202D.6.SV Collection Sludge Valve #13 Solenoid Valve DO MCC2-1 24VDC Q154.5 DO2-QX.5-,6
Collection Sludge Valve #13 Open Limit
BUT-W1202D.6 BUT-W1202D.6.OPL DI MCC2-1 Dry Contact,NO I256.5 DI3-IX.5-,6
Switch
Collection Sludge Valve #13 Close Limit
BUT-W1202D.6 BUT-W1202D.6.CLL DI MCC2-1 Dry Contact,NO I257.4 DI3-IX+1.4-,13
Switch

25 BUT-W1202D.7 BUT-W1202D.7.SV Collection Sludge Valve #14 Solenoid Valve DO MCC2-1 24VDC Q154.6 DO2-QX.6-,7
Collection Sludge Valve #14 Open Limit
BUT-W1202D.7 BUT-W1202D.7.OPL DI MCC2-1 Dry Contact,NO I256.6 DI3-IX.6-,7
Switch
Collection Sludge Valve #14 Close Limit
BUT-W1202D.7 BUT-W1202D.7.CLL DI MCC2-1 Dry Contact,NO I257.5 DI3-IX+1.5-,14
Switch
Butterfly Valve #3 Filter Tank #1 Solenoid
26 BUT-W1301D.3 BUT-W1301D.3.SV DO MCC2-1 24VDC Q154.7 DO2-QX.7-,8
Valve - Air backwash
Butterfly Valve #3 Filter Tank #1 Open Limit
BUT-W1301D.3 BUT-W1301D.3.OPL DI MCC2-1 Dry Contact,NO I258.0 DI4-IX.0-,1
Switch - Air backwash
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

Butterfly Valve #3 Filter Tank #1 Close Limit


BUT-W1301D.3 BUT-W1301D.3.CLL DI MCC2-1 Dry Contact,NO I258.6 DI4-IX.6-,7
Switch - Air backwash
Butterfly Valve #3 Filter Tank #2 Solenoid
27 BUT-W1301E.3 HV-W1301E-3.SV DO MCC2-1 24VDC Q155.1 DO2-QX+1.1-,10
Valve - Air backwash
Butterfly Valve #3 Filter Tank #2 Open Limit
BUT-W1301E.3 HV-W1301E-3.OPL DI MCC2-1 Dry Contact,NO I258.2 DI4-IX.2-,3
Switch - Air backwash
Butterfly Valve #3 Filter Tank #2 Close Limit
BUT-W1301E.3 HV-W1301E-3.CLL DI MCC2-1 Dry Contact,NO I259.0 DI4-IX+1.0-,9
Switch - Air backwash
Butterfly Valve #3 Filter Tank #3 Solenoid
28 BUT-W1301F.3 HV-W1301F-3.SV DO MCC2-1 24VDC Q155.3 DO2-QX+1.3-,12
Valve - Air backwash
Butterfly Valve #3 Filter Tank #3 Open Limit
BUT-W1301F.3 HV-W1301F-3.OPL DI MCC2-1 Dry Contact,NO I258.4 DI4-IX.4-,5
Switch - Air backwash
Butterfly Valve #3 Filter Tank #3 Close Limit
BUT-W1301F.3 HV-W1301F-3.CLL DI MCC2-1 Dry Contact,NO I259.2 DI4-IX+1.2-,11
Switch - Air backwash
Butterfly Valve #4 Filter Tank #1 Solenoid
29 BUT-W1301D.4 BUT-W1301D.4.SV DO MCC2-1 24VDC Q155.0 DO2-QX+1.0-,9
Valve - water backwash
Butterfly Valve #4 Filter Tank #1 Open Limit
BUT-W1301D.4 BUT-W1301D.4.OPL DI MCC2-1 Dry Contact,NO I258.1 DI4-IX.1-,2
Switch - water backwash
Butterfly Valve #4 Filter Tank #1 Close Limit
BUT-W1301D.4 BUT-W1301D.4.CLL DI MCC2-1 Dry Contact,NO I258.7 DI4-IX.7-,8
Switch - water backwash
Butterfly Valve #4 Filter Tank #2 Solenoid
30 BUT-W1301E.4 BUT-W1301E.4.SV DO MCC2-1 24VDC Q155.2 DO2-QX+1.2-,11
Valve - water backwash
Butterfly Valve #4 Filter Tank #2 Open Limit
BUT-W1301E.4 BUT-W1301E.4.OPL DI MCC2-1 Dry Contact,NO I258.3 DI4-IX.3-,4
Switch - water backwash
Butterfly Valve #4 Filter Tank #2 Close Limit
BUT-W1301E.4 BUT-W1301E.4.CLL DI MCC2-1 Dry Contact,NO I259.1 DI4-IX+1.1-,10
Switch - water backwash
Butterfly Valve #4 Filter Tank #3 Solenoid
31 BUT-W1301F.4 BUT-W1301F.4.SV DO MCC2-1 24VDC Q155.4 DO2-QX+1.4-,13
Valve - water backwash
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

Butterfly Valve #4 Filter Tank #3 Open Limit


BUT-W1301F.4 BUT-W1301F.4.OPL DI MCC2-1 Dry Contact,NO I258.5 DI4-IX.5-,6
Switch - water backwash
Butterfly Valve #4 Filter Tank #3 Close Limit
BUT-W1301F.4 BUT-W1301F.4.CLL DI MCC2-1 Dry Contact,NO I259.3 DI4-IX+1.3-,12
Switch - water backwash
Water collection Valve #1 after Filtering -
32 LV-W1301D-6 LV-W1301D-6.CIR AO 0-100 % MCC2-1 4-20mA QW180 AO1-QW0,1+,5-
control position
Water collection Valve #1 after Filtering -
LV-W1301D-6 LV-W1301D-6.IR AI 0-100 % MCC2-1 4-20mA IW309 AI2-IWX,9+,13-
position
Water collection Valve #2 after Filtering -
33 LV-W1301E-6 LV-W1301E-6.CIR AO 0-100 % MCC2-1 4-20mA QW182 AO1-QW1,2+,6-
control position
Water collection Valve #2 after Filtering -
LV-W1301E-6 LV-W1301E-6.IR AI 0-100 % MCC2-1 4-20mA IW311 AI2-IWX+2,10+,14-
position
Water collection Valve #3 after Filtering -
34 LV-W1301F-6 LV-W1301F-6.CIR AO 0-100 % MCC2-1 4-20mA QW184 AO1-QW2,3+,7-
control position
Water collection Valve #3 after Filtering -
LV-W1301F-6 LV-W1301F-6.IR AI 0-100 % MCC2-1 4-20mA IW313 AI2-IWX+4,11+,15-
position
35 LT1301D LT1301D Level Transmitter Filter Tank #1 AI 0-2 m MCC2-1 4-20mA IW300 AI1-IWX,9+,13-
36 LT1301E LT1301E Level Transmitter Filter Tank #2 AI 0-2 m MCC2-1 4-20mA IW302 AI1-IWX+2,10+,14-
37 LT1301F LT1301F Level Transmitter Filter Tank #3 AI 0-2 m MCC2-1 4-20mA IW304 AI1-IWX+4,11+,15-
38 ATNTU-W1401 ATNTU-W1401 Treated Water after Filtering NTU Value AI 0-100 NTU MCC2-1 4-20mA IW318 AI3-IWX,9+,13-
Pen stock Valve #1 Filter Tank #1 Solenoid
39 SLI-W1301D.1 SLI-W1301D.1.SV DO MCC2-1 24VDC Q155.5 DO2-QX+1.5-,14
Valve - water inlet
Pen stock Valve #1 Filter Tank #1 Open
SLI-W1301D.1 SLI-W1301D.1.OPL DI MCC2-1 Dry Contact,NO I259.4 DI4-IX+1.4-,13
Limit Switch - water inlet
Pen stock Valve #1 Filter Tank #1 Close
SLI-W1301D.1 SLI-W1301D.1.CLL DI MCC2-1 Dry Contact,NO I261.5 DI5-IX.5-,6
Limit Switch - water inlet
Pen stock Valve #1 Filter Tank #2 Solenoid
40 SLI-W1301E.1 SLI-W1301E.1.SV DO MCC2-1 24VDC Q156.0 DO3-QX.0-,1
Valve - water inlet
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

Pen stock Valve #1 Filter Tank #2 Open


SLI-W1301E.1 SLI-W1301E.1.OPL DI MCC2-1 Dry Contact,NO I259.7 DI4-IX+1.7-,16
Limit Switch - water inlet
Pen stock Valve #1 Filter Tank #2 Close
SLI-W1301E.1 SLI-W1301E.1.CLL DI MCC2-1 Dry Contact,NO I262.0 DI5-IX+1.0-,9
Limit Switch - water inlet
Pen stock Valve #1 Filter Tank #3 Solenoid
41 SLI-W1301F.1 SLI-W1301F.1.SV DO MCC2-1 24VDC Q156.3 DO3-QX.3-,4
Valve - water inlet
Pen stock Valve #1 Filter Tank #3 Open
SLI-W1301F.1 SLI-W1301F.1.OPL DI MCC2-1 Dry Contact,NO I261.2 DI5-IX.2-,3
Limit Switch - water inlet
Pen stock Valve #1 Filter Tank #3 Close
SLI-W1301F.1 SLI-W1301F.1.CLL DI MCC2-1 Dry Contact,NO I262.3 DI5-IX+1.3-,12
Limit Switch - water inlet
Butterfly Valve #2 Filter Tank #1 Solenoid
42 BUT-W1301D.2 BUT-W1301D.2.SV DO MCC2-1 24VDC Q155.6 DO2-QX+1.6-,15
Valve - Drain sunface
Butterfly Valve #2 Filter Tank #1 Open Limit
BUT-W1301D.2 BUT-W1301D.2.OPL DI MCC2-1 Dry Contact,NO I259.5 DI4-IX+1.5-,14
Switch - Drain sunface
Butterfly Valve #2 Filter Tank #1 Close Limit
BUT-W1301D.2 BUT-W1301D.2.CLL DI MCC2-1 Dry Contact,NO I261.6 DI5-IX.6-,7
Switch - Drain sunface
Butterfly Valve #2 Filter Tank #2 Solenoid
43 BUT-W1301E.2 BUT-W1301E.2.SV DO MCC2-1 24VDC Q156.1 DO3-QX.1-,2
Valve - Drain sunface
Butterfly Valve #2 Filter Tank #2 Open Limit
BUT-W1301E.2 BUT-W1301E.2.OPL DI MCC2-1 Dry Contact,NO I261.0 DI5-IX.0-,1
Switch - Drain sunface
Butterfly Valve #2 Filter Tank #2 Close Limit
BUT-W1301E.2 BUT-W1301E.2.CLL DI MCC2-1 Dry Contact,NO I262.1 DI5-IX+1.1-,10
Switch - Drain sunface
Butterfly Valve #2 Filter Tank #3 Solenoid
44 BUT-W1301F.2 BUT-W1301F.2.SV DO MCC2-1 24VDC Q156.4 DO3-QX.4-,5
Valve - Drain sunface
Butterfly Valve #2 Filter Tank #3 Open Limit
BUT-W1301F.2 BUT-W1301F.2.OPL DI MCC2-1 Dry Contact,NO I261.3 DI5-IX.3-,4
Switch - Drain sunface
Butterfly Valve #2 Filter Tank #3 Close Limit
BUT-W1301F.2 BUT-W1301F.2.CLL DI MCC2-1 Dry Contact,NO I262.4 DI5-IX+1.4-,13
Switch - Drain sunface
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

Butterfly Valve #2 Filter Tank #1 Solenoid


45 BUT-W1301D.5 BUT-W1301D.5.SV DO MCC2-1 24VDC Q155.7 DO2-QX+1.7-,16
Valve - Drain based
Butterfly Valve #2 Filter Tank #1 Open Limit
BUT-W1301D.5 BUT-W1301D.5.OPL DI MCC2-1 Dry Contact,NO I259.6 DI4-IX+1.6-,15
Switch - Drain based
Butterfly Valve #2 Filter Tank #1 Close Limit
BUT-W1301D.5 BUT-W1301D.5.CLL DI MCC2-1 Dry Contact,NO I261.7 DI5-IX.7-,8
Switch - Drain based
Butterfly Valve #2 Filter Tank #2 Solenoid
46 BUT-W1301E.5 BUT-W1301E.5.SV DO MCC2-1 24VDC Q156.2 DO3-QX.2-,3
Valve - Drain based
Butterfly Valve #2 Filter Tank #2 Open Limit
BUT-W1301E.5 BUT-W1301E.5.OPL DI MCC2-1 Dry Contact,NO I261.1 DI5-IX.1-,2
Switch - Drain based
Butterfly Valve #2 Filter Tank #2 Close Limit
BUT-W1301E.5 BUT-W1301E.5.CLL DI MCC2-1 Dry Contact,NO I262.2 DI5-IX+1.2-,11
Switch - Drain based
Butterfly Valve #2 Filter Tank #3 Solenoid
47 BUT-W1301F.5 BUT-W1301F.5.SV DO MCC2-1 24VDC Q156.5 DO3-QX.5-,6
Valve - Drain based
Butterfly Valve #2 Filter Tank #3 Open Limit
BUT-W1301F.5 BUT-W1301F.5.OPL DI MCC2-1 Dry Contact,NO I261.4 DI5-IX.4-,5
Switch - Drain based
Butterfly Valve #2 Filter Tank #3 Close Limit
BUT-W1301F.5 BUT-W1301F.5.CLL DI MCC2-1 Dry Contact,NO I262.5 DI5-IX+1.5-,14
Switch - Drain based
Chemical Panel MCC2-2
1 A-W1602C A-W1602C.Auto PAC Mixer Auto DI MCC2-2 Dry Contact,NO I268.2 DI3-IX.2-,3
A-W1602C A-W1602C.Run PAC Mixer Running DI MCC2-2 Dry Contact,NO I268.3 DI3-IX.3-,4
A-W1602C A-W1602C.FAL PAC Mixer Tripping DI MCC2-2 Dry Contact,NO I268.4 DI3-IX.4-,5
A-W1602C A-W1602C.AC PAC Mixer Active DO MCC2-2 24VDC I171.0 DO1-QX+1.0-,9
2 P-W1602D P-W1602D.Auto PAC Chemical pump #1 Auto DI MCC2-2 Dry Contact,NO I264.0 DI1-IX.0-,1
P-W1602D P-W1602D.DS PAC Chemical pump #1 DS DI MCC2-2 Dry Contact,NO I264.1 DI1-IX.1-,2
P-W1602D P-W1602D.Run PAC Chemical pump #1 Running DI MCC2-2 Dry Contact,NO I264.2 DI1-IX.2-,3
P-W1602D P-W1602D.FAL PAC Chemical pump #1 Fault DI MCC2-2 Dry Contact,NO I264.3 DI1-IX.3-,4
P-W1602D P-W1602D.Comm PAC Chemical pump #1 start command DO MCC2-2 24VDC Q170.0 DO1-QX.0-,1
P-W1602D P-W1602D.RET PAC Chemical pump #1 Reset DO MCC2-2 24VDC Q170.1 DO1-QX.1-,2
P-W1602D P-W1602D.ST PAC Chemical pump #1 frequency value AI 0-100 % MCC2-2 4-20mA IW345 AI3-IWX,9+,13-
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

P-W1602D P-W1602D.SR PAC Chemical pump #1 frequency Ref AO 0-100 % MCC2-2 4-20mA QW188 AO1-QW0,1+,5-
3 P-W1602E P-W1602E.Auto PAC Chemical pump #2 Auto DI MCC2-2 Dry Contact,NO I264.4 DI1-IX.4-,5
P-W1602E P-W1602E.DS PAC Chemical pump #2 DS DI MCC2-2 Dry Contact,NO I264.5 DI1-IX.5-,6
P-W1602E P-W1602E.Run PAC Chemical pump #2 Running DI MCC2-2 Dry Contact,NO I264.6 DI1-IX.6-,7
P-W1602E P-W1602E.FAL PAC Chemical pump #2 Fault DI MCC2-2 Dry Contact,NO I264.7 DI1-IX.7-,8
P-W1602E P-W1602E.Comm PAC Chemical pump #2 start command DO MCC2-2 24VDC Q170.2 DO1-QX.2-,3
P-W1602E P-W1602E.RET PAC Chemical pump #2 Reset DO MCC2-2 24VDC Q170.3 DO1-QX.3-,4
P-W1602E P-W1602E.ST PAC Chemical pump #2 frequency value AI 0-100 % MCC2-2 4-20mA IW347 AI3-IWX+2,10+,14-
P-W1602E P-W1602E.SR PAC Chemical pump #2 frequency Ref AO 0-100 % MCC2-2 4-20mA QW190 AO1-QW1,2+,6-
4 P-W1604E P-W1604E.Auto Polymer Anion Chemical pump #1 Auto DI MCC2-2 Dry Contact,NO I265.0 DI1-IX+1.0-,9
P-W1604E P-W1604E.DS Polymer Anion Chemical pump #1 DS DI MCC2-2 Dry Contact,NO I265.1 DI1-IX+1.1-,10
P-W1604E P-W1604E.Run Polymer Anion Chemical pump #1 Running DI MCC2-2 Dry Contact,NO I265.2 DI1-IX+1.2-,11
P-W1604E P-W1604E.FAL Polymer Anion Chemical pump #1 Fault DI MCC2-2 Dry Contact,NO I265.3 DI1-IX+1.3-,12
Polymer Anion Chemical pump #1 start
P-W1604E P-W1604E.Comm DO MCC2-2 24VDC Q170.4 DO1-QX.4-,5
command
P-W1604E P-W1604E.RET Polymer Anion Chemical pump #1 Reset DO MCC2-2 24VDC Q170.5 DO1-QX.5-,6
Polymer Anion Chemical pump #1 frequency
P-W1604E P-W1604E.ST AI 0-100 % MCC2-2 4-20mA IW349 AI3-IWX+4,11+,15-
value
Polymer Anion Chemical pump #1 frequency
P-W1604E P-W1604E.SR AO 0-100 % MCC2-2 4-20mA QW192 AO1-QW2,3+,7-
Ref
5 P-W1604F P-W1604F.Auto Polymer Anion Chemical pump #2 Auto DI MCC2-2 Dry Contact,NO I265.4 DI1-IX+1.4-,13
P-W1604F P-W1604F.DS Polymer Anion Chemical pump #2 DS DI MCC2-2 Dry Contact,NO I265.5 DI1-IX+1.5-,14
P-W1604F P-W1604F.Run Polymer Anion Chemical pump #2 Running DI MCC2-2 Dry Contact,NO I265.6 DI1-IX+1.6-,15
P-W1604F P-W1604F.FAL Polymer Anion Chemical pump #2 Fault DI MCC2-2 Dry Contact,NO I265.7 DI1-IX+1.7-,16
Polymer Anion Chemical pump #2 start
P-W1604F P-W1604F.Comm DO MCC2-2 24VDC Q170.6 DO1-QX.6-,7
command
P-W1604F P-W1604F.RET Polymer Anion Chemical pump #2 Reset DO MCC2-2 24VDC Q170.7 DO1-QX.7-,8
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

Polymer Anion Chemical pump #2 frequency


P-W1604F P-W1604F.ST AI 0-100 % MCC2-2 4-20mA IW351 AI3-IWX+6,12+,16-
value
Polymer Anion Chemical pump #2 frequency
P-W1604F P-W1604F.SR AO 0-100 % MCC2-2 4-20mA QW194 AO1-QW3,4+,8-
Ref
6 P-W1603C P-W1603C.Auto NaOH Chemical pump #1 Auto DI MCC2-2 Dry Contact,NO I266.0 DI2-IX.0-,1
P-W1603C P-W1603C.DS NaOH Chemical pump #1 DS DI MCC2-2 Dry Contact,NO I266.1 DI2-IX.1-,2
P-W1603C P-W1603C.Run NaOH Chemical pump #1 Running DI MCC2-2 Dry Contact,NO I266.2 DI2-IX.2-,3
P-W1603C P-W1603C.FAL NaOH Chemical pump #1 Fault DI MCC2-2 Dry Contact,NO I266.3 DI2-IX.3-,4
P-W1603C P-W1603C.Comm NaOH Chemical pump #1 start command DO MCC2-2 24VDC I171.1 DO1-QX+1.1-,10
P-W1603C P-W1603C.RET NaOH Chemical pump #1 Reset DO MCC2-2 24VDC I171.2 DO1-QX+1.2-,11
P-W1603C P-W1603C.ST NaOH Chemical pump #1 frequency value AI 0-100 % MCC2-2 4-20mA IW354 AI4-IWX,9+,13-
P-W1603C P-W1603C.SR NaOH Chemical pump #1 frequency Ref AO 0-100 % MCC2-2 4-20mA QW196 AO2-QW0,1+,5-
7 P-W1603D P-W1603D.Auto NaOH Chemical pump #2 Auto DI MCC2-2 Dry Contact,NO I266.4 DI2-IX.4-,5
P-W1603D P-W1603D.DS NaOH Chemical pump #2 DS DI MCC2-2 Dry Contact,NO I266.5 DI2-IX.5-,6
P-W1603D P-W1603D.Run NaOH Chemical pump #2 Running DI MCC2-2 Dry Contact,NO I266.6 DI2-IX.6-,7
P-W1603D P-W1603D.FAL NaOH Chemical pump #2 Fault DI MCC2-2 Dry Contact,NO I266.7 DI2-IX.7-,8
P-W1603D P-W1603D.Comm NaOH Chemical pump #2 start command DO MCC2-2 24VDC I171.3 DO1-QX+1.3-,12
P-W1603D P-W1603D.RET NaOH Chemical pump #2 Reset DO MCC2-2 24VDC I171.4 DO1-QX+1.4-,13
P-W1603D P-W1603D.ST NaOH Chemical pump #2 frequency value AI 0-100 % MCC2-2 4-20mA IW356 AI4-IWX+2,10+,14-
P-W1603D P-W1603D.SR NaOH Chemical pump #2 frequency Ref AO 0-100 % MCC2-2 4-20mA QW198 AO2-QW2,2+,6-
8 FT-W1602D FI-W1602D PAC Flowmeter value AI 0-1000 l/p MCC2-2 4-20mA IW327 AI1-IWX,9+,13-
FT-W1602D FQ-W1602D PAC Flowmeter totalizer DI MCC2-2 Wet Contact,NO I267.0 DI2-IX+1.0-,9
9 FT-W1604E FI-W1604E Polymer Flowmeter #1 value AI 0-1000 l/p MCC2-2 4-20mA IW329 AI1-IWX+2,10+,14-
FT-W1604E FQ-W1604E Polymer Flowmeter #1 totalizer DI MCC2-2 Wet Contact,NO I267.1 DI2-IX+1.1-,10
10 FT-W1604F FI-W1604F Polymer Flowmeter #2 value AI 0-1000 l/p MCC2-2 4-20mA IW331 AI1-IWX+4,11+,15-
FT-W1604F FQ-W1604F Polymer Flowmeter #2 totalizer DI MCC2-2 Wet Contact,NO I267.2 DI2-IX+1.2-,11
11 FT-W1603A FI-W1603A Sludge pump Flowmeter #1 value AI 0-120 m3/h MCC2-2 4-20mA IW333 AI1-IWX+6,12+,16-
FT-W1603A FQ-W1603A Sludge pump Flowmeter #1 totalizer DI MCC2-2 Wet Contact,NO I267.3 DI2-IX+1.3-,12
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

12 FT-W1603B FI-W1603B Sludge pump Flowmeter #2 value AI 0-120 m3/h MCC2-2 4-20mA IW336 AI2-IWX,9+,13-
FT-W1603B FQ-W1603B Sludge pump Flowmeter #2 totalizer DI MCC2-2 Wet Contact,NO I267.4 DI2-IX+1.4-,13
13 ControlCircuit ControlCircuit ControlCircuit DI MCC2-2 Dry Contact,NO I267.7 DI2-IX+1.7-,16
14 EMS EMS DI MCC2-2 Dry Contact,NO I268.0 DI3-IX.0-,1
Polymer Storage Tank Level Switch Low -
15 LS-M-W1604C.LL LS-M-W1604C.LL Powder Automatic Dispensing Dissolver- DI MCC2-2 Dry Contact,NO I268.1 DI3-IX.1-,2
Polymer #3
16 LS-W1602E.HL LS-W1602E.HL PAC Storage Tank Level Switch High DI MCC2-2 Dry Contact,NO I267.5 DI2-IX+1.5-,14
17 LS-W1602F.LL LS-W1602F.LL PAC Storage Tank Level Switch Low DI MCC2-2 Dry Contact,NO I267.6 DI2-IX+1.6-,15
Treated water pumping station Cabinet MCC3
1 P-W1401C P-W1401C.Auto Water Outlet Pumping #3 Auto DI MCC3-1 Dry Contact,NO I270.0 DI1-IX.0-,1
P-W1401C P-W1401C.DS Water Outlet Pumping #3 DS DI MCC3-1 Dry Contact,NO I270.1 DI1-IX.1-,2
P-W1401C P-W1401C.Run Water Outlet Pumping #3 Running DI MCC3-1 Dry Contact,NO I270.2 DI1-IX.2-,3
P-W1401C P-W1401C.FAL Water Outlet Pumping #3 Fault DI MCC3-1 Dry Contact,NO I270.3 DI1-IX.3-,4
P-W1401C P-W1401C.Comm Water Outlet Pumping #3 start command DO MCC3-1 24VDC Q172.0 DO1-QX.0-,1
P-W1401C P-W1401C.RET Water Outlet Pumping #3 Reset DO MCC3-1 24VDC Q172.1 DO1-QX.1-,2
P-W1401C P-W1401C.ST Water Outlet Pumping #3 frequency value AI 0-100 % MCC3-1 4-20mA IW362 AI1-IWX,9+,13-
P-W1401C P-W1401C.IT Water Outlet Pumping #3 current value AI 0-169 I MCC3-1 4-20mA IW364 AI1-IWX+2,10+,14-
P-W1401C P-W1401C.SR Water Outlet Pumping #3 frequency Ref AO 0-100 % MCC3-1 4-20mA QW204 AO1-QW0,1+,5-
2 P-W1401D P-W1401D.Auto Water Outlet Pumping #3 Auto DI MCC3-1 Dry Contact,NO I270.4 DI1-IX.4-,5
P-W1401D P-W1401D.DS Water Outlet Pumping #3 DS DI MCC3-1 Dry Contact,NO I270.5 DI1-IX.5-,6
P-W1401D P-W1401D.Run Water Outlet Pumping #3 Running DI MCC3-1 Dry Contact,NO I270.6 DI1-IX.6-,7
P-W1401D P-W1401D.FAL Water Outlet Pumping #3 Fault DI MCC3-1 Dry Contact,NO I270.7 DI1-IX.7-,8
P-W1401D P-W1401D.Comm Water Outlet Pumping #3 start command DO MCC3-1 24VDC Q172.2 DO1-QX.2-,3
P-W1401D P-W1401D.RET Water Outlet Pumping #3 Reset DO MCC3-1 24VDC Q172.3 DO1-QX.3-,4
P-W1401D P-W1401D.ST Water Outlet Pumping #3 frequency value AI 0-100 % MCC3-1 4-20mA IW364 AI1-IWX+4,11+,15-
P-W1401D P-W1401D.IT Water Outlet Pumping #3 current value AI 0-169 I MCC3-1 4-20mA IW366 AI1-IWX+6,12+,16-
P-W1401D P-W1401D.SR Water Outlet Pumping #3 frequency Ref AO 0-100 % MCC3-1 4-20mA QW206 AO1-QW1,2+,6-
3 ControlCircuit ControlCircuit ControlCircuit DI MCC3-1 Dry Contact,NO I271.0 DI2-IX+1.0-,9
4 EMS EMS DI MCC3-1 Dry Contact,NO I271.1 DI2-IX+1.1-,10
CLIENT: PROJECT :
TAG NAME LIST CHENLONG BINH DUONG PAPER CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD PHASE 2: 20.000 M3/DAY

Date Description No. 1


07-10-21 For As built

Type
No Device name Device Tag SERVICE / DESCRIPTION In/O Range Unit Regional Type Contact Address Terminal NO.
ut

Butterfly Valve #3 on pipe to site mill


5 HV-W1401C.2 HV-W1401C.2.SV DO MCC3-1 Dry Contact,NO Q172.4 DO1-QX.4-,5
Solenoid Valve
Butterfly Valve #3 on pipe to site mill Open
HV-W1401C.2 HV-W1401C.2.OPL DI MCC3-1 Dry Contact,NO I271.2 DI2-IX+1.2-,11
Limit Switch
Butterfly Valve #3 on pipe to site mill Close
HV-W1401C.2 HV-W1401C.2.CLL DI MCC3-1 Dry Contact,NO I271.3 DI2-IX+1.3-,12
Limit Switch
Butterfly Valve #4 on pipe to site mill
6 HV-W1401D.2 HV-W1401D.2.SV DO MCC3-1 Dry Contact,NO Q172.5 DO1-QX.5-,6
Solenoid Valve
Butterfly Valve #4 on pipe to site mill Open
HV-W1401D.2 HV-W1401D.2.OPL DI MCC3-1 Dry Contact,NO I271.4 DI2-IX+1.4-,13
Limit Switch
Butterfly Valve #4 on pipe to site mill Close
HV-W1401D.2 HV-W1401D.2.CLL DI MCC3-1 Dry Contact,NO I271.5 DI2-IX+1.5-,14
Limit Switch

Noted : DI2-IX+1.3-,12 DI2 : Number of Card Into Rack IO


IX.x Or IX+1.x : Byte.Bit On card
,12 : Number On Card for wiring ERATECH
DO1-QX+.4-,5 DO2 : Number of Card Into Rack IO
QX.x Or QX+1.x : Byte.Bit On card
5 : Number On Card for wiring
AI1-IWX+2,9+,13- AI2 : Number of Card Into Rack IO
IWX Or IWX+ : Word on Card
9+,13- : Number On Card for wiring
AO1-QW0,1+,5- AO2 : Number of Card Into Rack IO
QWX : Word on Card
1+,5- : Number On Card for wiring