RATED VALUE

A Rated HV current [A]


B Rated LV current [A]
C Rated HV voltage [kV]
LOAD TEST MEASUREMENT
D Current suplied [A]
E Power measured [W]
F Voltage measured [V]
𝜃1𝑎 Winding temperature [°C]
RESISTANCE MEASUREMENT
𝑅𝐻1−𝐻2 + 𝑅𝐻2−𝐻3 + 𝑅𝐻3−𝐻1
G Sum of HV resistance [W] ෍ 𝑅𝐻𝑉 =
2
𝑅𝑥1−𝑥2 + 𝑅𝑥2−𝑥3 + 𝑅𝑥3−𝑥1
H Sum of LV resistance [mW] ෍ 𝑅𝐿𝑉 =
2
𝜃1 Winding temperature [°C]
234.5 + θ1
J Correction factor 1 (θ1a to θ1 ) fk θ1 =
234.5 + θ1a
LOSSES CALCULATION

K I2 R loss at θ1 [W] A2 ×G×J + B 2 ×H×0.001×J


234.5+85
L Correction factor 2 (θ1 to 85℃) fk 85 =
234.5+θ1

M I2 R loss at 85℃ [W] K×L


2
𝐴
N Stray loss at θ1 {W} ቆ ቇ×𝐸−𝐾
𝐷
𝑁
O Stray loss at 85℃, 60 Hz [W] × 1.34
𝐿

P Load losses at 85℃, 60 Hz [W] M+O

IMPEDANCE CALCULATION
𝐴
Q Impedance voltage at θ1 [V] ×𝐹× 3
𝐷
𝐸
R Resistance voltage at θ1 [V] 𝑉𝑅 𝜃1 =
3×𝐴
𝑃
S Resistance voltage at 85℃ [V] 𝑉𝑅 85℃ =
3×𝐴

T Reactance voltage at 60Hz [V] 𝑉𝑋 = 𝑄2 − 𝑅2

U Impedance voltage at 85℃ [V] 𝑉𝑍 85℃ = 𝑆2 + 𝑇2

𝑈
V Impedance at 85℃ [%] 𝑉𝑍 85 = × 100
𝐶 × 1000