You are on page 1of 7

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/4049911

Evaluating transformer condition using DGA oil analysis

Conference Paper · November 2003


DOI: 10.1109/CEIDP.2003.1254893 · Source: IEEE Xplore

CITATIONS READS

48 11,352

1 author:

Sayed A. Ward
Delta University for Science and Technology
82 PUBLICATIONS   463 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Mitigation of transient overvoltages due to power system restoration using artificial neural network as a prediction and detection tool View project

Optimal grid size for precipitators using finite difference method based on full multi-grid method View project

All content following this page was uploaded by Sayed A. Ward on 10 March 2016.

The user has requested enhancement of the downloaded file.


2003 Annual Report Conference on Electrical Insulation and Dielectric Phenomena
Evaluating Transformer Condition Using DGA Oil Analysis
Sayed A. Ward
Faculty of Engineering (Shonbra)
Electrical Engineering Department
Cairo, Egypt

Abstract: Early detection of incipient faults in inception faults in transformers and other electrical
transformers reduces costly unplanned outages. The equipments using insulating oil. Gas-in-oil analysis
most sensitive and reliable technique for evaluating by gas chromatogaphy has proven to he predictive
the health of transformer is dissolved gas analysis and valuable some of the problems, which could
@CA). This paper uses dissolved gas analysis to progress to catastrophic failures in transformers that
study the history of different transformers in service, can be detected, are: arcing; corona; overheated oil,
from which dissolved combustible gases (DCG) in oil and cellulose degradation. These problems result in
are used as a diagnostic tool for evaluating the gas production as they start to develop and gas
condition of the transformer. Oil quality and production increases with increasing severity of the
dissolved gasses tests are comparatively used for this problem.
purpose. The effect of transformer aging on This paper shows how dissolved gases in
dissolved combustible gasses is also examined. It is insulating oil can be used as a diagnostic tool for
noted that the oil quality tests for transformer oil are faults occurring on apparatus using insulating oil
inconclusive and that the DGA test is then necessary such as transformers. This is achieved by comparing
for complete evaluation of transformer condition. the results of traditional testing techniques (quality
tests) with those using DGA.
Introduction
Tested Oil Samples
Insulating oils suffer from deterioration, which can
become fatal for transformers. Also, discharge in oil In this study, four samples of insulating oils are taken
can cause serious damage to the other insulating from transformers in service. The transformers bad
materials, making the monitoring of power different ratings and different conditions of
transformers insulation an important task. When operation. The four samples are: -
insulating oils and cellulose materials in reactive Sample 1: taken from a transformer in service since
equipment are subjected to higher than normal 1999 and is rated 230 kV and 180 MVA.
electrical or thermal stresses, they decompose to Sample 2: taken from a transformer in service since
produce certain combustible gases referred to as fault 1987 and is rated 115 kV and 30 MVA.
gases. For incipient fault conditions (i.e. slowly Sample 3 taken from a transformer in service since
evolving fault), the gases generated will be dissolved 1980 and is rated 66 kV and 25 MVA.
into the oil long before any free gas is accumulated in Sample 4 taken from a transformer in service since
the gas relay. Thus by analyzing oil sample for 1997 and is rated 69 kV and 40 MVA.
dissolved gas content it is possible to asses the
condition of the equipment and detecting faults at an Diagnostic Testing of Sample 1
early stage. If a fault is indicated, the type of fault
can be predicted using various analysis methods. Two groups of tests were performed, namely oil
Several dissolved gas analysis (DGA) tests should he quality tests and DGA tests. The former includes
taken over a period of time, in order to determine the dielectric breakdown voltage, interfacial tension.
rate of increase of the fault gases, and therefore the water content, and neutralization number tests.
rate of advancement of the fault.
Presently there are several on-line monitoring Oil quality tests
methods [I]. The most favorable tests for power
transformer insulation assessment are on-line types, When quality tests were performed on sample 1, the
including partial discharge (PD) monitoring and following results were obtained
dissolved gas-in-oil analysis [2]. A more successful
technique for on-line incipient fault diagnosis is Dielectric breakdown voltage test (BD), DGA
DGA, which is based on routine oil sampling, and the laboratories typically use ASTM No. D-877 or D-
modem technology of on-line gas monitors. 1816. The ASTM Test Method No. D-1816 was used
Dissolved gas analysis (DGA) is widely accepted in this work with an oil tester of output voltage up to
as the most reliable tool for the earliest detection of 100 kV.

0-7805791~1/03/$17.0002003 IEEE 463


Interfacial tension (IFT) test, this test was carried From Figla we see the concentration of Hzr C b ,
out according to ASTM D 971-91 [31. C*H, and CO is over the normal limits according to
IEEE [5]. By looldng for in these results as general
Water content test (WC), this study used the we can note that;
standard test method for measuring water in
transformer oil is the ASTM D1533 test b o & as - As Hz and CH, are over the normal limits this
the Karl Rscher reaction test. indicate that there is a corona in oil.
- Also, for CH, and C z b are over the normal limits,
Neutralization number (NN) test, in this study the these indicate that there is overheated in oil. For
neutralization number test carried out according to CO as it is over normal limits this means that there
ASTM D-971. is overheated in cellulose.
A second type of Diagnosis concerns on the Key
The history for oil quality tests results on sample 1 gas ratios such as Domenburg and Rogers ratio
are; BD is changed from 35 up to 43 kV, water methods, which use the ratios of dissolved gas
content is changed from 5 to l'lppm, IFT is 45 concentrations as the basis of fault diagnosis.
Dyndcm, and NN is changed from 0.005 to 0.02 mg Historically five ratios, which are C H m ,
KHOIg. So, the quality tests for this sample show the CZH21C2H4, C2H2/CH4, C2H6K2H2 and
overall quality of the oil are acceptable and normal. C2H4IC2H6, have been used 161.

Dissolved gas analysis test Domenburg ratio method, the Domenburg method
utilizes four calculated gas ratios to indicate a single
Agilent 6890 Series Gas Chroinatograph according to fault type from three general fault types. This
ASTM 3612 carried out this test. The results of DGA procedure requires sigruficant levels of the gases to
test on the transformer oil sample -1 are shown in he present in order for the diagnosis to he valid. The
Figure I . Figure l a shows the concentration of DCG four ratios and their diagnosis values are given [61.
in sample in ppm, hut the percent of DCG with By using Domenburg method that used five
respect to the total dissolved combustible gases individual gases or four-key gas ratios, which are
(TDCG) is shown in figure lh. (CHdH2, CzHzKzH4. CzWCH4 and CzHdCzHz), and
applying on sample 1 we have;
Interpretation of DCG results, a number of
methods are in use for the interpretation of the
dissolved gas analysis. A qualitative and quantitative
interpretation has a generally accepted list of gases
and associated conditions are found.

Key gases for interpretation. the key gas method


identities the key gas for each type of fault and uses
the percent of this gas to diagnose the fault [41. Key
gases formed by degradation of oil and paper
insulation are hydrogen (H2), methane (CHd, ethane
(CZ&), ethylene (CzH,), acetylene (CzHz). carbon
monoxide (CO), and oxygen (02). Except for carbon
monoxide and oxygen, all these gases are formed
from the degradation of the oil itself. Carbon
monoxide, carbon dioxide (COz), and oxygen are
formed from degradation of cellulose (paper)
insulation. Gas type and amounts are determined by
where the fault occurs in the transformer and the
severity and energy of the event. Events range from
low energy events such as partial discharge, which
produces hydrogen and trace amounts of methane W CHI C2H6 Qly c2K1 EO
and ethane, to very high energy sustained arcing, -*-
capable of generating all the gases including
acetylene, which requires the most energy. (b) % Concenmtion of DCG
Rgure I: DGA dam for sample I

464
From the diagnosis of sample 1, we have that this
sample suffer from thermal effect which reach to 700
C? and this may he due to circulating currents
between core and tank and/or due to overloaded
joints. So, this transformer has a fecondition in order
to remove the dissolved gases in this transformer.
After the recondition, a transformer's DGA results
From this range we see that the transformer is are as follows;
suffering from a thermal fault (Thermal Hz=l, Cfi=IO, CzH6=2, C2&=7, CZHFI a d C-5.
decomposition).
Testing Sample2
Rogers ratio method, it is an additional tool that
may be used to look at dissolved gases in transformer Oil quality tests
oil. The Rogers ratio method taking into
consideration industrial experiences, laboratory tests, The history for quality tests results on oil transformer
and further theoretical assessment, the method was are as follows, BD is in range from 33 to 46 kV,
further modified into an IEC standard b71. The water content is changed from 8.5 to 20.5 ppm, IFT
original Rogers ratio method used four gas ratios range is from 27 to 36.5 Dyndcm, and NN changed
which are C U Z , CzHdCH4, C2HdC2b and between 0.005 to 0.07mg KHO/g
C2H21CZH4for diagnosis [5]. The refmed Rogers
method used two tables: one defmed the code of the Dissolved gas analysis test
ratio, and the other defined the diagnosis rule. The
ratio C2HdC& only indicated a limited temperature This sample is taken from the bottom of the
range of decomposition, but did not assist in further transformer in service. The DGA test results in ppm
identification of fault. Therefore, in IEC standard are;
599, the further development of Rogers ratio method, H2=59, CH4=93, C&=89, C2H4=6, CzHz=l,
it was deleted. Rogers ratio method and IEC 599 C-736, and C02=1519
have gained popularity in industrial practices. From the DGA on sample 2 we have the evaluation
However, it may give no conclusion in some cases. for combustible gases and so the condition of
This is the " no decision" problem. transformer by using the diagnostic tools such as
follows;
The diagnosis by Rogers ratios which are; ( CZHZ
ICz&, CHdH2 and C2HdC2H6)is given the type of Key Gas Method from DGA test the key gas is CO
general problem which the transformer is suffer and so we can say that, the transformer is under the
from. For this sample we have; overheated. Also, if we take into consideration that
the year of manufacture of this transformer 1987, the
all other DCG are in normal range with respect to the
age of transformer. As CO is the key gas in this case,
Thus the suggested fault detection is thermal more so we can use the ratio of CO2 I C 0 as a diagnosis for
than 700 c" [8]. this case.
For interpreting the severity of the problem and in
order to get more detail on this problem we using Paper degradation diagnosis, as shown from DGA
Rogers ratio method which have four ratios which for sample 2 the key gas is CO, so we must apply the
are, (CH4/H,, C2HdCH4,CZWCIH, and C Z H Z K ~ H ~ ) . paper degradation diagnosis. Paper degadation
diagnosis is an essential part of transformer
insulation condition assessment. Conventionally this
C H 4 - 1.367 > 1.0, ___-
-- C z H 6 - 0.1098 < 1.0, is done using the ratio of CO2 and CO.
H2 CH I
From the DGA of sample 2 we have CO2 is 1519
ppm and CO is 736 ppm. So, the ratio of CO2lCO is
less than 3 (2.063) and this generally considered an
indication of probable paper involvement in an
Based on Rogers ratios method, the evaluation for
electrical fault (arcing or sparking), along with some
the condition of the transformer is appem that the carbonization of paper. Normal COdCO ratios are
transformer suffer from circnlaimg currents between typically around seven [9].
core and tank andlor have over-loaded joints.

465
Domenburg Method, by using Domenburg ratio as - The possible faults on this transformer is thermal
a diagnostic tool on sample 2 we have; fault less than 300 C' in an area close to paper
insulation (paper is being heated), and
- Possible fmding of fault is discoloration of paper
CH
4:1.576 > 1.0, H Z = 0.167 < 0.75 insulation. Overloading and lor cwling problem.
H, CZH, Bad connections in lead or tap changer. Stray
%= 0.011 < 0.3 , --
'lH6 - 89 > 0.4 current path and lor stray magnetic flux.
CH C*H,
From -this range we see that the transformer is Paper degradation diagnosis, for this sample as the
suffering from a thermal fault (Thermal key gas CO and Hz is high not over limits according
decomposition). to the age of the transformer, so we can use paper
degradation diagnosis. For this sample, as COzlCO
Rogers ratio method,by using Rogers ratio we have equal to 33W3100. This indicates that COz/CO ratio
the following ratios, approaches to 1 and so, the transformer is suffering
from overheating of cellulose (for instance under
_
CH- I - 1 . 5 7 6 < 3 . 0 , - - CzH6 - 0.957 < 1.0 , arcing conditions) because arcing generates CO very
H, CH 4
rapidly [lo].

C.H,
= 0.067 < 1.0 and
CJi. __
= 0.167 c 0.5
By using this ratios and compare it with the
Testing on Sample 4
suggested diagnosis from gas ratio [SI, the suggested oil quality tests
diagnosis is the transformer is slight overheated to
150 C'. The oil quality tests carried out on this sample are
satisfied the following results, BD is 41 kV, water
Testing Sample 3 content is 6 ppm, I F I is 35 Dyndcm, and NN is 0.05
mg KHOlg. From these tests we can concluded that,
Oil quality tests the oil quality tests for this sample are satisfied the
ASTM specification.
By applying the quality tests on this sample we have
the breakdown test appear that the BD = 40kV, the DGA Tests
water content is 12 ppm, the ET is 33 Dynelcm and
the NN is 0.01 mg KOW g. From tests we can say From the DGA test, which is carried out on sample 4,
that this sample is satisfied the standard specification the concentration of DCG in ppm for oil sample is
and it is good from the point of view of oil quality shown in Rgure 3. Figure 3a shows the concentration
tests. of DCG in oil sample, but Figure 3b shows the
percent concentration of DCG from the TDCG.
DGA Tests From figure 3 we have, most of the individual
combustible gases such as H2, C h , C&, and C2&
The DGA test is carried out on sample 3. The data are over normal limits. Thus in order to evaluate the
from this test is shown in Figure 2. figure 2a shows condition of this transformer we use the following
the concentration of DCG in sample 3 in ppm and methods for interpretation.
figure 2b shows the percentage concentration of
DCG with respect to TJXG. From this figure we see Key Gas Method, from the DGA test on this sample
that, the following combustible gases (Ch.c2~6.CZ& we see that most of DCG are over limits. By using
and CzH)are within normal limits,but H2 and CO are individual and total dissolved key gas concentration
over normal limits. in ppm as a guide to classify risks to transformers
As the most individual combustible gases have not and according to IEEE [4]. This sample indicates
exceeded over the normal limits except HZ and CO. excessive decomposition of cellulose insulation and
So, the Rogers ratio method and Doerenburg method lor oil. Continued operation could result in failure of
is not valid for diagnosis in this case. For diagnostic the transformer.
the case of this transformer we used IEC 60599 of
key gases, possible faults and possible findings [71. The diagnosis for this sample can be satisfied by
For this sample we see that Hz and CO are the key using IEC 60599 of key gases [7]. For this sample, as
gases and referred to IEC 60599 of key gases we Hz, C h , C& and CO are key gases. so
have that, ~ The possible fault is thermal fault between 300 'C
and 7ooc"

466
16m, - The possible fmdings are paper insulation
nm I destroyed andor oil heavily carbonized.

Domenburg method, by using Domenburg method


of four key gases ratios and applying it on this
sample we have,
_ - 2.1683
'Ha - > 1.0, --
',HZ - 0.0016 < 0.75 ,
H, C,H,
''HZ_ -- 0.000746 < 0.3 , -
_ CzH6- 170 > 0.4
CH, C,H, _ _
So, by using Ratios key gases which is above, the
diagnosis is Thermal decomposition.

Rogers ratio method, the Rogers ratio method is


applied on this sample and has the following values,

Thus the suggested fault detection is Thermal more


than 700 c".
Thus hy using four Roger ratio which determines
the severity of the problem, the suggested diagnosis
is circulating currents between core and tank; and
overloaded joints and this' ratios are given by;
_ -
CH4-2.168>1.0and<3.0 ,--
C2H6- 0.1269 < 1.0
H2 CH 4

F O this
~ sample we See that the DCG is over the
normal limits and so it is must be take more than one
sample from this transformer in order to obtain a
suitable results that will lead to a suitable decision on
this transformer. Figure 4 shows the concentration of
DCG in ppm for individual gas for sample 4, which is
taken from transformer in service for a week. From
this figure we see that, the individual gases are
increasing significantly (more than 30 ppdday), so
the fault is active and the transformer should be de-
energized.

For sample 4, we study the effect of place from


which we take the sample of oil from the
transformer. The sample may be taken from Bottom,
top of transformer or from the buchholz. Figure 5
shows the concentration of DCG in ppm for samples
taken from one transformer (from Bottom, top, and
buchholz). From this figure we see that the DCG
concentration is very large in bottom of transformer
C0mbeai-b- than that of top of transformer and from that of
huchbolz. So the dissolved gas concentration in
(b)
bottom of transformer is large and dangerous and so
Figme 3 Concentration of DCG for ramle 4 most samples taken for DGA are taken from the
bottom of transformer.

467
think that this transformer has a manufacture
problem
5. The DCG concentration is very large in bottom of
transformer than that of top of the transformer
and from that of buchholz. So the dissolved gas
concentration in bottom of transformer is large
and dangerous and so most samples for DGA are
taken from the bottom of transformer.

References

[I] H.M. Shertukde, H.Alnazjar, U. Prabhnne, '' Fault


detection device for electrical power transformera
using novel DSP schema", Roceedings, ICSPA 96,
Boston, October 1996.
[2] Donald Chu, Andre Lux, " On-line monitoring of
power transformers and components: A renew of key
1 parameters", IEEE Electrical Insulation Conference

i.:m m/
5mD
0-
& Electrical Manufactures and coil winding
Exposition, Cincinnati Ohio,Oct. 25, 1999.
[3] ANSJIMTM D971-91, Standard Test Method for
Interfacial Tension of oil agmst water by &g
Method, 1991.
[4] ANSI / IEEE Standard C 57.104-1991, Guide for the
interpretation of gases generated m oil-immersed
transformen, institute of ElecUical and Electronic
Engineering, Inc., New York, NY, 1994.
H2 CH4 C%E CaU CaiZ CO [5] IEEE and IEC Codes to Interpret Incipient Faults io
-b*9..s
Transformers. using gas in oil analysis, By
R.R.Rogers C.E. G.B., Transmission Division,
Guilford, England, circa. 1995.
figme 5 : Place of sample effect on DCG io oil
[6] R.D.Stebbins, J.J.Kelly. S.D.Myers, '' Power
hansformer fault diagnosis', 1997 IEEE PESWM,
conclusions Panel Session, New York, Feb.6, 1997.
[7] IEC Publication 60599, Interpretation of the analysis
1. We have transformers that have operated safely of gases in (ransformen and other oil med electrical
with abnormal concentration of individual gases equipment in &, Geneva, Switzerland, 1999.
with no problem; however, they are stable and [SI S.D.Myers, I.J.Kelly, R.H.Parrish,Fay years; a guide
gases are not increasing, or are increasing very to uansformer maintenance, Chapter 4, aansformer
slowly. If TDCG and individual gases are . Maintenaxe Institute, Aloon, Ohio, USA, 1988.
increasing sigtllficantly (more than 30 ppdday), [Y] Transformer Maintenance; Electrical Maintenance,
Facilities Instructions, Standards and Techniques,
the fault is active and the transformer should be Volume 3-30, Last Updated October 2wO.
de-energized such as sample 4. [IO] P.J.GriEn, " Monitoring the integrity of cellulose
2. A sodden increase in key gases and the rate of gas insulation in order to determine power transformer
production is more important in evaluating a life", Minutes of F&y-Eighth Intemational
transformer than the amount of gas. An Conference of Doble Clients, Section 6-16,1991.
increasing gas generating rate indicates a problem
of increasing severity; therefore, as the generation Author address: Sayed A. Ward Faculty of
rate (ppwday) increases, a shorter sampling Engineering (Shoubra), Electrical Engineering
interval is recommended. Department, 108 Shoubra Street, Cairo, Egypt,
3. The oil quality tests are important for evaluating Email: Drsayedw@yahoo.com
the condition of the insulating oil hut it is not
sufficient for evaluating the condition for
transformer.
4. For sample 4, the year of manufacture is 1999 but
we see that this transformer is suffering from
severe overheating. This overheating make the
decision of transformer is de-energized and we

468

View publication stats

You might also like