ELECTRICAL SYSTEM PHILOSOPHY EXM01-03NH-BER0- REV.

SHEET: 10
0009 (M12028-60-009) FINAL TOTAL: 17

Table -1 Normal Lighting Lux Levels


LOCATION LUX
Passageways/Stairways 150
Engine room 200
Emergency generator room 150
Switchboard room 300
Auxiliary machinery 200
Work shop 300
State room 100
Mess room 300
Working position in the galley 300
Recreation room 100
Cabins 150
Wash room/Change room 100
Hospital 300
Office 500
Control room 300
Radio room 500
Accomodation outer passage 50
Stores 100

Table -2 Escape Lighting Lux Levels


LOCATION LUX
Passageways/Stairways 5
Engine room 10
Emergency generator room 10
Switchboard room 10
Auxiliary machinery 5
Work shop 5
State room 5
Mess room 10
Galley 10
Recreation room 5
Cabins 5
Wash room/Change room 5
Hospital 200
Office 10
Control room 250
Radio room 250