Selectivity in Medical IT circuits can be imple-
‘mented with thermomagnetic switches or fuses
of adequate size,
When using fuses, their purpose isto protect
teach socket in the group and, upstream in the
room switchboard. to protect the power supply
duct for each group of sockets. Total selectivity is
Implemented by choosing fuses of the appropri-
ate size and the main switch with avery high
magnetic trip current,
The advantages are obvious: if one considers that.
a short circuit in an operating room normally oc-
curs because the plugs have been pulled out by
tugging the cable instead of grasping the actual
plug, or due to fluids entering into contact with
active parts, a chorteireult ona ocket causes
tripping of the respective fuses, and therafore it.
is possible to use another socket (there are al-
ways more sockets than necessary) without any
serious disservice.
‘with the use of automatic miniature circult break-
ers, selectivity can be obtained by choosing the
protection devices so that forall the short circuit
values, up to the maximum leakage current pro-
vided for the duct protected by the downstream
Cireuit-breaker, the tripping zones of the minia~
ture circuit breakers in series do not overlap (fig,
3.16). In general, however, selectivity between cir-
cuit breakers is obtained also by regulating their
tripping time delays.
Selectivity must also be implemented for the
RcDs assigned to protect equipment powered di-
rectly by the network.
‘ror example, in the hospital accommodation
rooms (group 1 rooms) there are three circuits
(lighting, plug sockets, headboard sockets) each
protected with a 30 mA RCD; to protect the power
3
Temmcmanassimed
supply circuits for a group of rooms, a300 mA
RCD is installed, while upstream in the cabinet
there fs a 500 mA RCD. Lastly, total selectivity f2
‘obtained by regulating the tripping time delays of
the RCDs.
2.2.6 installation criteria
‘The switchboard containing the insulating trans-
former can be installed either wall-mounted or
floor-standing outside group 2 rooms, or inside
provided that itis outside the patient environ-
ment, in order to avoid contact between the pa-
tient- including via medical personnel and the
‘cabinet, which contains not just the circuits
downstream of the transformer, but also its
power supply conductors.
If the requirements demand power higher than
that allowed (10 kVA) for the insulating trans-
former, then multiple insulating transformers
‘must be installed in order to contain the leakage
currents. n this way itis possible to benefit from
the redundancy of the circuits in order to maxi-
mize continuity of service, also in the case of
maintenance.
‘The insulation monitoring and measuring device
‘can be placed in the electrical switchboard of the
Medical T system, but a panel with repetition of
acoustic/optical signals and a test pushbutton
‘must be located in the most used premises,
where the continuous presence of healthcare op-
‘erators is assumed.
Both the plug sockets and the mintature ctrcutt
breakers must be installed at more than 20cm
(from centre to centre) from any connection for
‘gas for medical use.
‘The socket outlet powered by a Medical IT system
‘must not be interchangeable with the plug sock-
‘ts of the same premises that are powered di-
rectly by the network,