You are on page 1of 4

Note on English translation / Hinweise zur englischen Fassung

This is a translation of the product data sheet valid in Germany.


All stated details and properties are in compliance with the regulations of the German standards
and building regulations. They are only applicable for the specified products, system components,
application rules, and construction details in connection with the specifications of the respective
certificates and approvals.
Knauf Gips KG denies any liability for applications outside of Germany as this requires changes
acc. to the respective national standards and building regulations.

Drywall Systems

D11-E01.de
Supplement to the 2019-01
System Data Sheet

Knauf Board Ceiling

Technical and building physical data D112.de, D113.de and D116.de


Fire resistance class F60 solely from below
Data for planning
Technical and physical building data

System variants
Fire resistance solely from below (fire resistance in conjunction with the basic ceiling see system data sheet D11.de)
Requirements on the basic Fire Cladding (lateral application) Rated weight Furring Insulation layer
ceiling for fire exposure resistance channel
class Required for fire

Knauf Piano fire-resistant board


From below resistance

Massivbauplatte Solid Board


Knauf fire-resistant board
No fire resistance requirements for For fire Minimum Without Max. axial Minimum Min.
basic ceiling/roof construction exposure thickness insulation layer clearances thickness den-
sity

Knauf Wallboard
From above (Plenum) b
Raw ceiling must have same fire

Silentboard
Fireboard
Diamant
resistance class as the suspend-
From From
ed ceiling
below above mm kg/m² mm mm kg/m³
D112.de Board ceiling with metal grid

● 20 Without
F60 – + 30.9 500 or
● 12.5 Mineral wool G

D113.de Board ceiling with flush metal grid

● 20 Without
F60 – + 30.9 500 or
● 12.5 Mineral wool G

D116.de Board ceiling with large-span metal grid

● 20 Without
F60 – + 33.7 500 or
12.5 Mineral wool G

Possible suspensions:
Universal brackets / damping universal brackets
Adjustable Universal Bracket / adjustable Damping Universal Bracket
Nonius Hanger Top with Nonius stirrup or Nonius hanger bottom
Determination of the load class
Load class Rated weight +
Weight of additional loads
kN/m2 kg/m²

Up to 0.65 60
50
Up to 0.50
40
Up to 0.40
30
Up to 0.30 20
Up to 0.15 10

Extension of the fire resistance Certificate of Usability Observe the notes on page 4.
■■ Divergences from the construction variants page 3 Notes For further information on planning and design see system
Prior consultation in acc. to page 4 is recommended. data sheet Knauf Board Ceilings D11.de.

2 D11-E01.de Knauf Board Ceiling


Data for planning
Technical and physical building data

Maximum grid spacings Dimensions in mm D112.de Fire resistance solely from below – Furring channel only
D112.de Fire resistance solely from below – Carrying and furring channel Axial spacings Suspender spacings a
Furring channel
Axial spacings Suspender spacings a Load class in kN/m²
Carrying channel b Up to 0.401) Up to 0.501) Up to 0.651)
Load class in kN/m²
c Up to 0.501) Up to 0.651) 500 950 900 850
500 800 750 D116.de Fire resistance solely from below – Carrying and furring channel
600 750 700
Axial spacings Suspender spacings a
700 700 650 Carrying channel
Load class in kN/m²
800 700 – c Up to 0.50 Up to 0.65
D113.de Fire resistance solely from below – Carrying and furring channel 500 1600 1200
Axial spacings Suspender spacings a 600 1300 1000
Carrying channel 700 1100 850
Load class in kN/m²
c Up to 0.401) Up to 0.501) Up to 0.651) 800 1000 –
500 850 800 750 1) Use suspenders of load carrying capacity class 0.40 kN
600 800 750 700 Customized dimensioning of the ceiling substructure is
700 750 700 650 possible on request. It is recommended that the substructure
Notes
800 750 700 – is designed to accommodate a possible additional ceiling
(≤ 0.15 kN/m²).
900 700 – –
1000 700 – –

Fire protection solely from below acc. to AbP P-SAC02/III-915


The system variants shown here generally show the exact system variants as in the National Technical Test Certificate. Divergences, e.g. use
Note of other suspenders, other spacings of the grid are possible in accordance with the specifications on pages 2 and 3. The notes acc. to page 4
apply accordingly.
Knauf board ceiling D112.de with metal grid
■■ Fire protection class F60 solely from below
■■ Double layer profile (carrying and furring channel)
■■ Without insulation layer

Design alternatives
Connection to solid walls and Perimeter runner UD 28/27, fastening spacing to solid walls ≤ 625 mm
lightweight partitions Fastening to lightweight partition cladding ≥ 15 mm Knauf Diamant with
≥ XTN 3.9 x 33 in every stud a ≤ 625 mm
Suspension Description Nonius hanger, spacing a ≤ 700 mm
Grid Carrying channel CD 60/27, axial spacing c ≤ 1350 mm
(Axial spacing 1st carrying channel for connection to lightweight partitions ≤ 625 mm)
Furring channels CD 60/27, axial spacing b ≤ 500 mm
Connection of the profiles Intersection connector for CD
Mineral wool insulation layer EN 13162 Without –
Cladding Board thickness/type ≥ 20 mm Solid Board
+ 12.5 mm Knauf Piano fire-resistant board, double-layer
Maximum board size 625 mm x 2500 mm (Solid Board),
1250 mm x 2500 mm (Knauf Piano fire-resistant board)
Fastening Knauf Schnellbauschraube Drywall Screw TN 3.5x35 mm (first layer),
Knauf Schnellbauschraube Drywall Screw TN 3.5x45 mm (second layer)
Spacing of fasteners ≤ 510 mm (first layer), ≤ 170 mm (second layer)

Observe the notes on page 4.


Notes
For further information on planning and design see system data sheet Knauf Board Ceilings D11.de.
D11-E01.de Knauf Board Ceiling 3
Usage instructions
Notes I Certificate of Usability

Notes on the document Fire resistance effect


Knauf System Data Sheets are the planning and application basis for the If the fire resistance effect from the classification of Knauf board ceiling is
planners and professional installers with the application of Knauf systems. achieved without involvement or consideration of the basic ceiling, the fire
The contained information and specifications, constructions, details and resistance is referred to as solely.
stated products are based, unless otherwise stated, on the certificates of This is relevant in particular when the plenum is to be protected against
usability (e.g. National Technical Test Certificate (abP) valid at the date they the exposure to fire from the room (fire resistance solely from below) or
are published as well as on the applicable standards. Additionally, design and a protective effect for the room against fire exposure in the plenum (fire
structural requirements and those relating to building physics (fire resistance resistance solely from above).
and sound insulation) are considered. A combination of both requirements may be necessary depending on the
The contained construction details are examples and can be used in a similar requirements stipulated by the building inspectorate and/or fire resistance
way for various cladding variants of the respective system. At the same time, concept.
the demands made on fire resistance and/or sound insulation as well as any Certificate of usability
necessary additional measures and/or limitations must be observed.
Knauf system Fire protection
References to other documents suspended ceilings,
System data sheets allocated solely to a single fire resistance class
■■ Suspended ceilings linings and suspended ceilings,
see system data sheet Knauf Board Ceilings D11.de D112.de

Product data sheets D113.de F60 solely from below: AbP P-SAC02/III-915
■■ Observe the product data sheets of the Knauf system components D116.de
Symbols in the document The stated constructional and structural properties, and characteristic
The following symbols are used in this document: building physics of Knauf systems can solely be ensured with the exclusive
Insulation layers use of Knauf system components, or other products expressly recommended
G Mineral wool insulation layer acc. to EN 13162 by Knauf. The validity and up-to-datedness of the stated proofs have to be
Non-combustible considered.
(insulating material, e.g. from Knauf Insulation) Notes on fire resistance
The specifications marked with offer additional application options,
Spacings of ceiling grid
which are not directly included in the Certificate of Usability. On the basis
a Spacing of suspenders/anchors of our technical assessments, we assume that these marked design
b Axial spacing furring channel (cladding span width) solutions can be assessed as a non-significant divergence. We can make
the documentation on which this assessment is based, such as surveyors'
c Axial spacing carrying channel (spacing furring channel)
reports or technical assessments, available to you together with the
Intended use of Knauf Systems Certificate of Usability on request. We recommend that a non-significant
Please observe the following: divergence be coordinated and authorised in advance in consultation
between the persons responsible for fire resistance and/or the relevant
Knauf systems may only be used for the application authorities.
cases as stated in the Knauf documentation. In case third
party products or components are used, they must be
Caution
recommended or approved by Knauf. Flawless application
of products/systems assumes proper transport, storage,
assembly, installation and maintenance.
Videos for Knauf systems and products can be found under the
following link:
EPD www.youtube.com/knauf

The iPad App Knauf Infothek now provides all the current
information and documents from Knauf Gips KG at any time and
in every location in a clear and comfortable way.
Knauf Infothek
Knauf Direct Knauf Gips KG Am Bahnhof 7, 97346 Iphofen, Germany
Technical Advisory Service:
All technical changes reserved. Only the current printed instructions are valid. The stated information represents current state-of-
the-art Knauf technology. The entire state of approved engineering rules, appropriate standards, guidelines, and rules of crafts-
knauf-direkt@knauf.de manship are not included herewith. These and all application instructions have to be adhered to separately by the installer. Our
warranty is expressly limited to our products in flawless condition. All application quantities and delivery amounts are based on
empirical data that are not easily transferable to other deviating areas.
www.knauf.de All rights reserved. All amendments, reprints and photocopies, including those of excerpts, require our expressed permission.

The stated constructional and structural design specifications and characteristics of building physics of Knauf systems can
D11-E01.de/eng/01.19/0/Dbl
only be ensured with the exclusive use of Knauf system components, or other products expressly recommended by Knauf.

You might also like