Air-Conditioners
Symbol explanations
WARNING
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or death.
CAUTION
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or dam-
age to the unit.
Indicates that caution must be taken with rotating parts. (This symbol is on the main unit label.) <Color: Yellow>
Indicates that the parts that are marked with this symbol pose a risk of electric shock. (This symbol is on the main
unit label.) <Color: Yellow>
WARNING
Carefully read the labels affixed to the main unit.
WARNING
Ask your dealer or a qualified technician to install the unit. Do not make any modifications or alterations to the unit.
Consult your dealer for repair.
Improper installation by the user may result in water leak-
age, electric shock, or fire. Improper repair may result in water leakage, electric shock,
or fire.
Properly install the unit on a surface that can withstand its
weight. Do not touch the heat exchanger fins with bare hands.
Unit installed on an unstable surface may fall and cause in- The fins are sharp and pose a risk of cuts.
jury.
In the event of a refrigerant leak, thoroughly ventilate the
Only use specified cables. Securely connect each cable so room.
that the terminals do not carry the weight of the cable.
If gaseous refrigerant leaks out and comes in contact with
Improperly connected cables may produce heat and start a an open flame, toxic gases will be generated.
fire.
Properly install the unit according to the instructions in the
Take appropriate safety measures against wind gusts and Installation Manual.
earthquakes to prevent the unit from toppling over.
Improper installation may result in water leakage, electric
Improper installation may cause the unit to topple over and shock, or fire.
cause injury or damage to the unit.
Have all electrical work performed by an authorized electri-
Only use accessories (i.e., air cleaners, humidifiers, electric cian according to the local regulations and the instructions
heaters) recommended by Mitsubishi Electric. in this manual. Use a dedicated circuit.
Insufficient power supply capacity or improper installation
of the unit may result in malfunctions of the unit, electric
shock, or fire.
HWE07120
i GB
WARNING
Keep electrical parts away from water. Consult your dealer or a qualified technician when moving
or reinstalling the unit.
Wet electrical parts pose a risk of electric shock, smoke, or
fire. Improper installation may result in water leakage, electric
shock, or fire.
Securely attach the control box cover.
After completing the service work, check for a refrigerant
If the cover is not installed properly, dust or water may infil-
leak.
trate and pose a risk of electric shock, smoke, or fire.
If leaked refrigerant is exposed to a heat source, such as a
Only use the type of refrigerant that is indicated on the unit fan heater, stove, or electric grill, toxic gases will be gener-
when installing or relocating the unit. ated.
Infiltration of any other types of refrigerant or air into the unit
Do not try to defeat the safety features of the unit.
may adversely affect the refrigerant cycle and may cause
the pipes to burst or explode. Forced operation of the pressure switch or the temperature
switch by defeating the safety features for these devices, or
When installing the unit in a small space, take appropriate the use of accessories other than the ones that are recom-
precautions to prevent leaked refrigerant from reaching the mended by Mitsubishi Electric may result in smoke, fire, or
limiting concentration. explosion.
Leaked refrigerant gas will displace oxygen and may cause
Consult your dealer for proper disposal method.
oxygen starvation. Consult your dealer before installing the
unit.
Do not use a leak detection additive.
CAUTION
HWE07120
ii GB
CONTENTS
I Features
[1] Features.................................................................................................................................... 1
II Components and Functions
[1] Components and Functions...................................................................................................... 2
III Specfications
[1] Specifications............................................................................................................................ 4
1.Specfications .......................................................................................................................... 4
2.Electrical component specifications........................................................................................ 6
HWE07120 GB
HWE07120 GB
[ I Features ]
I Features
[1] Features
HWE07120 -1- GB
[ II Components and Functions ]
II Components and Functions
(A)
(A) Air
(A)
2. Remote Controller
[PAR-21MAA]
Once the operation mode is selected, the unit will remain in the selected mode until changed.
1
[Set Temperature] Button 7 [Vane Control] Button
2
[Timer Menu] Button 8 [Ventilation] Button
[Monitor/Set] Button [Operation] Button
3 [Mode] Button 9 [Check/Clear] Button
[Back] Button 10 [Test Run] Button
4 [Timer On/Off] Button 11 [Filter] Button
[Set Day] Button [ ] Button
5 [Louver] Button 12 [ON/OFF] Button
[Operation] Button 13 Position of built-in room thermistor
6 [Fan Speed] Button 14 [Set Time] Button
Keep the remote controller out of direct sunlight to ensure accurate measurement of room temperature.
The thermistor at the lower right-hand section of the remote controller must be free from obstructions to ensure accurate mea-
surement of room temperature.
HWE07120 -2- GB
[ II Components and Functions ]
HWE07120 -3- GB
[ III Specfications ]
III Specfications
[1] Specifications
1. Specfications
HWE07120 -4- GB
[ III Specfications ]
HWE07120 -5- GB
[ III Specfications ]
HWE07120 -6- GB
20 157.5
15 12 37 100 37 IV Outlines and Dimensions
HWE07120
Access door
(B)
(A)
Note
50 7
88
77
G
50
Note2 0
50 45 00
~1 45
0 n3
50 tha
re
Mo
(A)
A
C
[ IV Outlines and Dimensions ]
100 x J=K
D (Duct)
Air Air
100 x (E-1)=F
outlet inlet
[1] Outlines and Dimensions
100
1. PEFY-P15, 20, 25, 32, 40, 50, 63VMS1-E
100
88
Less than 300mm
30
57
20
20
12
175mm 5mm
10
25
100
(Actual length)
23
90
49 625(Suspension bolt pitch) Air filter
Knockout hole 27
<accessory>
-7-
brazing connection (liquid) 270 Drain pipe (Power source wiring)
10 Drainpump Control box
23
(O.D. 32)
25
100
200
150(Duct)
2 x 2- 2.9 116 70 Terminal block(Power source)
1 Refrigerant piping 270 Drain pipe(O.D. 32)
Terminal block(Transmission)
brazing connection (gas) (Spontaneous draining)
4 To connect an intake duct, uninstall the air filter on the unit, and install a locally procured air filter on the intake
3 The dimensions in the table are those of the PEFY-P40, 50VMS1-E models, which have 3 fans. The PEFY-
GB
HWE07120
20 157.5
(B)
(A)
12 37 100 37
Note
15
88
Access door
50 7
77
G
50
Note2 0
45 00
50~ 450 n3
150 t ha
[ IV Outlines and Dimensions ]
M ore
(A)
A
C
H
100 x J=K
D (Duct)
100 x (E-1)=F
outlet inlet
100
100
Ceiling surface Access door
88
More than 10mm
12
30
20
20
10
100
25
23
L- 2.9
2 x E- 2.9
90
Air filter
-8-
49 625(Suspension bolt pitch)
Knockout hole 27
700 Suspension bolt hole
(Transmission wiring)
23 677 4-14 x 30 Slot Knockout hole 27
23
25
102
170
100
200
150(Duct)
2 x 2- 2.9 116 70 Terminal block(Power source)
1 Refrigerant piping 270 Drain pipe(O.D. 32) Terminal block(Transmission)
brazing connection (gas) (Spontaneous draining)
4 To connect an intake duct, uninstall the air filter on the unit, and install a locally procured air filter on the intake
3 The dimensions in the table are those of the PEFY-P40, 50VMS1L-E models, which have 3 fans. The PEFY-
GB
V Wiring Diagram
HWE07120
INSIDE SECTION OF CONTROL BOX
[ V Wiring Diagram ]
I.B.
CND
12345678 1234 21 (Black) 1 3 5
SW3 SW4 SW2
CN32 CN81 CN42 CN2M
(Red) (Red) OFF ON (Blue) DSA
1
CN3A LED2 ZNR02
3 (Blue) SWE
CN90 U
CN4F
TO NEXT INDOOR UNIT
A.B. 1234 TB2
L
4 8 N PULL BOX
3 7
-9-
2 6 *FOR PEFY-P VMS1L-E
SW1 SWA SWB 1 5
CN43 4 FUSE (16A)
3
9 0 1 9 0 1 0 2
EF 1 2
8 2 8 2 D 3 1
C 4 BREAKER (16A)
7 3 7 3 B 5
6 5 4 6 5 4 SWC A 9 76
8
CN82
TB5 TB15
SW12 SW11 SW14 M1 M2 S(SHIELD) 1 2
(10’s digit)(1’s digit) (Connection No.)
POWER SUPPLY
~220,230,240V
50,60Hz
GB
[ V Wiring Diagram ]
Note 1 Wiring to TB2, TB5, and TB15 indicated by the double-dashed lines is on-site work.
2 terminal block, connector.
HWE07120 - 10 - GB
[ VI Refrigerant System Diagram ]
VI Refrigerant System Diagram
(A)
(B)
(G)
(D)
(H) (C)
(F)
(E) (E)
(I)
HWE07120 - 11 - GB
[ VII Troubleshooting ]
VII Troubleshooting
[1] Troubleshooting
1. Check methods
1. Component and check points
(1) Thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 10°C - 30°C)
Normal Abnormal
4.3k - 9.6k Open or short
(Refer to the thermistor characteristic graph below.)
Low-temperature thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22) 50
Gas pipe thermistor (TH23)
Drain sensor (DS)
Thermistor R0 = 15 k 3% 40
Multiplier of B = 3480 k 2%
Rt = 15 exp { 3480( 1 1 )}
273+t 273 30
(B)
0°C 15k
10°C 9.6k
20°C 6.3k 20
25°C 5.2k
30°C 4.3k
40°C 3.0k
(A) Temperature (°C) 10
(B) Resistance (k )
0
-20 -10 0 10 20 30 40 50
(A)
HWE07120 - 12 - GB
[ VII Troubleshooting ]
12VDC
(J) (A) 6
4 (C) (B) 5
(I)
(A) (C) 4
M 6
(E) (D) 3
5 2
1 (E) 2
3
(F) (B) (D)
(F) 1
(H)
HWE07120 - 13 - GB
[ VII Troubleshooting ]
2) LEV operation
(a) Close
(b) Open
(b)
(c)
(d)
(e)
When the power is turned on, a pulse signal of 2200 pulses is output (valve closure signal), to bring the valve to position A.
When the valve is operating normally, it is free of vibration noise. If the valve locks or when it goes from point E to A in the
figure, it makes louder noise than would be heard when there is an open phase.
Check for abnormal sound/vibration by placing the metal tip of a screwdriver against the valve and the handle side against
your ear.
3) Troubleshooting
Pulse signals are output for 10 seconds when the main power is turned on. If there
are LEDs that do not light up at all or remain lit after the pulses are turned off, there
is a problem with the driving circuit.
Locked LEV The motor will idle and make small clicking noise if it is run while the LEV is locked. Replace the LEV.
If this clicking noise is heard both when the valve is fully closed and while it is being
opened, it indicates a problem.
Disconnected or easure the resistance between the coils with a tester (red-white, red-orange, Replace the LEV.
shorted LEV motor brown-yellow, brown-blue). The normal range of resistance is 150 10%
coils
HWE07120 - 14 - GB
[ VII Troubleshooting ]
(A)
LEV
Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is
leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly
lower than the inlet temperature on the remote controller, valve closure failure is
suspected. If the amount of leakage is insignificant, replacement of LEV is unnec-
essary unless it is causing a problem.
Misconnections of Perform a visual check for disconnected connectors. Disconnect the con-
connectors or con- Perform a visual check of lead wire color. nectors on the con-
tact failure trol board and
perform a continuity
test.
Normal Abnormal
1
340 Open or short
3
HWE07120 - 15 - GB
[ VII Troubleshooting ]
2. Troubleshooting
Symptom: Indoor unit fan does not run.
Yes
15VDC (same with the voltage between fan connector 5 (+) and 4(-))
1 - 6.5VDC (same with the voltage between fan connector 6 (+) and 4(-))
[Values for Vsp are the values that are measured with the fan motor in operation.
Vsp is 0V when the fan motor is stopped.]
Yes
Yes
HWE07120 - 16 - GB
[ VII Troubleshooting ]
(A)
(B)
ON ON
OFF OFF
1. When using an ME remote controller, set the address with the rotary switches (SW11, SW12).
Address setting is not required when the unit remote controller is used.
On-site address setting is required for the indoor units to run.
3. Address is set with a combination of SW12 (10's digit) and SW11 (1's digit).
To set the address to "3," set SW12 to "0" and SW11 to "3."
To set the address to "25," set SW 12 to "2" and SW 11 to "5."
HWE07120 - 17 - GB
[ VII Troubleshooting ]
HWE07120 - 18 - GB
[ VII Troubleshooting ]
Factory setting
(2) SW3
Factory setting
HWE07120 - 19 - GB
[ VII Troubleshooting ]
3. Model setting
(1) SW4
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
Note:
Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller
off). There is no need to power cycle the unit.
3 2
3 2
3 2
3 2 2
1 (B) 1
2 2 2 2
1 1 1 1 1 1 1 1 SWA SWC
SWA SWC SWA SWC SWA SWC SWA SWC
(A) Option
(B) Standard
Note:
Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation
status (RUN/STOP) or the remote controller status (ON/OFF).
Factory setting
HWE07120 - 20 - GB
[ VII Troubleshooting ]
Factory setting
Note:
Changes to the dipswitches SW11, SW12, SW14, and SW15 must be made while the unit is stopped and the remote controller
is OFF.
HWE07120 - 21 - GB
[ VIII Disassembly Procedure ]
VIII Disassembly Procedure
(A)
Fig.1
Fig.2
HWE07120 - 22 - GB
[ VIII Disassembly Procedure ]
(B)
Fig.3
(2) Pull out the thermistor holder (C) and thermistor (D) on
the control box.
Fig.4
HWE07120 - 23 - GB
[ VIII Disassembly Procedure ]
3. Drainpan
Exercise caution when removing heavy parts.
(D) (E)
Fig.5
2. Removing the drainpan
(1) Pull out the drain pan in the direction of the arrow 1.
Fig.6
Note
Drain the water out of the drain pan before removing
it.
To avoid dew condensation, use insulated screws in (a)
the places marked with circles in Figure 7.
(E)
Fig.7
(a) Insulation material
HWE07120 - 24 - GB
[ VIII Disassembly Procedure ]
(F)
Fig.8
3. Removing the thermistor
(1) Remove the thermistor (G) from the thermistor holder (H)
on the copper tube.
Thermistor size
Liquid pipe: ø8mm
Gas pipe: ø6mm
(G), (H)
Fig.9
HWE07120 - 25 - GB
[ VIII Disassembly Procedure ]
(J)
Fig.10
(a) Tab
2. Removing the punching metal
(a)
(1) Remove the two fixing screws on the punching metal (K)
to remove it.
3. Removing the fan casing (bottom half)
(1) Squeeze the tabs on the fan casing to remove it in the di-
rection of arrow 2.
(K)
Fig.11
4. Removing the motor cable
(1) Remove the motor cable threw the rubber bush.
5. Removing the fan motor and the Sirocco fan
(1) Remove the two motor fixing screws to remove the motor
and the Sirocco fan in the direction of arrow 3.
Fig.12
(2) Remove the four fan case fixing screws to take the top
half of the fan casing off.
Fig.13
HWE07120 - 26 - GB
[ VIII Disassembly Procedure ]
6. Bearing
P40, P50, P63 models only.
Exercise caution when removing heavy parts.
(M)
Fig.14
(2) Remove the two bearing retainer screws to remove the
bearing.
Fig.15
HWE07120 - 27 - GB
[ VIII Disassembly Procedure ]
7. Heat exchanger
Exercise caution when removing heavy parts.
(T)
Fig.16
(T) Pipe support plate
4. Removing the Heat exchanger
(1) Remove the fixing screws on the heat exchanger (S) to re-
move it.
(S)
Fig.17
HWE07120 - 28 - GB
Aug. 2007 HWE07120 New publication, effective Aug. 2007