EXISTING

HYDRANT FIRE PROTECTION SPECIFICATIONS SYMBOL SCHEDULE FIRE PROTECTION GENERAL NOTES
PIPING
1. BUILDING OWNER: 1. PROVIDE A COMPLETE SPRINKLER SYSTEM AND PORTABLE FIRE EXTINGUISHERS AS
KELTIC DIRECTION OF FLOW REQUIRED BY CURRENT BUILDING CODES. PROVIDE ALL SYSTEM COMPONENTS AND
ACCESSORIES REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM
2. CONTRACTOR: PIPE DROP
CONTRACTOR NOT YET DETERMINED, PERMIT TO BE UPDATED WITH INSTALLING PIPE RISE 2. IN LAYING OUT THE SPRINKLER SYSTEM, THE CONTRACTOR SHALL REVIEW THE
CONTRACTOR ONCE PROJECT IS AWARDED CONTRACT DOCUMENTS AND SITE CONDITIONS TO ENSURE THAT PIPING SYSTEMS DO
PIPE TEE UP NOT CONFLICT WITH OTHER BUILDING ELEMENTS. GENERALLY SPRINKLER
3. SITE ADDRESS: PIPE TEE DOWN COVERAGE CONFLICTS SHOULD BE RESOLVED BY THE CONTRACTOR ON SITE BUT
220 PRIOR STREET TS ANY SERIOUS INTERFERENCES SHALL BE REPORTED TO THE ENGINEER PRIOR TO
BUTTERFLY VALVE WITH TAMPER SWITCH
VANCOUVER, BC V6A 2E5 NO COMMENCEMENT OF WORK
ISOLATION VALVE (NORMALLY OPEN)
NC 3. SPRINKLER COUNTS ON THE 'SPRINKLER HEAD LEGEND' REPRESENT THE NUMBER OF
ISOLATION VALVE (NORMALLY CLOSED)
4. WATER SUPPLY INFORMATION: SPRINKLERS SHOWN ON THE DRAWING PLANS. ADDITIONAL SPRINKLERS ARE TO BE
· STATIC PRESSURE: 124.8 PSI CHECK VALVE PROVIDED AS REQUIRED FOR COORDINATION.
· RESIDUAL PRESSURE: 123.7 PSI PRESSURE REDUCING VALVE (PRV)
· AT FLOW RATE: 1200 GPM 4. SPARE SPRINKLERS CABINET AND HEADS ARE TO BE PROVIDED IN THE WATER ENTRY
· WATER SUPPLY DATA PROVIDED BY THE CITY OF VANCOUVER WATER MODEL, STRAINER ROOM AS PER NFPA 13.
+/- 10% (OCTOBER 06, 2020) BACKFLOW PREVENTOR (BFP)
P
5. SIZE TEST & DRAIN VALVES ACCORDING TO THE SMALLEST ORIFICE SPRINKLER ON
PRIOR STREET 5. DESIGN CRITERIA: PRESSURE GAUGE THE CORRESPONDING ZONE.
· NFPA 13 (2013), STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS;
PUMP
FIRE DEPARTMENT · NFPA 10 (2010), STANDARD FOR THE INSTALLATION OF FIRE EXTINGUISHERS; 6. ALL FLOW AND TAMPER SWITCHES ARE TO BE MONITORED BY THE FIRE ALARM
CONNECTION · NFPA 14 (2013), STANDARD FOR THE INSTALLATION OF STANDPIPES; HOSE VALVES SYSTEM.
· VBBL 2019
2 @ 6"Ø WATER MAINS LOBBY ENTRANCE OUTLETS AND DRAINS 7. INSTALL FLEXIBLE COUPLINGS ALONG WITH PIPE SUPPORTS AND SEISMIC RESTRAINT
TO CITY. REFER TO
6'-7" 6. FITTINGS AND JOINTS: AS REQUIRED BY NFPA 13. FLEXIBLE COUPLINGS ARE TO BE PROVIDED AS REQUIRED
CIVIL DRAWINGS FOR 9'-11" BY NFPA 13.
· 25mm - THREADED CAST IRON FITTINGS TO ASME B16.4, CLASS 125 OPEN DRAIN
MORE INFORMATION. · 32mm TO 150mm - LISTED GROOVED COUPLINGS AND FITTINGS COMPATIBLE
WITH THE PIPING MATERIAL 8. PROVIDE LOW POINT DRAINS AS REQUIRED. INCLUDE DRUM DRIP ASSEMBLY IN
AREAS SUBJECT TO FREEZING.
7. PIPE: SYSTEM MONITORING
· WITH THREADED END FITTINGS (25mm) - SCHEDULE 40 STEEL TO ASTM A53 9. LAY OUT DRY SYSTEM PIPING TO SLOPE BACK TO THE SYSTEM MAIN DRAIN WHERE
· WITH GROOVED END FITTINGS (32mm TO 150mm) - SCHEDULE 10 STEEL TO ASTM NEW POSSIBLE AND PROVIDE READILY ACCESSIBLE DRAIN POINTS WHERE REQUIRED.
A53
· BELOW GRADE FDC CONNECTION PIPING TO BE INTERNALLY GALVANIZED FS 10. INSTALL ALL PIPING AS HIGH AS POSSIBLE. VICTORIA VANCOUVER CALGARY
SCHEDUDLE 10 STEEL INSTALLED WITH EXTERIOR PIPE WRAP. FLOW SWITCH T. 250-382-5999 T. 604-684-5995 T. 403-252-2333
F. 250-382-5998 F. 604-684-5993 F. 403-253-3324
FIRE ALARM 11. ENGINEER TO BE NOTIFIED FOR FIELD REVIEWS PRIOR TO COVERING WORK AND 721 JOHNSON ST 200 - 638 SMITHE ST 710 - 1122 4TH STREET SW
ANNUNCIATOR AND P VICTORIA, BC V8W 1M8 VANCOUVER, BC V6B 1E3 CALGARY, AB T2R 1M1
8. PIPE HANGERS: PRESSURE SENSOR 48HRS PRIOR TO CITY OF VANCOUVER ROUGH-IN INSPECTIONS.
67'-11"
CACF · ADJUSTABLE SWIVEL RING HANGERS WITH REDI ROD THAT ARE SEISMICALLY
RATED AND APPROVED FOR SPRINKLER SYSTEMS. 3 8" HANGER ROD FOR PIPE
SIZES UP TO 4"Ø AND 12"Ø HANGER ROD FOR PIPE SIZES 5"Ø TO 6"Ø.
· LOCATION AND SPACING AS PER LISTING AND NFPA 13 OWNER'S RESPONSIBILITIES
FIRE PROTECTION
9. PIPE RESTRAINT:
· REFER TO DETAILS FE 1. IT IS THE OWNER'S RESPONSIBILITY TO ENSURE THAT ADEQUATE HEAT IS PROVIDED
FIRE EXTINGUISHER
· LOCATION AND SPACING AS MARKED ON THE DRAWING PLANS PER NFPA 13 IN ALL AREAS HOUSING WET SPRINKLER SYSTEM PIPING AND/OR SPRINKLER
FIRE DEPARTMENT SIAMESE CONNECTION SYSTEM CONTROL VALVES TO PREVENT FREEZING.
· END OF LINE RESTRAINT: CABLE WIRE WITH FASTENERS AS PER NFPA 13
WARNING: FAILURE TO PROVIDE ADEQUATE HEAT MAY RESULT IN BURST PIPING AND
DRY SPRINKLER ALARM VALVE WATER DAMAGE.
FIRE DEPARTMENT
CONNECTION 220 PRIOR STREET WET SPRINKLER SUPPLY LINE
2. REGULARLY INSPECT, TEST, MAINTAIN ALL FIRE PROTECTION SYSTEMS INCLUDING
DSP DRY SPRINKLER SUPPLY LINE
LOT AREA: 20,430 SQ FT DRY SYSTEM CAPACITY F FIRE LINE TO STANDPIPE
THE SPRINKLER SYSTEM AND PORTABLE FIRE EXTINGUISHERS PER THE BC FIRE
CODE AND THE LATEST EDITION OF NFPA 25 - STANDARD FOR THE INSPECTION,
TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS.
· PARKADE LEVEL P4: 263 USG
· PARKADE LEVEL P3: 256 USG DRAWING TAGS
· PARKADE LEVEL P2: 281 USG
· PARKADE LEVEL P1: 1121 USG
· LEVEL 1-HIGH : 172 USG
- DETAIL NUMBER FIRE PROTECTION DRAWING LIST
M- DRAWING NUMBER
· LEVEL 2: 60 USG DRAWINGS NO. DESCRIPTION SCALE
ISSUED FOR 2022-06-10
NOTE: PARKADE LEVEL P1 SYSTEM TO - SECTION NUMBER FP000 COVER PAGE, DRAWING NOTES AND SYMBOL SCHEDULE AS NOTED CONSTRUCTION STAGE 1
BE PROVIDED WITH A M- DRAWING NUMBER FP100 SCHEMATIC NTS
QUICK-OPENING DEVICE ISSUED FOR 2021-12-08
FP101 DETAILS NTS
STATION STREET

(ACCELERATOR) AND REQUIRES SPRINKLER PERMIT


WATER DELIVERY TESTING PER FP201 FIRE PROTECTION PLAN - P4 1/8" = 1'-0"
NFPA-13 PART 7.2.3 FP202 FIRE PROTECTION PLAN - P3 1/8" = 1'-0" ISSUED FOR TENDER 2021-10-07
FP203 FIRE PROTECTION PLAN - P2 1/8" = 1'-0"
FP204 FIRE PROTECTION PLAN - P1 1/8" = 1'-0" ISSUED FOR BP 2021-09-10
FP205 FIRE PROTECTION PLAN - LEVEL 1 1/8" = 1'-0" REVIEW
FP206 FIRE PROTECTION PLAN - INTERNAL EXIT LEVEL 1 1/8" = 1'-0"
ISSUED FOR 2021-08-04
FP207 FIRE PROTECTION PLAN - LEVEL 2 1/8" = 1'-0" REVIEW
FP208 FIRE PROTECTION PLAN - LEVEL 3 1/8" = 1'-0"
PROPERTY LINE

FP209 FIRE PROTECTION PLAN - LEVEL 4 1/8" = 1'-0" ISSUED FOR 2021-07-22
REVIEW
FP210 FIRE PROTECTION PLAN - LEVEL 5 1/8" = 1'-0"
FP211 FIRE PROTECTION PLAN - LEVEL 6 1/8" = 1'-0"
ISSUED FOR 2021-06-18
FP212 FIRE PROTECTION PLAN - LEVEL 7 1/8" = 1'-0"
PROGRESS
FP213 FIRE PROTECTION PLAN - LEVEL 8 1/8" = 1'-0"
FP214 FIRE PROTECTION PLAN - LEVEL 9 1/8" = 1'-0" ISSUED FOR 60% 2021-05-03
PROPERTY LINE COORDINATION
FP215 FIRE PROTECTION PLAN - LEVEL 10 1/8" = 1'-0"
FP216 FIRE PROTECTION PLAN - ROOF 1/8" = 1'-0" Revisions YYYY-MM-DD
1 SITE PLAN
FP000 SCALE: 1/16"=1'-0" EQUIPMENT LIST
TRUE TYPE MAKE MODEL
NORTH
FLOW SWITCHES POTTER VSR-F
DRY PIPE VALVE VICTAULIC FIRELOCK NXT SERIES 768
AIR COMPRESSOR (COMP-1) SWAN SV-202 C/W 1 HP MOTOR
PL F E D C B A PL PL 1 2 3 4 5 6 7 8 9 PL AIR COMPRESSOR (COMP-2) VICTAULIC SERIES 7C7 C/W 1/6 HP MOTOR
HEAT TRACE CONTROLLER PENTAIR 465 ULC LISTED CONTROLLER
HEAT TRACE CABLE RAYCHEM XL-TRACE
171.34' T.O.PARAPET 171.34' T.O.PARAPET
FIRE DEPARTMENT CONNECTION NATIONAL FIRE MODEL 229 FLUSH MOUNT
BACKFLOW PREVENTER WATTS 3000SE
158.84' E.M.R. 158.84' E.M.R.
FIRE EXTINGUISHER NATIONAL FIRE SF-ABC310 , 5LB
2 1/2" HOSE VALVES - STANDARD NATIONAL FIRE A56
145.67' LEVEL 10 145.67' LEVEL 10

ELEC.

132.50' LEVEL 09 132.50' LEVEL 09


905

HYDRAULIC DESIGN CRITERIA:


GREEN ROOF

119.33' LEVEL 08 119.33' LEVEL 08


MECHANICAL ROOMS, ELECTRICAL ROOMS, PARKADE.
CROSSOVER FLOOR CROSSOVER FLOOR
ELEC.
705 · ORDINARY HAZ. GP1 - DENSITY 0.15 GPM/SQ.FT
106.16' LEVEL 07 106.16' LEVEL 07 · COMBINED HOSE ALLOWANCE 250 GPM

Seal
93.00' LEVEL 06 93.00' LEVEL 06 COMMERCIAL RETAIL, MANUFACTURING, AND STORAGE (STORAGE NOT TO EXCEED 8'-0")
ELEC.
505 · ORDINARY HAZ. GP2 - DENSITY 0.20 GPM/SQ.FT 220 PRIOR
79.84' LEVEL 05 79.84' LEVEL 05 · COMBINED HOSE ALLOWANCE 250 GPM

66.67' LEVEL 04 66.67' LEVEL 04 CORRIDORS, LOBBY, OFFICE LEVELS, AMENITY ROOMS
ELEC.
305 · LIGHT HAZ. - DENSITY 0.10 GPM/SQ.FT
· COMBINED HOSE ALLOWANCE 100 GPM
53.50' LEVEL 03
CROSSOVER FLOOR
53.50' LEVEL 03
CROSSOVER FLOOR 220 PRIOR STREET
ELEC.
205

35.50' LEVEL 02 35.50' LEVEL 02


VANCOUVER, BC
Project
AV

9'
G

.9
G

m : 13
COVER PAGE,
R
AD
15.50' LEVEL 01 15.50' LEVEL 01

65 EL
EL: 15.50' EL: 15.50' EL: 14.40'
(4

EL:14.00'

)
E

(4 DE
.2

EL
65

A
:1

.2
R
m

G
3.9
)

G
9'

AV
EL: 11.20'

EL: 6.69'

-2.17' PARKING P1 -2.17' PARKING P1


EL: -1.17'
EL: 2.23'

EL: -3.86'
DRAWING NOTES
-11.51' PARKING P2
CROSSOVER FLOOR
-11.51' PARKING P2
CROSSOVER FLOOR
EL: -10.51'
EL: -13.20'
AND SYMBOL
-20.85' PARKING P3 -20.85' PARKING P3
EL: -19.85'
EL: -22.53'
SCHEDULE
EL: -29.20'
-30.20' PARKING P4 -30.20' PARKING P4
Drawing

Scale AS NOTED

Project 362b-001-20
1 BUILDING SECTION A 2 BUILDING SECTION B
FP000 SCALE: 1/32"=1'-0" FP000 SCALE: 1/32"=1'-0"
Sheet FP000