STAIR 2
MANUFACTURING
BELOW
24" DP
DESIGN AREA NUMBER : 9
DESIGN AREA LOCATION : LEVEL 1 HIGH
HAZARD/OCCUPANCY : ORDINARY HAZARD G2
DESIGN DENSITY : 0.20 GPM/FT²
DESIGN AREA : 1532 FT²
NUMBER OF SPRINKLERS IN DESIGN AREA : 19
24" DP
ISSUED FOR 2021-07-22
GARBAGE /
REVIEW
RECYCLING
BELOW
FE
ISSUED FOR 2021-06-18
4"Ø DRY
EXIT EXPOSURE PROGRESS
SYSTEM
HEAD, 3FT FROM FROM P1
DEMISING WALL, 6-12 ISSUED FOR 60% 2021-05-03
INCHES FROM PLANE COORDINATION
OF GLAZING
Revisions YYYY-MM-DD
HEADS AND
SPRINKLER LINE TO STAIR 3 HYDRAULIC CALCULATION DATA
RUN BELOW STAIR EXIT BELOW 30" DP
D PRESSURIZATION
DUCTWORK 24" DP D
DESIGN AREA NUMBER : 5
DESIGN AREA LOCATION : LEVEL 1 HIGH
HAZARD/OCCUPANCY : ORDINARY HAZARD G2
DESIGN DENSITY : 0.20 GPM/FT²
DROP BRANCH LINES DESIGN AREA : 2106 FT²
BELOW GENERATOR NUMBER OF SPRINKLERS IN DESIGN AREA : 8
EXHAUST
SYSTEM FLOW : 561.81 GPM
SYSTEM PRESSURE : 86.40 PSI
ROLL UP GARAGE
HOSE ALLOWANCE (INCLUDED ): 250 GPM
DOOR
SYSTEM DEMAND: 811.81 GPM
SAFETY MARGIN: 25.31 PSI
²
DRY SPRINKLER ZONE PROTECTED TO
HEADS ON SPRIGS NFPA-13 HAZARD CLASS:
UP TO 10" BELOW PARKADE GARBAGE ROOMS - O.H.1
SLAB (TYP. FROM LOADING DOCK - O.H.2
LOW BRANCH LINE) VESTIBULE - L.H
E E Seal
220 PRIOR
STAIR EXIT CORR. GENERATOR INSPECTOR
STAIR04
4 TEST DRAIN
BELOW
GARBAGE/RECYCLING
BELOW
220 PRIOR STREET
VANCOUVER, BC
F F Project
FIRE PROTECTION
2HR RATED EMERGENCY
GENERATOR ROOM.
PLAN - INTERNAL
EXTRA HAZ. GROUP 1
MAX 130SQ.FT PER HEAD
EXIT LEVEL 1
SPRINKLER HEAD LEGEND
SYMBOL MAKE MODEL S/N POSITION RESPONSE FINISH TEMP K NPT QUANTITY COVERAGE
1 FIRE PROTECTION PLAN - INTERNAL EXIT LEVEL 1 TYPE SUBTOTAL AREA Drawing
FP206 SCALE: 1/8"=1'-0"
TYCO EC-14 TY6137 UPRIGHT QUICK BRASS 155°F 14 3/4" 36 18' x18' MAX COVERAGE
Scale 1/8" = 1'-0"
TYCO TY-FRB TY3131 UPRIGHT QUICK BRASS 155°F 5.6 1/2" 53 130 sq.ft
VIKING 06662BA-X VK302 CONCEALED PENDENT QUICK BRASS 155°F 5.6 1/2" 27 175 sq.ft Project 362b-001-20
FP206
TOTAL SPRINKLER COUNT: 116