Professional Documents
Culture Documents
A A
FE PROVIDE NON-EXTENDED
COVERAGE HEADS BELOW
COMM. ROOM MAIN ELECTRICAL
SPRINKLER PIPE RACKING
P1-11 P1-12 EXCEEDING 4' IN WIDTH
FE
)
YP.
(T
4"Ø UP TO FDC
CONNECTION FE
UTILITY ACCESS
P1-14
FE ISSUED FOR 2022-06-10
CONSTRUCTION STAGE 1
C C ISSUED FOR 2021-12-08
SPRINKLER PERMIT
BIKE STORAGE
WOMENS CHANGE ROOM ELEV
P1-09 ISSUED FOR TENDER 2021-10-07
P1-06 1
HATCH DENOTES LINE OF UP
19" SLAB STEP AT 2021-09-10
ISSUED FOR BP
PERIMETER OF BUILDING REVIEW
ABOVE. REFER TO
STRUCTURAL.
ISSUED FOR 2021-08-04
REVIEW
ELEV
EOT LOBBY 2 ISSUED FOR 2021-07-22
P1-16 REVIEW
STAIR 03
UNIVERSAL CHANGE ROOM FE BIKE STORAGE
P1-03
P1-07 ELEV. LOBBY P1-10 ISSUED FOR 2021-06-18
FE INSTALL
P1-01 PROGRESS
SPRINKLER
BAFFLE, EL.-1.42' ELEV
MIN 8"x6" ISSUED FOR 60% 2021-05-03
(-0.43 m) 3 COORDINATION
DN
MENS CHANGE ROOM 4"Ø , 12'-2"
P1-08 UP TO L1 Revisions YYYY-MM-DD
C.O. VEST.
P1-05
SERVICE RM
P1-02
D FE
D
FE
4"Ø UP TO
L1 DRY
SYSTEM
SECURITY FOR
ELEVATOR LOBBY.
STORM RETENTION SPRINKLERS SPACED
TANK (NIC) 6FT ON CENTRE,
GLAZING FOR LOCATED
VESTIBULE DOOR. 6" TO 12"
SPRINKLERS PERPENDICULAR TO
FE LOCATED GLAZING AS PER
6" TO 12" VBBL 3.3.7.7.
PERPENDICULAR TO
GLAZING AS PER
E P104 VBBL 3.3.7.7. E Seal
EL.-1.42'
INSPECTOR
220 PRIOR
TEST DRAIN
.) -6
YP 0
(T ring
S
220 PRIOR STREET
STAIR 04
P1-04 VANCOUVER, BC
F F Project
FIRE PROTECTION
PLAN - P1
SPRINKLER HEAD LEGEND
SYMBOL MAKE MODEL S/N POSITION RESPONSE FINISH TEMP K NPT QUANTITY COVERAGE
1 FIRE PROTECTION PLAN - P1 TYPE SUBTOTAL AREA Drawing
FP204 SCALE: 1/8"=1'-0" TYCO EC-14 TY6137 UPRIGHT QUICK BRASS 155°F 14 3/4" 59 18' x18' MAX COVERAGE
Scale 1/8" = 1'-0"
TYCO TY-FRB TY3131 UPRIGHT QUICK BRASS 155°F 5.6 1/2" 33 130 sq.ft
VIKING 06662BA-X VK302 CONCEALED PENDENT QUICK BRASS 155°F 5.6 1/2" 17 225 sq.ft Project 362b-001-20
FP204
TOTAL SPRINKLER COUNT: 109
Sheet