Professional Documents
Culture Documents
Abstract
Daylight represents a free source of illumination of building’s internal spaces. For the right and optimal use of this resource, in addition
to the resort to some simple designing expedients that can be brought back to the practice of “building in a workmanlike manner”, it
is possible to adopt specific devices able to improve the sunlight captation. Among these devices a class that presents a very interesting
compromise between simplicity of realization, costs and daylighting performances is represented by the so-called “light pipes”. Light pipes
usually work by means of a device placed on an external closing element which attends to collect, redirect and in some cases, concentrate or
collimate the incident luminous flux, and a device situated inside the environments able to transport the daylight inwards the building and
distribute it into the deep zone of the rooms so as to obtain a better illuminance distribution. In this work, we propose a light pipe equipped
with a flat captation system suitable to be integrated in a building’s facade, without any protrusion as to the architectural envelope.
This system includes: a planar closing element, a sunlight’s collecting and deflecting device that optimizes the direction of the incoming
solar rays as the solar position varies, a rectilinear duct with optical properties suitable for the transport of the sunlight and for its introduction
into the room that has to be illuminated.
The daylighting performances are simulated in different conditions of external illuminance and it is done an assessment of the lighting
energy savings in a test room simulating a class room. At the end, some considerations and applying indications useful for the designer
are presented.
© 2004 Elsevier B.V. All rights reserved.
0378-7788/$ – see front matter © 2004 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2004.05.001
1164 R. Canziani et al. / Energy and Buildings 36 (2004) 1163–1176
Fig. 1. (a) Average work plane illuminance profile with (a) sidelighting and (b) light pipe.
energy balance; indeed, in addition to the electric power 2. The proposed light pipe
directly employed for lighting, a remarkable portion is
consumed by cooling systems to get rid of the thermic loads In this work, a device is set up to make available natural
produced by the illuminating devices inside the rooms. luminous radiation inside, paying particular attention to ob-
This trend is particularly emphasized in those buildings tain a luminous environment suitable for a comfortable use
that are employed for the services sector (directional and of the rooms, either in terms of quantity and mostly of qual-
commercial buildings, schools, hospitals, sporting installa- ity. On the other side, the control of energy exchanges with
tions, community’s buildings, etc.) where it is very frequent the external environment have not been neglected, by reduc-
the discarding of the building envelope as light source, and ing transparent openings. The research soon turned to obtain
the creation of an internal environment totally artificial, even a component responding to the following characteristics:
during daytime.
• capability of attenuation of the illuminance gradient be-
On the other hand, the prevalence of compact constructive
tween the deepest zones of the rooms and those ones close
typologies having great depth and side openings with low
to the openings;
transparency glazing necessarily causes a quick decay of
• control of the direct solar component and glare’s potential
the daylighting’s level in the environments, as the distance
phenomenon;
from windows increases; in fact, the depth of the adequately
• possibility of exploiting the daylighting’s potential of en-
lighted area rarely exceeds twice the height of the openings
ergy saving, both in terms of reduction of the electric
(Fig. 1a).
power’s consumption for the artificial lighting, and in
Over the last decades, the statement of the so-called
terms of reduction of thermic loads;
“energy-conscious architecture” also produced the develop-
• ease of integration in the building, by the containment of
ment of a new planning methodology in which, besides the
the section’s dimensions;
technics of solar-heating and passive cooling, daylighting
• possibility of use also in pre-existent structures, as im-
rational exploitation assumes a role of primary importance;
proving solution of the conditions of environments’ lumi-
for this aim, sophisticated systems and technics of daylight-
nous comfort;
ing have been studied and developed to control the intensity
• possibility of an adequate degree of compositive integra-
of the solar radiation, its internal distribution as well as the
tion with the canonical elements of architecture by the
energetic gains and losses, improving at the same time, the
dimensional reduction of the external opening and the
comfort and the visual performances of the environments
maintenance of facade’s planarity;
[4–7]. The most recurring approach is represented by the
• constructive and functional simplicity to contain the costs
sunbeam’s controlled deviation, which is directed towards
of realization and management.
the ceiling of the rooms to be successively spread, more
or less uniformly, all over the room; this field also com- Altogether, these considerations brought to the design of
prises the advanced systems of daylighting’s collection and the device represented in Fig. 2. The reported measures are
transport, named light pipes: they usually work by means of no absolute value, since there is an interdependence be-
of a device placed in the external end that intercepts, devi- tween the light pipe’s geometry and that one of the room
ates and sometimes concentrates or collimates the incident in which it has to be used, but they refer to an application
beam, which is subsequently directed towards the deep- in a standard test room 7 m width × 11.5 m depth × 3.5 m
est area of the rooms to get the best distribution of the ceiling height; in any case, similar reasonings and conclu-
illuminance.(Fig. 1b). sions are obviously possible by proper geometric modifica-
This project is included in this field of research, having tions. The device’s definition was carried on starting from a
as object the design of one of these lighting devices, able to basic idea and varying both dimensions and physical prop-
collect and adequately convey the sunlight into the deepest erties of materials and verifying the obtained performances
areas of the rooms, and the assessment of its performances. by numerical simulation.
R. Canziani et al. / Energy and Buildings 36 (2004) 1163–1176 1165
Light pipe’s specific peculiarity is to carry out the trans- needed to collimate the oblique sunbeam in cases of solar
port of the daylight in horizontal direction allowing, there- positions not in axis with the pipe. The chamber is coated
fore, its use in every south-facing room. It has a transversal with a highly reflecting film (total reflectance ρt = 0.95,
section of trapezoidal shape (in fact, the sides are tilted of specular reflectance ρs = 0.92).
2◦ with regard to the base’s normal direction), that varies in
its dimensions according to the distance from the external 2.2. Reflector
opening, which has an area equal to only 0.29 m2 (0.27 m ×
1.07 m); the diffusion of the collected light inside the room It is the device that collects and redirects solar rays; it
is secured by a series of nine openings, different in sizes, for belongs to the category of active daylighting components,
a total area of 24.7 m2 . The openings are placed beginning since it varies its inclination according to the incident sun-
from a distance of 2.6 m from the external opening, in such beam angle determined by the different sun’s positions dur-
a way as to increase the uniformity’s level in the work plane ing the day and the seasons, covering a set of positions which
illuminance distribution. The whole device has a shape with starts from an inclination approximately equal to 7◦ (Fig. 4,
an overall height less than 0.5 m so as to be quite easily 12/21, 09:00 a.m./03:00 p.m.), till an inclination equal to
fitted into the technical spaces also available for the other 36.7◦ (Fig. 5, 6/21, 09:00 a.m./03:00 p.m.).
plants’ ducts, and in any case to allow an application also
for lighting refurbishment of pre-existing buildings, by the 2.3. Diffusing chamber
realization of a simple false ceiling.
In fact, the designed device, rather than a single compo- It is used to spread the light collimated by the reflector and
nent, is a system of components for daylighting, since it is by the reflecting chamber towards the inner openings, and
made of a set of distinct parts that differ in functions and has a longitudinal section slightly tapered towards the bot-
physical–optical properties; these parts are separately ex- tom of the room; this expedient has been taken to compensate
plained and illustrated in detail in Fig. 3. the decay of the luminous flux; it is coated with a perfectly
diffusing material, with a reflectance equal to ρd = 0.9.
2.1. Reflecting chamber
2.4. Glazing openings
It is the area where the sunbeam is collected and redi-
rected inwards, thanks to the combined actions of the active The outer opening is closed by a simple glazing with
reflector and of the chamber’s walls; its sides continue into a transmittance coefficient equal to τ = 0.86; on the in-
the inner chamber named diffusing chamber, since they are ner openings, there are two types of translucent diffusers
1166 R. Canziani et al. / Energy and Buildings 36 (2004) 1163–1176
Fig. 3. Light pipe’s components: (a) reflecting chamber; (b) reflector; (c) diffusing chamber and (d) glazing openings.
perfectly diffusing (Fig. 3d); the first one includes six ele-
ments (grey colour) with a transmittance of τ d = 0.88, while
the second one formed by the three openings of black colour
has a transmittance equal to τ d = 0.35; the area that over-
hangs these last three openings corresponds to the zone of
incidence of the sunbeam collimated by the reflector, there-
fore, requesting the control of the luminous energy’s peaks
that are present.
It is worth considering the reflector in detail. As al-
ready mentioned, the starting idea was not to realize a
dynamic device, since it was in contrast with the proper-
ties of functional and constructive simplicity which had to
be kept in the device; however, the performed simulations
Fig. 4. Reflector winter limit conditions.
shown the difficulty to control the uniformity of the inter-
nal illuminance in case of employment of fixed reflecting
systems as well as a very poor performance with oblique
sunbeams.
Therefore, the necessity of a dynamic device of reflection
and collimation of the incident sunbeam came out, and we
tried to solve it in the less sophisticated possible way (Fig. 6).
The adopted solution consists of a reflector formed by a
metal sheet (aluminum, for example) with a thickness ade-
quate to sustain the traction’s efforts, which are extremely
limited, and to guarantee the flexibility needed for the mo-
bile device’s operation. This sheet is constrained along an
edge to the frame of the pipe’s external opening, and at
the other end, to a flat bar connected to two springs, that
serve to maintain the right tension’s degree of the sheet itself
(Fig. 7). Fig. 5. Reflector summer limit conditions.
R. Canziani et al. / Energy and Buildings 36 (2004) 1163–1176 1167
Fig. 10. Sun angle chart and simulated cases (latitude, 45.5◦ N, Venice).
R. Canziani et al. / Energy and Buildings 36 (2004) 1163–1176 1169
Table 1
Monthly average illuminance and daylight factor values with and without light pipes
Month Em,i (lx) Percentage difference fmed (%) Percentage difference
For a complete evaluation of the illuminating device’s average values are essentially the same (approximatively,
performances, we analyzed the yearly pattern of the single 350 lx), while the monthly ones present light differences. In
luminous environment’s parameters: average work plane il- particular, proposed system has better performances than the
luminance (Em,i ), average daylight factor (fmed ), illuminance reference model in February, March, April, August, Septem-
gradient factor (IGF = Ei,a /Ei,p ); average work plane illu- ber and October, while its results are worse in the remaining
minance, measured dividing the room in two areas, the first months, especially in June. The obtained average daylight
one starting from the glazing openings till a depth of 5 m factor has the same annual behaviour of the average illumi-
(Ei,a ), and the second one included between 5 and 11 m from nance and in both cases the yearly average value is equal to
the window (Ei,p ). 3% (Table 1).
To allow a general evaluation of the above-mentioned pa- The flexion of the performance in the year’s central
rameters, we considered the average value that they assume months is due to the reduced useful reflection area that is
during the sequence of the considered 6 h (from 09:00 a.m. determined on the mobile reflector with high sunbeam’s in-
to 03:00 p.m.), for every month of the reference year. The cidence angles (Fig. 11); the designing constraint of respect
results obtained in the test room with and without the light of the facade’s planarity, in fact, determines a fairly lim-
pipes and the percentage difference between the two situa- ited penetration of the sunlight that joined with the scarce
tions are reported in Tables 1 and 2. As shown by Table 1, transmission’s coefficient of the glazing surface at the high
the absolute values of average work plane illuminance, mea- angle of incidence cause a drastic reduction of the energy
sured in the room with the light pipes, substantially collimate useful to the aim. It would easily have been possible to rem-
with those ones obtained by the reference room; the yearly edy for this scarcity appropriately modifying the opening’s
Table 2
Monthly average values of the average illuminance in the zone distant from the window Ei,p and in the zone close to the facade Ei,a
and reflecting system’s geometry, inclinating, for example, of light pipes (test room), is lower of 62% than the one ob-
the pipe’s extremity so as to increase the useful sunbeam’s tained by the reference room (3,7 contrary to 9,6, therefore,
reflecting area on the reflector. less than half); during the whole year, it is always below the
To avoid overhangs and/or recesses on the facade, the sys- reference one, getting near to it only in June. It can be seen
tem of active collimation would be thought over, and this as, in the reference room, the highest values are obtained in
would have brought to a certain increase of its complexity; winter months, while with the proposed system, the gradient
the performance deficit was accepted, also in consideration is higher in the summer ones and approximately constant in
of the highest probability of days with clear sky with sun that the remaining months (Fig. 12).
takes place in those months in which the illuminant device Afterwards, also we analyzed the average illuminance ob-
does not offer the best performance. The above-mentioned tained on the work plane in the deeper area of the room
results demonstrate, therefore, that the room illuminated (Table 2). It can be noticed that in May, June and July, the
with the light pipes provides in practice the same perfor- average illuminance level drops to approximatively 200 lx,
mance, in quantitative terms of the reference room, in spite in opposition to an annual average value of 310 lx (as re-
of the reduction of the glazing area. gards the 178 lx obtained in the reference case, therefore,
Analyzing, on the contrary, the annual trend of those pa- with an increment equal to 74%).
rameters that can be characterized as indicators of luminous In spite of this, the system’s performance keeps itself on
environment’s quality and uniformity, it is clearly shown the acceptable levels showing, however, an increment as regards
disparity of performance of the two solutions and the supe- the reference case approximately equal to the 12%; further-
riority of the proposed system. First of all we analyzed the more, it has to be shown the sharp improvement of the lumi-
trend of the illuminance gradient (IGF) and the results are nous field obtained in the zone immediately contiguous to
shown in Fig. 12. The gradient that we obtained by the use the opening (Table 2); the average illuminance level, in fact,
12.0
10.0
reference
IGF
8.0 room
4.0
2.0
0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Month
Fig. 13. Average work plane illuminance profile during the equinoxes (09:00 a.m./03:00 p.m.).
Fig. 14. Average work plane illuminance profile during the equinoxes (10:00 a.m./02:00 p.m.).
lowers of the 31% as regards the reference case, settling on contribution supplied by the light pipes expressed by the
absolute values close to 400 lx and allowing the controlled attenuation of the illuminance level’s decay in the deeper
fruition of the daylighting radiation during the whole year. area of the room; it can also be noticed the appreciable
In Figs. 13–16, there is a further description of the system’s performance also when the sunbeam is oblique as
system’s performances in terms of average illuminance on regards the light pipes (typical situations of the morning
the work plane along the longitudinal middle section of the and the afternoon hours, Figs. 13 and 14), while it results
room; they refer to the equinox days (3/21, 9/21) and show maximum in the central hours of the day, that is to say with
the difference of behaviour of the room provided with the azimuth angles close to zero (Figs. 15 and 16).
light pipes as to the reference one, without the light pipes. The uniformity of the luminous field on the whole work
By comparison of the results, it is possible to appreciate the plane appears also more evident in Fig. 17, which permits
Fig. 15. Average work plane illuminance profile during the equinoxes (11:00 a.m./01:00 p.m.).
1172 R. Canziani et al. / Energy and Buildings 36 (2004) 1163–1176
Fig. 16. Average work plane illuminance profile during the equinoxes (12:00 a.m.).
in addition to the quantitative analysis by the isolux lines, immediately contiguous to the window. The proposed solu-
also an immediate visual valuation of the luminous comfort tion permits, therefore, to adequately answer to the comfort
level expressed in the two different cases. The employment requisites requested by the demanding visual tasks typical
of the light pipes allows, on one side, the exploitation of of the non-residential buildings, without necessarily resort
the daylighting component in the deepest zone of the room, to internal shading device (as curtains, Venetian blinds or
and on the other one, the reduction of the illuminance gradi- similar, manually or automatically controlled), frequently
ent through the attenuation of the luminous level in the area used.
Table 3
Performances and characteristics of the artificial lighting considered
Minimum work plane illuminance (lx) 410
Maximum work plane illuminance (lx) 561
Average work plane illuminance (lx) 504
Uniformity ratio, Emin /Emed 0.81
Utilization coefficient 0.45
Maintenance coefficient 0.85
Table 4
Comparison of the total values of needed luminous flux from January to June
Model January February March April May June
Reference room 88638 80512 59185 81642 56639 67370 φt,τ (lm)
Test room 58889 85951 54239 50857 59196 71908 φt,τ (lm)
Reference room 85 88 72 69 66 66 L (%)
Test room 58 63 52 57 56 68 L (%)
Reference room 86 89 74 72 68 68 P (%)
Test room 62 66 57 61 60 71 P (%)
Reference room 196 213 194 148 178 170 Cel,i (kWh)
Test room 141 158 149 125 157 178 Cel,i (kWh)
−28 −26 −23 −15 −12 +4 ∆ (%)
Table 5
Comparison of the total values of needed luminous flux from July to December
Model July August September October November December
Reference room 55744 52835 54081 84263 93662 89823 φt,τ (lm)
Test room 58708 48399 45813 49240 73198 68640 φt,τ (lm)
Reference room 58 54 62 84 92 86 L (%)
Test room 56 46 44 47 70 65 L (%)
Reference room 62 60 66 86 93 87 P (%)
Test room 60 52 50 53 72 68 P (%)
Reference room 148 137 158 216 212 168 Cel,i (kWh)
Test room 144 118 120 133 164 132 Cel,i (kWh)
−3 −13 −24 −38 −23 −22 ∆ (%)
level obtainable with larger openings and assuring, therefore, the negative thermic fluxes of exchange with the external
in any case, a control of the summer thermic loads and a environment.
strong reduction of the winter ones. In terms of visual comfort, the advantages offered by the
light pipe’s device are evident: the values of the illuminance
gradient on the work plane and the values of the illumi-
5. Conclusions nance in the deeper zone of the room have shown the right
distribution and uniformity of the luminous field that is an
The focal point in the exploitation of the potential of essential condition to obtain an adequate level of luminous
daylighting’s energy saving is located in the redefinition and comfort and to prevent and reduce the visual fatigue. The
optimization of the glazing element that must not only be performed simulations have demonstrated that this group of
delegated to the captation of the sunbeam but also to its dynamic devices of daylighting’s exploitation has a potential
control and to the correct distribution of the light in the en- of energy saving, both electric (energy for artificial lighting)
vironment, in accordance with the requested characteristics and thermic (energy for heating and cooling of the environ-
of comfort. ments); in addition, they are able to avoid the appearance of
As it also come out from the results of this study, the phenomena such direct irradiation, glare, overheating and to
light pipes consent to optimize the dimensions of the glazing uniformly distribute the illuminance, optically modulating
openings in relation to the wished conditions of thermic and the contrast ratios and assuring an adequate luminous com-
visual comfort in such a way as to exploit to the utmost the fort. A possible development that could improve the pipe’s
natural light for lighting and, at the same time, to reduce efficiency is the improvement of the reflector, realizing a
1176 R. Canziani et al. / Energy and Buildings 36 (2004) 1163–1176
much more efficacious reflecting device from the optical [7] G. Courret, J.L. Scartezzini, D. Francioli, J.J. Meyer, Design and
point of view, no more only for the sunbeam’s collimation assessment of an anidolic light-duct, Energy and Buildings, vol. 28,
1998.
but also for its concentration. In this way, it could be pos- [8] G. Ward Larson, R. Shakespeare, Rendering with Radiance—The Art
sible to obtain an acceptable contribution also in overcast and Science of Lighting Visualization, Morgan Kaufmann Publishers,
conditions exploiting for example, the anidolic systems [7]. San Francisco, USA, 1998.
[9] Opticad Corporation, OPTICAD User’s Guide, Santa Fè, USA, 1999.
[10] A. Grynberg, Comparison and Validation of Radiance and Superlite,
LBNL, Berkeley, USA, 1988.
References [11] A. Grynberg, Validation d’un programme de simulation d’eclairàge:
radiance, LBNL, Berkeley, USA, 1989.
[1] P. Brunello, Prestazioni termiche ed illuminotecniche delle finestre, [12] A.B. Khodulev, E.A. Kopylov, Physically Accurate Lighting Simu-
in: Proceedings of the Conference “Edilizia e Ambiente”, Trento, lation in Computer Graphics Software, Moscow, USSR, 1996.
Italy, 1998. [13] J. Krockmann, M. Seidl, Quantitative data on daylight for illu-
[2] A. Carbonari, G. Rossi, P. Romagnoni, Optimal orientation and minating engineering, Lighting Research and Technology 6 (3)
automatic control of external shading devices in office buildings, in: (1974).
Proceedings of the PLEA 2001, Florianópolis, Brazil, 2001. [14] A. Biasi, Disponibilità locale di luce naturale: un modello per rapp-
[3] A. Carbonari, G. Rossi, P. Romagnoni, Control logic to minimize resentare il sito di Verona, Degreee Thesis, Istituto Universitario di
energy needs for shading devices integrating PV cells, in: Proceedings Architettura di Venezia, AA 1998–99.
of the PLEA 2001, Florianópolis, Brazil, 2001. [15] UNI, UNI 10380-Illuminazione di interni con luce artificiale, Milano,
[4] L.O. Beltran, E.S. Lee, S.E. Selkowitz, Advanced optical daylighting Italy, 1994.
systems: light shelves and light pipes, in: Proceedings of the IESNA [16] N. Hopkirk, J. Stoffel, Adeline 2.0, User’s Manual, International
Annual Conference, Cleveland, USA, 1996. Energy Agency, 1996.
[5] S. Selkowitz, E.S. Lee, Advanced fenestration systems for improved [17] R. Sullivan, E.S. Lee, S. Selkowitz, A method of optimizing solar
daylight performance, Building Technologies Department, LBNL, control and daylighting performance in commercial office buildings,
Berkeley, USA, 1998. LBNL, 1992.
[6] M. Smart, J.A. Ballinger, Tracking mirror beam sunlighting for deep [18] S. Selkowitz, J. Schuman, Integrated envelope and lighting technolo-
interior spaces, Solar Energy, vol. 30, 1983. gies for commercial buildings, LBNL, 1992.