Professional Documents
Culture Documents
CT Connection For Transformer Differential Protection - PAC Basics
CT Connection For Transformer Differential Protection - PAC Basics
Reference
The previous discussion on the transformer vector group showed how transformer connection can cause
phase displacement between the HV and LV winding. This phase displacement will result in the
misoperation of differential protection if left uncompensated. In this article, CT connection for transformer
differential protection will be discussed. The analysis of different CT connections will be presented in order
to lay down the basis for the matrix equations used in modern numerical relays.
尊重您隐私的广告
Phase Angle Compensation by CT Connection
Figure 1 shows a wye-delta transformer connection of vector group YNd11.
Based on the previous discussion, the connection shown in figure 1 indicates that the LV winding leads the
HV winding by 30°. Figure 2 shows a delta-wye transformer connection of vector group Dyn1. This
connection indicates that the LV winding lags the HV winding by 30°.
This phase shift needs to be compensated to avoid the misoperation of the differential protection. Phase
compensation is done by means of wiring current transformers either delta or wye, or through internal
relay compensation in numerical relays. To do just that, CTs are wired such that the 30° phase shift is
reversed. This is shown in figure 3.
It can be seen from the CT connection for transformer differential protection that wye-connected CTs are
used in the delta side of the transformer while CTs on the wye side of the transformer is DAB-connected.
Using DAB-connected CTs, secondary currents seen from the relay will lead the actual currents by 30°, thus
offsetting the 30° phase displacement (LV lagging HV) introduced by the transformer vector group Dyn1.
We can then calculate the secondary currents seen from the relay,
With the measured secondary currents displaced at 180°, the differential (operate) current, IOP, will yield a
value equal to zero. See discussion on The Operate Quantity.
Doing the same for IBW2 and ICW2, we can obtain a matrix that relates the actual currents to the secondary
currents seen from the relay. The derived matrix represents how DAB-connected CTs compensate for a 30°
phase angle displacement in a Dyn1 transformer.
Without compensation, secondary currents seen from the relay are displaced by 150°. This would yield an
IOP ≠ 0 during normal operation. To do phase compensation numerically, we use the previously derived
matrix to solve for IAW2C, IBW2C, and ICW2C. Since our CTs are wye connected, we can see that IAW2, IBW2,
and ICW2 are equal to Ia, Ib, and Ic, respectively.
After the phase angle compensation using the derived matrix equation, the secondary currents seen from
the relay are now displaced by an angle of 180° and will result in a differential (operate) current, IOP, equal
to zero.
This phase angle displacement may result to a differential (operate) current if left uncompensated
Phase angle compensation is conventionally done by connecting CTs either in wye or delta so as to
compensate for the phase angle displacement
Numerical relays provides flexibility by using matrix equations to compensate for angle
displacement instead
Reference
SEL-387A Instruction Manual. Available in SEL, Inc. website.
Prev Next
Related Articles
Thank you Engr. Luciano Mercado. Your lessons are very valuable. We appreciate you for
sharing these for free.
Loading...
Reply
Hi Sir Tope,
Thank you for the support! Your comment is very much appreciated.
I am hoping that the knowledge we share through this website will reach a lot of people.
Loading...
Reply
Email Address
Subscribe