Znatok
Member
Hi, folks, Running into a small problem here. I currently have two two redundant AB CLX processors talking to the SLC 5/05 via a built-in SLC Ethernet port (connected by copper to a switch and then via fiber to another switch, and then copper to the AB 1756-ENBT cards of the CLX processors). SLC is the master and reads/writes to the CLX via MSG instructions (16 total, with a maximum of 8 running at any given time). The system is working OK, however, I get random (not periodic!) Ethernet hardware faults on the SLC (fault code
Join Date: Oct 2005 Location: Orenburg You are not registered yet. Please click here to register!
You are not registered yet. Please click here to register! Posts: 1 A2h). AB manual states that this fault is unique to the SLC
5/04 - 5/05, and that this fault can be cleared by writing to the status file, but the communications would only restore once the power of the SLC is cycled. Just curious, if anyone has ever had similar problem before and how it was corrected (if it was). I'm just not sure whether simple replacement of the SLC processor (as recommended by AB TechSupport) would help.... Any help is very much appreciated. Thanks, Alexei
#2
Alan Case
Find it hard to believe that replacing a working processor will fix the fault. How are the messages staged, ie are they getting enough time to complete or are you sometimes filling a buffer. Regards Alan Case
#3
Ken Roach
Error code 0xA2 covers several different possible failures of the Ethernet daughtercard on the SLC-5/05, including firmware crashes and hardware failures. You can get more detail from the Status file for the Ethernet channel; RA technical support can walk you through how to capture that information after a controller crash. The Ethernet LED on the SLC should also flash in a repeating pattern; slow flashes for the first digit of the failure code, fast flashes for the second digit. If your controller has failed multiple times, I tend to think that you have a defective Ethernet daughtercard and you're going to need to eventually replace the controller anyhow. If it were me, I'd also add an Ethernet sniffer (www.ethereal.com) to the system and see if I could capture the last traffic between the SLC and the Logix to see if it is somehow different from the other messages sent between the two. But then, that's me.
Bookmarks Twitter Reddit Digg del.icio.us StumbleUpon Google Previous Thread | Next Thread
Posting Rules You You You You may may may may not not not not post new threads post replies post attachments edit your posts
Similar Topics
Thread SLC 5/05 Ethernet Problems AB SLC 5/05 Ethernet MSG Errors SLC 5/05, RSLinx & Ethernet problem Strange fault on SLC 5/05 system. Serial to AB Ethernet SLC 5/05 Thread Starter dilkep Forum LIVE PLC Questions And Answers Replies 44 Last Post December 27th, 2009 07:30 PM January 20th, 2009 12:10 PM February 6th, 2008 11:46 AM June 1st, 2006 03:02 PM June 10th, 2003 07:28 PM
mrdegold
hhuong
93lt1
11
ndzied1
All times are GMT -5. The time now is 07:27 AM. Contact Us - PLCS.net - Text - Top .