Professional Documents
Culture Documents
xxx/ALG
SIEMENS
Ventilation V3.xx
SAPHIR
Basic Documentation
Siemens Building Technologies AB © 2001 Siemens Building Technologies AG
HVAC Products, OEM Med förbehåll för ändringar
Eletronvägen 4
141 87 Huddinge
Tel. +46 8 578 410 00
Fax +46 8 578 419 92
www.landisstaefa.se
2/164
2 Handling ........................................................................................................ 18
Installation ..................................................................................................................... 18
2.1 Installation procedure .................................................................................... 18
2.1.1 Controller ACX32.000/ALG ........................................................................... 18
2.1.2 Fault handling ................................................................................................ 18
2.1.3 HMI (Operator unit)........................................................................................ 19
2.2 Connection guide........................................................................................... 20
2.2.1 Connection terminals.................................................................................... 20
2.2.2 Connection instruction ................................................................................... 21
Operation 23
2.3 Operating elements ACX8…/SWE ................................................................ 23
2.3.1 Restoration of character set .......................................................................... 24
2.3.2 Configuration of the HMI................................................................................ 24
2.4 Navigation...................................................................................................... 24
2.4.1 Levels ............................................................................................................ 24
2.4.2 Menus............................................................................................................ 26
2.4.3 Passwords ..................................................................................................... 27
2.4.4 Overview of menu structure........................................................................... 28
2.4.5 Navigation for basic settings.......................................................................... 29
2.4.6 Overview of the basic settings....................................................................... 30
2.4.7 Navigation parameters for end-user and HVAC engineer ............................. 32
2.4.8 Start / stop button (Service switch)................................................................ 35
2.4.9 Alarms list ...................................................................................................... 36
2.4.10 Overview of end-user parameters ................................................................. 38
2.4.11 Overview of HVAC engineer parameters ...................................................... 64
3 Commissioning .............................................................................................. 75
3/164
4/164
5/164
6/164
7/164
8/164
9/164
7 Communications ..........................................................................................156
8 Applications..................................................................................................157
10/164
11/164
12/164
The list below contains examples of equipment, suitable for use with Saphir.
13/164
Active and passive safety are product related statuses: the safe status is ensured
actively by the product itself (system safety, e.g. intrinsic safety designed into the
system), or the product has passive safety characteristics and has to rely on the safety
that is to be constantly exercised when the product is used.
Active safety
Active safety of the ACX32.000/ALG is achieved through the following measures:
Use of safe software (self-diagnosis, plausibility tests, warning of potential risks,
shutdown in the case of serious system faults, data backup in the event of power
failure, etc.)
Safe construction
Passive safety The passive safety of ACX32.000/ALG is enhanced through the following measures:
Training of commissioning staff by Siemens to make certain that the system will be
correctly used and safety regulations complied with.
Instructing the operator, including detailed information about safety measures.
14/164
The ACX32.000/ALG is a state-of-the-art product with the level of safety that can be
expected in all relevant circumstances.
Correct use Prerequisites for the flawless and safe operation of the ACX32.000/ALG are: correct
and adequate transport and storage, mounting, installation and commissioning,
followed by accurate and careful operation.
Note The following notes on safety refer not only to the ACX32.000/ALG but also to the
controller’s environment (e.g. the control panel) and the related building services plant.
Observe all notes on safety and comply with the relevant general safety regulations to
ensure that no damage to people and / or property can occur.
It is forbidden to remove, circumnavigate or disable any safety devices, safety
functions or monitoring equipment
Devices and system components may only be used when in a flawless condition
from a technical point of view. Faults that can affect the safety must immediately be
corrected
Observe the protective measures aimed at preventing electric shock and do not
take any actions that might adversely affect the existing protective measures
Never remove covers, housings or other protective equipment. Do not operate the
plant or any plant sections or components when standard protective equipment is
not operative or when its operation is impeded
Do not take any action that could affect the prescribed segregation of protective
low voltage (AC 24 V)
Before opening the control panel, turn the power supply off. Never perform any
work when equipment is under voltage
Turn the power supply off when changing fuses. Use the correct replacement fuses
Avoid electromagnetic and other disturbances on signal lines and connecting wires
that could trigger functions and actions detrimental to safety
Always mount and install the system and other plant components in compliance
with the relevant mounting and installation instructions
15/164
Required packing for storage and transport depends on the mechanical and climatic
conditions.
Use original packing Use Siemens’ original packing or that of the supplier if, during transport, the usual
mechanical and climatic conditions can be expected.
Mechanical protection Avoid excessive mechanical strain on the packing from outside (caused by, for
example, pointed or blunt objects). Pile packed products only when the packing will
keep the load safely away from the product.
Transport under severe For transport under more severe conditions (e.g. on open trucks, in case of extreme
conditions vibrations, seafreight or shipment to subtropical countries), additional or special packing
is required.
Storage Store the product such that harmful environmental effects cannot cause any damage.
Avoid frequent and especially abrupt temperature changes during storage. They are
particularly harmful in the case of condensation.
For storage and transport, the limits specified in Data Sheet CE1N3222 must be
observed. If in doubt, please contact your supplier or Siemens
Damage resulting from improper packing, storage or transport will not be the
responsibility of Siemens
Cleaning All that is required in terms of maintenance is cleaning at regular intervals. System
components fitted inside the control panel should be cleaned from dust and dirt at the
normal service intervals.
Faults Should system faults occur and you are not authorized to make a diagnosis or rectify
the fault, call in your Siemens service engineer.
Diagnostics, rectification of faults and fresh startup of plant may only be carried out by
authorized staff. This also applies to work to be performed inside the control panel
(inspections, changing fuses, etc.).
In the case of unauthorized interventions, Siemens will not assume any responsibility.
Any damage to the system or consequential damage will be the responsibility of the
party that caused it.
16/164
Disposal The controller contains electrical and electronic components and must not be disposed
of together with household garbage. Local and currently valid legislation must
always be observed!
17/164
25
159
283
3221M02
A specific transformer for the power supply is required. It must not be connected
to the sensors or to other equipment, since this will ruin the entire unit!
Note For detailed information about, for example, the installation and mechanical design of
ACX32.000/ALG, refer to Basic Documentation SICLIMAT® SAPHIR (CE2P3690en).
18/164
+0,5
are 153.5 x 99.3 mm.
0
135,5
3221M01
+0,5
87,5 0
3221Z01
When fitting the unit, make certain
that the seal is on the front of the
housing!
Note For technical data of the HMI, refer to Data Sheet N3223en.
19/164
3221A01D
X11 UI4
X3
X4
X7
X1
X9
24V AC/DC
AO1
AO3
AO4
DO5
DI1
AO2
UI1
UI2
UI3
UI5
UI6
UI7
DO1
DO6
DI2
DO2
Ingång
DIL-1
DIL-2
DIL-3
DIL-4
+
+
+
+
+
-
-
10
11
12
13
14
1
2
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
1
2
3
4
5
6
1
2
3
4
5
6
7
8
9
1
10
11
12
13
14
1
2
3
1
2
1
2
3
4
5
6
4
5
6
3
4
1
2
3
4
5
6
1
2
3
4
5
6
7
8
9
+
+
+
+
-
-
8-
7-
6-
5-
4-
3-
2-
1-
GND
12V DC
12V DC
CTS
TxD
RTS
RxD
GND
UI10
UI11
UI12
UI13
UI14
DI3
DO3
DO7
UI8
UI9
DO4
DO8
DI4
AO5
AO6
AO7
AO8
X10
X12
X13
X8
X5
X6
Saphir IO Function IO type Connection Saphir
Relay outputs
DO1 Pump or electric air heater Digital X3 (Pin 1,2,3)
DO2 Cooling pump or DX Step1 Digital X3 (Pin 4,5,6)
DO3 Supply fan Switching (FVO) / Low-speed Digital X4 (Pin 1,2,3)
DO4 Exhaust fan Switching (FVO) / Low-speed Digital X4 (Pin 4,5,6)
DO5 Smoke damper Digital X5 (Pin 1,2,3)
DO6 Outside air damper Digital X5 (Pin 4,5,6)
DO7 Alarm output priority A Digital X6 (Pin 1,2,3)
DO8 Alarm output priority B Digital X6 (Pin 4,5,6)
Analog outputs
AO1 Heating Analog (0 - 10 V) X9 (Pin 1,3)
AO2 Cooling / DX Step2* Analog (0 - 10 V) X9 (Pin 2,3)
AO3 Heat exchanger Analog (0 - 10 V) X9 (Pin 4,6)
AO4 Posttreatment / Extra heating Analog (0 - 10 V) X9 (Pin 5,6)
AO5 Frequency converter Supply Analog (0 - 10 V) X10 (Pin 1,3)
AO6 Frequency converter Exhaust Analog (0 - 10 V) X10 (Pin 2,3)
AO7 Indication full speed* Analog (0 – 10 V) X10 (Pin 4,6)
AO8 External unit (via time channel)* Analog (0 – 10 V) X10 (Pin 5,6)
Binary inputs
DI1 Timer low speed Digital X7 (Pin 1,2)
DI2 Timer high speed Digital X7 (Pin 3,4)
DI3 Alarm smoke damper Digital X8 (Pin1,2)
DI4 Smoke/fire alarm Digital X8 (Pin 3,4)
Universal inputs
UI1 Room / Exhaust air temperature Passive (Ni 1000) X11 (Pin 1,2)
UI2 Supply air temperature Passive (Ni 1000) X11 (Pin 3,4)
UI3 Outside temperature Passive (Ni 1000) X11 (Pin 5,6)
UI4 Frost temperature Passive (Ni 1000) X11 (Pin 7,8)
UI5 Setpoint / CO2 sensor / Supply pressure Passive (Ni 1000) / X11 (Pin 9,10)
Active (0-10 V)
UI6 Multifunc. input 1 Passive (Ni 1000) / X11 (Pin 11,12)
Digital
UI7 Multifunc. input 2 Passive (Ni 1000) X11 (Pin 13,14)
UI8 Alarm Supply fan / Supply pressure Digital/Active (0–10 X12 (Pin 1,2)
V)
UI9 Alarm Extract fan / Extract pressure Digital/Active (0–10V) X12 (Pin 3,4)
UI10 Alarm Filter Digital/Active (0–10V) X12 (Pin 5,6)
UI11 Alarm circ.pump heating/overheating Digital X12 (Pin 7,8)
UI12 Alarm cooling Digital X12 (Pin 9,10)
UI13 Alarm HRC Digital X12 (Pin 11,12)
UI14 Free alarm input (AUX) Digital X12 (Pin 13,14)
DIL switches
DIL 1 Set values after loading of new program Digital (switch)
DIL 2 For configuration of HMI Digital (switch)
* Via voltage relay, e.g. Styrelec RB111V-12VDC
20/164
24VAC G
50/60 Hz 24VAC
20VA 50/60Hz G0
+/- 15%
230VAC
50/60Hz
IMPORTANT!
The controller must have a separate power supply to prevent damage due to
voltage transients.
Digital outputs
X3 X4 X5 X6
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Digital inputs
X7 X8
1 2 3 4 1 2 3 4
21/164
1 2 3 4 5 6 1 2 3 4 5 6
G
G0
G G0 Y
Universal inputs
X11
+- +- +- +- +- +- +-
1 2 3 4 5 6 7 8 9 10 11 12 13 14
NI1000
X12
+ - + - + - + - + - + - + -
1 2 3 4 5 6 7 8 9 10 11 12 13 14
G
G0
B M G
X12
+ - + - + - + - + - + - + -
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Digitla Ingång
Digital input
22/164
Legend
Operating element Function
LCD with 4/8 line, each one Display of actual values and settings
with 20 characters
Start menu button (F1) Jumps back to the start page
Return button (F2) Jumps one menu back
23/164
When using operator unit ACX80.910/SWE, the character set may sometimes get lost
when the HMI cable is connected/disconnected during operation. To restore the
character set, proceed as follows:
Disconnect the HMI and then connect it again with the ”Return key” =F2
pressed down.
This opens a window with a large number of characters. Press the ”Start menu
key”= F1 and the ”Alarm key”= F4 at the same time. All characters will now
appear in the window.
Disconnect and then reconnect the HMI without pressing any keys. All
characters are now restored in the menu. If not, please repeat the procedure
above.
After system configuration (applies to changes in the Commissioning menu and control
functions), DIL-switch 2 on the Saphir must be switched from OFF-ON. After this, the
Saphir will restart automatically in order to update the menu structure in the operator
unit according to the selected configuration.
2.4 Navigation
2.4.1 Levels
At the information level, all users may read certain values without input of password.
Basically, these values are current plant values and states.
At the operating level, the end-user can read and change certain values by entering the
corresponding password. Basically, this applies to current plant values and states and
the possibility to change setpoints etc., i.e. end-user parameters.
Parameter setting level The HVAC engineer has access to the parameter setting level:
The end-user has no access to the parameter setting level. It is for exclusive use by the
HVAC engineer and can only be accessed by entering the appropriate password. Input
of the correct password gives access to the highest entry level, which makes it possible
to read and change all values available at the operating level.
24/164
The parameter names are accessed via the main menus and the submenus. After the
parameter names, values are given that can be read and changed.
The basic settings (and the time scheduler) do not have parameter names, but go via
menus directly to the setting lines, i.e. to values that can be read and changed.
Note In this documentation, the parameter names are given in Courier font type, in order to
facilitate their distinction from the menus.
25/164
The parameter names or the setting lines are accessed via main menus (start page)
and submenus. The structure is shown in section 2.4.6.
The order in which the menus associated with the individual parameter names or
setting lines are selected, is also described in the overview and description section of
this documentation. In the parameter overviews (section 2.4.10 for end-user
parameters, and section 2.4.11 for HVAC engineer parameters) and in the description
part (chapter 3-6), a line highlighted in gray provides information about the selected
menus that lead from the start page to the parameter names or setting lines.
Default value
Parameter
Function
Change
Section
Range
name
Read
Unit
Menu Configuration Timer inputs Parameter name
TimerOnTime Time for timer input 0...12 h 0 P P 5.18
TimerSetp Selection of Econ/Comf Comf P P 5.18
setpoint for timer
operation
TimerOnTime 0…12 H 0
Note Depending on the application, some of the parameters are not used and do not appear
on the HMI. The parameters listed and described in this documentation always appear
in the same order however. The menus are always displayed.
26/164
Password levels Info password (I) for the operating level (no password required!)
Operator password (B) not used
Parameter setting password (P) for the parameter setting level
Numeric code The operator password and the parameter setting password use a factory-set numeric
code: Password level 2 and 4.
In addition, user-defined passwords can be entered: Password level 1 and 3.
Note The password levels are hierarchically structured: for example, if password 3 is
entered, everything can be read or written at password level 1 or 2.
User-defined password The user-defined password is different from the default password and is intended for
individual use. After entering the user or parameter setting level, the user can change
the relevant password. For that purpose, the line “Change Password” under menu
“Password“ is to be used. The password level below the level used for entering the
system can be changed. This means that if a user gained access with password 2, he
can change the user-defined password to level 1, but not to level 3.
The default password can be changed if the user selected level 2 or 4 by mistake, in
place of 1 or 3 (user-defined passwords).
Overview:
What can be read Parameters for all users: End-user parameters: Basic settings:
and changed at the Actual values, Setpoints, Alarms Actual values, Setpoints, Alarms Language selection, Daylight-
different levels? Chapter 4 Chapter 4 saving time, HMI parameters
And where is what Chapter 3
described? HVAC
engineer parameters:
Chapter 5
27/164
A
Commissioning will only be shown when the controller is unconfigured.
28/164
The basic settings can be read on the information level and changed on the operating
level. The basic settings include settings that apply to the plant. Navigation through the
basic settings is explained here using the example ”Language Selection”:
Press the line selection buttons until you reach ”Password function” and
Setpoints
Alarm history
confirm with ENTER .
Password function
Log In 2. Select the line “Log In“ and confirm with ENTER
.
Log Out
Password function
Press buttons until you reach the first digit of the numeric code and
0*****
When the last digit is confirmed with ENTER, the cursor returns to the first line
of the start page; the same thing happens if you enter the wrong password.
Timerinput 4. Press the line selection buttons until you reach ”System parameters” and
Nightmode confirm with ENTER
”System parameters” contains all the setting lines for the basic settings.
SmokeDamper
System parameters
Language Selection 5. Select the required line with the buttons and confirm with ENTER
Communication
Summer/Winter
Diagnose
If several values appear side by side: The cursor can be moved horizontally by
pressing buttons .1
Pressing the return button takes you back to the next higher menu.
Pressing the Start Page button takes you back to the start page.
29/164
The listing of menu levels below (Time / Date, Language Selection, etc.) is the same as
on the HMI.
„“ symbol for ENTER
with subsequent selection of the line with the line selection keys .
Password: B
Setting: Day, month, year (dd.mm.yyyy)
Hours, minutes, seconds (hh.mm.ss)
Description: Section 5.2
Password: P
Setting: Language
Description: Section 4.1
Password: P
Setting: Communication
Description: Section 4.3, 4.4, 4.5
Password: Service
Setting: Start, end daylight saving time
Start, end non-daylight saving time
Switch-over time
Description: Section 4.2
30/164
Password: P
Setting: Process unit status, and store / load factory settings
Description: Section 4.6
Password: Service
Setting: All display-relevant settings
Description: Section 4.7
Password function
Operation status Log In Log In
Setpoints Log Out
Alarms history Change Password ****
Password function
31/164
When the last digit is confirmed with ENTER, the cursor returns to the first line
of the start page; the same thing happens if you enter the wrong password.
D a gs P ro g ram
4. Based on the overview, the menu tree and by use of the setting instructions
V eck oP r og ra m B
D r iftS ta tus S ty r In gån g
M ätV ärd en
U tg ån g ar D ig itala
B ra n dS p jäll
given in the description part, you reach the parameter names for the different
D r iftT id s M ä ta re
menu levels.
V V X V erk nG rad
M i n/M a xT F tem p
F lö de sR eg u lato r
Tr yc kR eg u lato r
P a r a m e te r n a m n
Lar mH is to rik
L ös e nO r d Lo g ga In
Lo gg a U t
Ä n dr a Lö s eno rd
K o nta ktf un k ti on
R eg ler P ara me tr ar
P ar am etra r F läk t
F löd e
Try ck
D X -K y la 1S teg
K y la
P um p
F ry sv ak t
VV X
Ex tern tB ö rv ärd e
S ty r In gån g ar
T em pe ratu rL arm
Lar m
L arm K las s
N attD r ift
N attK y la
D ep lace rad V en t
S m r/V n trK om p
B ran d Sp jäll
C U pp s tart
K o m mu nik atio n
S om m ar/V in ter
B S - V er sio n
D iag n os
A H M I -P ar ame trar
5. Press the line selection buttons till you reach the respective menu(s) and
confirm each one with ENTER until you reach the parameter names.
The last selected menu is displayed within parentheses with asterisks (*xyz*)
on the top line.
32/164
If the value consists of several parts, press the buttons – after confirming the
entry of the first part – to get to the next part of the value. Change the value
and confirm it.
Pressing the return button takes you back to the next higher menu.
Pressing the Start Page button takes you back to the start page.
When button (3) is pressed, the unit stops. This is indicated on the top line of Operation
Info.
At repeated pressing of the button, Service switch (3) goes to auto, i.e. the unit starts if
the time scheduler or control input so admits. The function of the service switch can be
changed, see section 5.1.
A green LED indicates that the unit is in operation (only applicable to HMI ACX84.910)
33/164
Description The alarms list provides an overview of active alarms (alarms still due). A maximum of
15 alarms can be displayed.
To access the alarms list, you must press the alarms button (5) one time. By another
pressing the red LED assumes a fixed light (incoming alarms will then generate a
flashing red light). When an alarm has been attended to, press the button once more
and the alarm disappears from the list.
SupTemp Alarm A/B/C The temperature has exceeded or fallen below the selectable
deviation against the setpoint of the supply air temperature
HRC Alarm UI13 A/B/C Alarm from control unit for rotating heat exchanger
Pump/Heater Alarm UI11 A/B/C Overload heat pump, alternatively overheating electric heater
Chiller Alarm UI12 B Overload cooling pump, alternatively alarm from chiller
SupFanAlarm UI8/- A/B/C Overload supply air fan speed 1 or 2, Deviation alarm
(high/low pressure/flow) at pressure/flow control
ExhFanAlarm UI9/- A/B Overload exhaust air fan speed 1 or 2, Deviation alarm
(high/low pressure/flow) at pressure/flow control
Unit override - B Some component is manually operated from the hand terminal
FilterAlarm UI10 A/B/C Filter monitor triggered for supply or extract air filter
34/162
AlarmRunCounter - B The operating time of the unit has exceeded the set value
35/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
Current Selection of Swedish / – Swed I I 3.1
language language English ish
Commissioning
Date Setting of year, – – 2003 I I 5.2
month, day -06-
01
36/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
MultiFuncInpu Function of Multi- Disable / – Disa I I 3.4
t 1 function input 1 HRC ble
Frosttemp /
DefrostTmp
PlateHRC /
PressGuard
HRC /
Supplytemp
HRC /
Usedairtemp
/ AUX Temp
1
37/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
ExternalContr Selection of Disable / – Disa I I 3.6
l external control ExtSetp 0- ble
10V
/ExtSetpNi1
000 /
Airquality /
SupplyPress
ure
38/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
FanfunctionFi Fan function at fire Stop EX / Stop I I 3.12
re Stop SU / EX/S
Stop EX/SU U
/ Run EX/SU
39/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
Commissioning Removes blocking No / Yes – No I I 3.18
Done of unit
Overview
Serviceswitch Service switch Auto/Stop/L – – I – 5.5
: ow/High
40/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
Room/Exhaustt Disable / -50...150.0 °C – I – 5.15
emp Roomtemp /
(Dynamic) Exhausttemp
41/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
Heating Output signal 0...100 % – I – 5.38
heating battery
42/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
Menu Scheduler Parameter name
43/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
T4 Switching point 4 00:00...24:0 – 12:00 I B 5.3.1
Start: 0 Off
Of/Ec1/Ec2/ ----
Mode: Co1/Co2
---- / Actv
Enabling:
44/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
T3 Switching point 3 dd.00:00...2 – Mo II B 5.3.2
Start: 4:00 12:00 I
dd.00:00...2 Mo
Stop: 4:00 12:01
Of/Ec1/Ec2/ Off
Mode: Co1/Co2 ----
---- / Actv
Enabling:
45/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
T6 Switching point 6 dd.00:00...2 – Mo II B 5.3.2
Start: 4:00 12:00 I B
dd.00:00...2 Mo
Stop: 4:00 12:01
Of/Ec1/Ec2/ Off
Mode: Co1/Co2 ----
---- / Actv
Enabling:
46/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
T2 Switching point 2 dd.mm – I B 5.3.3
Start: 00:00...24:0
0
Mode: Of/Ec1/Ec2/
Co1/Co2
Stop: dd.mm
00:00...24:0
Enabling: 0
----/ Actv
47/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
T5 Switching point 5 dd.mm – I B 5.3.3
Start: 00:00...24:0
0
Mode: Of/Ec1/Ec2/
Co1/Co2
Stop: dd.mm
00:00...24:0
Enabling: 0
----/ Actv
Enabling:
Enabling:
T3 Switching point 3 00:00...24:0 – 12:00 I B 5.3.5
Start: 0 Off
Off/On ----
Mode: ---- / Actv
Enabling:
48/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
T4 Switching point 4 00:00...24:0 – 12:00 I B 5.3.5
Start: 0 Off
Off/On ----
Mode: ---- / Actv
Enabling:
Enabling:
Enabling:
T3 Switching point 3 dd.00:00...2 – Mo I B 5.3.6
Start: 4:00 12:00 I
dd.00:00...2 Mo
Stop: 4:00 12:01
Off/On Off
Mode: ---- / Actv ----
Enabling:
49/162
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
T4 Switching point 4 dd.00:00...2 – Mo I B 5.3.6
Start: 4:00 12:00 I B
dd.00:00...2 Mo
Stop: 4:00 12:01
Off/On Off
Mode: ---- / Actv ----
Enabling:
50/161
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
SmokeDamper Status DI Smoke Off / On – – I – 5.14
damper
51/161
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
Pressure/Flow Supply air 0.0 ...1000 Pa – I – 5.23
SU (Dynamic) pressure or 0.0… l/s
Supply air flow
52/161
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
B-Alarm Alarm priority B OK / alarm – – I B 5.34
53/161
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
Menu Operation status HRC Efficiency Parameter
name
54/160
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
Min/Maxlim: Type of Fixed / – – I B 5.56
min.limitation Sliding
Heating setpoint
55/160
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
DeadzoneComf Dead zone 0.0…10.0 °C 2.0 I B 5.68
Comfort setpoint
56/160
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
SetpLow EX Setpoint, low- l/s / 500 / I B 5.78
speed exhaust air Pa 150
57/160
Function
Read 2
Change
Default
Section
Range
2
name
value
Unit
Highspeed Exh High-speed, 0...100 % 80 I B 5.86
exhaust air
58/160
Default value
Parameter
Function
Change1
Section
Range
Read1
name
Unit
Menu Configuration Sensor Parameter name
59/159
Function
Change1
Section
Range
Read1
name
Unit
Alarmclass Alarm class A/B/C – B P P 6.2
60/159
Function
Change1
Section
Range
Read1
name
Unit
HRC FROSTPROT Alarm HRC freezing – – – P – 6.2
61/159
Function
Change1
Section
Range
Read1
name
Unit
ExternalContrl Selection of external control Disable/ExtSetp 0- – Not P P 6.7
10V/ExtSetpNi1000 / active
Airquality / Press SU
Fancontrol Selection of control type for the Flow / Pressure / 1- – Flow P P 6.11
fans 2 Speed /
Press+Flow
PressureSensor Working range for pressure sensor 0-100 / 0-300 / 0- Pa 0-500 P P 6.14
500 / 0-1000 / 0-
1500 / 0-2500 / 0-
3000
HRC Funct Selection of function for recovery Rot-HRC / RecircAir – Rot-HX P P 6.16
/ Plate-HRC / Water
62/159
Function
Change1
Section
Range
Read1
name
Unit
Extra heating Selection of extra heating Disable / Enable – Not P P 6.17
sequence active
63/159
Function
Change1
Section
Range
Read1
name
Unit
PosttreatmentContr For posttreatment controller (Heating) KP 10.0 P P 6.20
(Cooling) KP -10.0
TN s 120.0
TD 0.0
Startdelay Delay of fan start and stop delay 0.0...180 Sec 30 P P 6.21
for damper
Delay SU Start Delay of Supply air fan start 0...120 s 45 P P 6.22
Co2 Start CO2 for start of compensation 0...2000 ppm 800 P P 6.23.1
Co2 Stop CO2 for stop of compensation 0...2000 ppm 1200 P P 6.23.2
64/159
Function
Change1
Section
Range
Read1
name
Unit
SmrStart Temp. setpoint for start summer -35.0...35.0 °C 25.0 P P 6.24.1
65/159
Function
Change1
Section
Range
Read1
name
Unit
WinterStart Start point winter compensation -30.0...20.0 °C 5.0 P P 6.30.4
66/159
Function
Change1
Section
Range
Read1
name
Unit
Menu Configuration Heating Parameter name
BlockElectr Min. flow for activation of el. battery 0...1000 l/s / Pa 200/50 P P 6.43
DefrostSetp Defrosting setpoint flat plate heat -10.0 – 30.0 °C -3.0 P P 6.52
exchanger
Setp Co2 Set point value at Co2 control for 0…2000 ppm 800 P P 6.49
return air damper
67/159
Function
Change1
Section
Range
Read1
name
Unit
Menu Configuration RemoteSetp Parameter name
68/159
Function
Change1
Section
Range
Read1
name
Unit
Open OutDamper Open outside air damper No / Yes No P P 6.61.3
DlyBeforeTest Delay before test of Night mode 0…600 Min 420 P P 6.62
1
Password that gives authorization to read the value and/or change it
69/159
Description Languages included in the basic version are Swedish and English with Swedish as
default. The language selection can be extended, provided a translation is made to the
required language.
Description At activation of smoke damper, the dampers are run for anti-seizing after a selectable
time (see section 6.63). If signals from the limit positions are not received in the correct
order during the anti-seize run, an A alarm is issued and the unit stops. At anti-seize
operation, the plant is stopped to avoid running the unit run against closed dampers.
70/159
72/159
Description This selects installation of room sensor or exhaust air sensor. For exhaust air sensor
and required unoccupied mode, se DelayBeforeTest (section 6.62).
Description This adjusts the controller for different types of control, more specifically selection of
main sensor, which may be room sensor, exhaust air sensor or supply air sensor.
With room sensor or exhaust air sensor selected, it is possible to use cascade control,
otherwise constant supply airflow must be used. It is also possible to choose between
two types of cascade control; this is done in the Menu- Setpoints-
Min/MaxSupplyAirTemp-Min/MaxLim: (section: 5.56).
In other words: four different control principles may be selected
1. Cascade control with fixed limitation or the supply air. For room or exhaust air
sensor.
2. Differential control with shifting supply air limitation. For room or exhaust air sensor
and activation of shifting min. limitation type. Function Min/MaxSuppltAirTemp, section
5.56.
3. Constant supply air control.
4. Cascade control in summer and constant supply air control in winter.
Description Control principle 1 maintains the room temperature at a constant level. The control loop
for the room generates the setpoint to the control loop for the supply air. The limitation
of the supply air (MinTemp SA and MaxTemp SA) guarantees that the supply air
temperature is maintained within the set range.
73/159
Description For cascade control with shifting limitation of the supply air temperature, the limitation is
calculated as a function of the room temperature.
Roomtemperature
Delta Heating
Delta Cooling
3221D12D
16
Min.limit of supply air temperature
(MinTemp SU)
t
Description For pure supply air temperature control, the supply air temperature is maintained at a
constant level.
Description The fans can be compensated in different ways to make sure that the required
temperature is maintained.
Disable = no function, fan control according to the setpoint values.
Cooling = principally used when there is no cooling battery. When cooling is needed,
the fans increase their speed toward to the maximum set value.(See sections 5.80 &
5.81). If there is a cooling battery, the cooling valve opens only after the fans have
reached the maximum setpoint value. This function may have the opposite effect in
supply air control, when the temperature will increase at the supply air sensor. The
well-being for the people in the room will, however, be greater, since the air turnover
will be greater.
Heating = When the heating valve is fully open and there still is a need for heating, the
fans reduce their speed by reducing the current setpoint value toward the low-speed
setpoint value. (See sections 5.76, 5.78).
Clg+Htg = Both the heating and the cooling function are activated, see above.
The following conditions must apply for fan compensation to take place:
- Fan compensation must be active
- The fans must run at high-speed
- CO2 control must not be active
Description At a triggered fire alarm, the fans control to the selected operational state.
Stop EX = The exhaust air fan is stopped and the supply air fan increased to the set
value (section 6.26).
Stop SU = The supply air fan is stopped and the exhaust air fan increases to the set
value (section 6.26).
Stop EX/SU = Both fans are stopped.
Run EX/SU = Both fans increase to the set value (section 6.26).
75/159
Description This sets the working range for the pressure sensors.
At DX cooling, the steps start when the cooling signal exceed the set values. (See
sections 6.35 – 6.38). This does not apply to DX-binary since those steps are set with a
fixed switching differential.
76/159
Desciption An extra heating sequence placed between heat recovery and heater can be activated.
It could by an 0…10 V DC signal control for example the heating sequence of an
compressor (Do NOT confuse with Extra Control that is not included in this sequence).
This sequence is also possible to be set to circulation damper control with setting of
min outdoor air and CO2 control. However, the sequence is still considered a heating
sequence which implies that a signal of 0% corresponds to full outdoor air supply and
vice versa.
Description This selects the type of air heater to be used. The alternatives are water-borne or
electric air heater.
Disable = No heating function
Water = Frost protection function activated (see section 6.44) and digital output gets
pump function. The pump starts on one of the following conditions: valve opens,
outside temperature falls below 12°C, anti-seizing operation or pump set for continuous
operation.
Electric = Digital output activated at output signal to electrical battery. Anti-seizing and
frost protection function blocked.
Description After the configuration, this parameter must be changed to ”Yes”. For the hand terminal
to be updated according to the new configuration, DIL switch 2 must be switched off/on
(the DIL switch is located above the HMI connector) and the SAPHIR must then be
restarted.
When the SAPHIR starts, the Commissioning menu disappears and the unit is no
longer blocked. If something is wrong in the configuration, this may be changed in
77/159
CommissioningDone No / Yes No
78/159
Description Available standard languages for selection are Swedish and English, with Swedish as
the default setting. The language selection can be extended to meet individual
customer needs, provided that a translation to the required language has been made.
4.2 Summer/Wintertime
Description ”Summer/Wintertime” defines the two points in time when changeover takes place from
winter time to summer time, and vice versa. The standard setting is for Central
European time.
The following lines define the switch-over between ”Summer/wintertime” (in the order
listed below):
Saving Time»:
Enabled
Line Enabled shows whether the function changeover time is enabled.
Activated
Line Activated shows whether summertime is active.
B-TimeActive
Line B-TimeActive shows that the B-time is active when changing to normal time.
Saving Hours
For changeover to summertime, the changeover time is added. For changeover to
wintertime, it is subtracted.
Month (Mth)
The month that defines start (S) and end (E) of the summertime must be entered.
Weekday (Wday)
The weekday on which changeover takes place must be entered.
Offset (Ofs)
Set the offset for weekday above, according to the table below:
3 – Second to last weekday of the month
4 – Last weekday of the month
6 – First weekday of the month
7 – Second weekday of the month
8 – Third weekday of the month
79/159
Description For the RCC board to be able to communicate via TCP/IP, an IP address must be set.
This can be made via a DHCP server or manually in the hand terminal.
IP
Current IP address
Mask
Current network mask
Gate
Current gateway address
Change IP address
The configuration of own IP address can be made here. Not necessary if DHCP server
has been selected. When the IP address has been changed manually, the parameter
”Apply” must be changed from ”No” to ”Yes”.
Description Under ”Modem information” it is possible to read modem status and make settings for
SMS function.
80/159
Description Configuration of Modbus communication. Restart is required for changes to take effect.
81/159
82/160
Description In this menu, you can read information for internal diagnostics, etc.
Overview
OS-Vers: Shows operating system version
Ser.-Nr: Shows serial number
Targettype: Type of controller, e.g. ACX32
Comslot 1: Type of communication board mounted in place 1
Comslot 2: Type of communication board mounted in place 1
MSR fail: Number of errors in program loop
MSR fail type Type of error in program loop
MSR su finish 1=Yes 0=No
Factoryrestore Reset to factory settings
NB! Restart required for the new values to become active.
Factoryset Saves all current settings as factory settings.
NB! The process unite will restart after this function
CycleTimes
ActCycletime Current loop time
AvrCycletime Average loop time
MinCycletime Minimum loop time
MaxCycletime Maximum loop time
ResetCycletime Resets all loop-time values
Application Info
Shows information about manufacturer, unit type and application version.
83/160
Description The operator unit can be controlled via "HMI Parameter". Under ”HMI Parameter”, the
following parameters are available in the order listed.
Settings Menu Configuration System Parameter HMI Parameter
HMI brightness Setting lines
HMI contrast Setting lines
etc.
MSR Type
Displays current configuration to show/hide values in the HMI.
HMI Type
Choice of HMI to recieve correct LED function. (ACX82 or ACX84)
84/160
Log-Out
The password will be reset and the backlighting switched off.
Change Password
A user-defined password can be entered. It is possible to change the password level
that is lower than the password level at which the system was entered. This means that
if the entry was made with password 2, the user-defined password on level 1 can be
changed, but not password 3.
Current level
Displays the current level that the user is logged in at.
The factory default password can be changed if the user by mistake has selected level
2 or 4 instead of 1 or 3 (user-defined passwords). To reactivate the default password,
the controller must be switched off and on again!
85/160
Description In order to control the unit from an external system the scheduler con be overridden
instead of performing changes to the pre-programmed schedule. The override remains
until the setting is changed back to “Auto”, when the scheduler assumes control again.
Operation mode switch This overrides the scheduler in order to start or stop the unit at chosen position. At
auto-position the unit is controlled by the scheduler, and at all unscheduled points the
override controls the unit to a designated position. However, the service switch and
timer input takes precedence over the operation mode switch.
BMS override The scheduler can be overridden through a communication bus from an external
system (BMS). This parameter indicates current position should the scheduler be
overridden in such a way.
When the unit is set to auto position it operates according to the scheduler, otherwise
according to preferred setting. Operation mode switch, night mode, control input and
service switch on the HMI takes precedence over the BMS override.
Current scheduler The parameter Curr. scheduler: displays current operation mode in regard to
daytime scheduler, weektime scheduler, yeartime scheduler, BMS override and
Operation mode switch in priority order where the daytime scheduler has the lowest
priority and the operation mode switch has the highest.
5.2 Date/time
Description When accessing the menu level «Time channel», the cursor flashes by the date field.
On this setting line, you may enter the date (dd.mm.yyyy) and the time of day
(hh.mm.ss) according to predefined criteria.
5.3 Scheduler
The ACX32.000/ALG features a time scheduler for the unit with four independent
switching times per day (day program), six possible exceptions per week (week
program) and five possible exceptions per year (year program). In addition, the
ACX32.000/ALG has another timeswitch program for control of external equipment.
This program comprises four switching times per day (day program) and four possible
exceptions per week (week program).
86/160
Description On the line «Daytimescheduler», 4 independent switching times can be entered. The
settings include time of day, fan speed and the double setpoints (Economy/Comfort).
The table below gives the operating mode to be entered with a 2-speed fan, single-
speed fan, or a fan using a frequency converter.
Note The day program applies to all weekdays. Using operating line «Weektimescheduler»,
it is possible to enter 6 exceptions from the daytime schedule.
When making the setting, it must be observed that enabling of a switching time
(..../Actv) must take place only after the values are set.
Description The week program is used for a maximum of 6 exceptions from the day program.
Time of day
Time of day
Switching
Enable
Day of
Day of
action
Mode
Off
On
Graphic presentation of the timeswitch program using the 2 examples day program and
week program:
87/160
When making the setting, it must be observed that enabling (..../Actv ) of a switching
action takes place only after selecting the weekday (Mo...Su), the time of day (hours /
minutes), the setpoint (Economy / Comfort), and the fan speed (Off, 1, 2).
A switching action is defined by the day and time of day switching on/off take place.
When the switching action is completed, the day program goes active again.
Description The year program is used to create exceptions from the day and week program.
switching off
switching off
switching on
switching on
Time of day
Time of day
Switching
Month of
Month of
Enable
Day of
Day of
action
Mode
Off
On
When making the setting, it must be observed that enabling of a switching time
(..../Actv ) must take place only after all the parameters have been set in the respective
switching alternative
88/160
Description On the line «Daytimescheduler», 4 independent switching times can be entered plus
operational mode “Off” or “On”.
Example of possible setting of a day program:
Note The day program applies to all weekdays. It is, however, possible – on the line “Week
program” - to enter two exceptions from the day program.
When making the setting, it must be observed that enabling of a switching time
(..../Actv ) must take place only after all the values have been set.
Description The week program is used for a maximum of 4 exceptions from the day program.
onInkopplings
switching off
switching on
Time of day
Time of day
Switching
Enable
Day of
Day of
action
Mode
Off
On
Vid inställning skall beaktas att omkopplingen (..../Aktiv) inte får frisläppas förrän efter
inställningen av veckodagen (må…sö), tiden (timmar/minuter) och det inställda
driftstättet (Till, Från) Ett omkopplingsalternativ definieras för en inkopplingsdag och -tid
samt för en urkopplingsdag och -tid. När den inprogrammerade omkopplingsalternativet
har löpt ut aktiveras åter programmet för dagprogram.
89/160
Description A timer or a switch can be connected to the digital inputs DI1 and DI2. These external
components can be used to manually preselect the fan speeds. Manual selection
always has higher priority (with the exception of an alarm) and therefore overrides the
other control sources (timeswitch programs, unoccupied mode, etc.). When the digital
inputs DI1 and DI2 are not used, the parameter Timer inputs shows “Automatic”.
DI1 controls the half-speed and DI2 controls the full-speed. If both inputs are activated
simultaneously, the set alternative rules (see 6.57).
Parameter TimerInputs indicates the fan speed with which the plant is operating:
Automatic Off
Off Stop
Low-speed Low
High-speed High
Description It is possible, via a service button on the operator unit (HMI), to stop or force the unit to
the set operation mode (see section 6.65). The manual setting always has higher
priority (with the exception of an alarm) and therefore overrides the other control
sources (timeswitch programs, unoccupied mode, etc.).
When the button is pressed again, the unit reverts to automatic.
Description An external emergency stop switch will shut down the unit. At an emergency stop fans
stops and dampers closes without delay. There will not be any fan over run for
electrical heater. To activate, see section 3.3
90/160
Fire/Smoke Off / On
HRC Off / On
Description Indicates the current value for digital input Pump/Electric heater.
Pump/Heater Off / On
Chiller Off / On
AUX Off / On
91/160
Filter Off / On
Description Indicates the current value for digital input HRC Pressure guard.
HRCPressGuard Off / On
Description Indicates the current value for digital input Smoke damper.
SmokeDamper Off / On
92/160
Description Indicates the current value of the room temperature or exhaust air temperature. The
menu shows Disable for not activated sensor function.
Room/Exhausttemp -50.0...150.0 °C
(Dynamic)
Outtemp -50.0...150.0 °C
Supplytemp -50.0...150.0 °C
Frost temperature The frost protection function is only used in the case of ventilation and air conditioning
plants equipped with hot water air heater batteries. The frost detector is connected to
input UI4. Parameter Frosttemp then displays the current temperature acquired by
the frost detector.
Frosttemp -50.0...150.0 °C
93/160
MultiFuncInput 1 -50.0...150.0 °C
(Dynamic)
Description Universal temperature input where the function is selected in section 3.4 or 6.5.
Depending on the selected function, the text display on the HMI is one of: Disable /
PostTreaTemp / SupplyTemp HRC / UsedairTemp / AUX Temp 2 / Roomtemp ctrl /
Roomtemp meas.
MultiFuncInput 2 -50.0...150.0 °C
(Dynamic)
Description Following selection of CO2 control (section 3.5), this indicates the current airquality.
ExternalSetp -3.0...50.0 °C
Description Indicates pressure or flow for the supply air, depending on the selected type of fan
control. The flow is calculated via the pressure and a selectable K factor.
94/160
Pressure SU 0...3000 Pa
Flow SU 0... l/s
Description Indicates pressure or flow for the exhaust air, depending on the selected type of fan
control. The flow is calculated via the pressure and a selectable K factor.
Pressure EX 0...3000 Pa
Flow EX 0... l/s
Description Indicates pressure for the supply air if the solution is activated under section 3.6,
selection of external control. At not activated solution “Disable” is displayed.
Pressure SU 0...3000 Pa
95/160
Description Control of the circulation pump in the heating circuit or control of electric heater. For
water battery, the digital output is activated when the valve opens, at anti-seize
operation or when the outside temperature falls below 8oC. If there is no outside sensor
or if there is an sensor error, the pump runs continuously. The pump may also be set to
continuous operation (see section 6.41). For electric heater, the output is activated by
heating signal but is blocked at low flow/pressure over the supply fan.
Pump/Heat Off / On
Description Control of the pump in the cooling circuit or control of DX cooling step 1. The pumps
starts when the cooling valve opens or at active anti-seize operation. The pump may
also run continuously (see section 6.33). For DX cooling, the steps start when the
cooling signal exceeds the set value (see sections 6.35 – 6.38).
DX Step2 Off / On
Supplyfan Off/Lowspeed/Highspeed
Note To make a functional check, the value can be readjusted directly on this level after
entering password 1, provided the plant is in operation and there is no alarm present.
96/160
Description Activation signal for the frequency converter of the exhaust air fan.
Exhaustfan Off/Lowspeed/Highspeed
Note To make a functional check, the value can be readjusted directly on this level after
entering password 1, provided the plant is in operation and there is no alarm.
Description Controls the output for outside air damper. The damper opens at start of unit, except for
unoccupied mode heating or cooling (see section 6.61.3) when the outside damper
may be blocked (selectable), thus only circulating the air via an extract air damper.
When the unit is stopped, closing of the damper is delayed by the same time as the set
start delay (see section 6.21) – exception for A alarm, when the damper closes
immediately.
OutDamper Off / On
Description Controls the output for the smoke damper. The damper opens at start of unit, provided
that the function “SmokeDamper” has been selected (see section 3.2 or 6.3) and that
there is no alarm present and no anti-seizing operation active.
SmokeDamper Off / On
Description Indicates the operating state of the output for common fault alarm A. The output is
activated when there is an outstanding unattended "A alarm".
A-Alarm Off / On
B-Alarm Off / On
General description of The alarm outputs for the 2 parameters A-Alarm and B-Alarm serve the overall plant
the alarm function for supervisory operation. The individual plant faults are combined in the common fault
and displayed as an alarm with priority A or B. The common fault message indicates
that there is a fault in the plant, but does not say which one it is. In the event of an
alarm or if the HMI is incorrectly operated, the LED next to the alarm button on the HMI
flashes.
Note An audible or optical alarm can be connected to the alarm outputs (DO7/DO8).
98/160
Note
An alarm is acknowledged by pressing the alarm button on the HMI. It may take a few
seconds until flashing stops.
When another alarm class is displayed within parentheses, it means that the alarm
class can be changed, see section 6.2
99/160
Cooling 0...100 %
Note To make a functional check, the value can be readjusted directly on this level after input
of password 1.
HRC 0...100 %
Note To make a functional check, the value can be readjusted directly on this level after
entering password 1.
Note To make a functional check, the value can be readjusted directly on this level after
entering password 1.
Heating 0...100 %
100/160
Posttreatment 0...100 %
Description Indicates the current output frequency for the supply air fan.
Supplyfan 0...100 %
Description Indicates the current output frequency for the exhaust air fan.
Exhaustfan 0...100 %
101/160
TestSmokeDamper Off / On
Description Set interval for anti-seize operation of smoke dampers. Should a damper assume an
incorrect position (detected via limit positions contacts), an alarm will be issued. This
function requires connection according to the connection diagram below.
Setting of the interval, see section 6.63.
Interval 00:00...23:00 h
Hours-run 0…48 h
102/160
Description The parameter Fanruncounter shows the total number of fan operating hours since
the controller was first commissioned or since the last meter reset.
Description The parameter Reset Counter can be used to reset the fan operating hours counter.
Note The hours-run counter can be reset directly on this level after input of password 1.
103/160
5.47 Efficiency
104/160
Description Indicates the setpoint currently valid for the main sensor.
Description Indicates the current measured value for the main sensor.
Description Temperature setpoint for heating where the cooling setpoint is calculated by means of
deadzone economy.
Description Temperature setpoint for heating where the cooling setpoint is calculated by means of
deadzone comfort.
105/160
Description With external control selected as “ExtSetp0-10” or “ExtSetpNI1000” (see section 3.6 or
6.7), “BasicSetp” is overridden and summer/winter compensation has no function any
more.
106/160
Description Type of min./max-limitation for the supply air. In most control cases, fixed limitation is
used, but for deplaced ventilation with so-called low-impulse units, a shifting
min./max.limitation is required.
A cascade control with shifting supply air limitation is then used (differential
temperature control, as opposed to room temperature control).
Depending on the current room temperature, the shifting limits of the supply air are
calculated, and the supply air is then allowed to shift within the calculated values for
min. and max. limitation, respectively.
T [°C]
Max.limit of supply air temperature
(MaxTemp SU)
28
Sliding limit
Roomtemperature
Delta Heating
Delta Cooling
3221D12D
16
Min.limit of supply air temperature
(MinTemp SU)
t
Description Indicates the current heating setpoint for the supply air temperature.
ActHtgSetp -50.0...150.0 °C
Description Indicates the current cooling setpoint for the supply air temperature.
107/160
Supplytemp -50.0...150.0 °C
Description The minimum supply air temperature allowed during operation with fixed limitation.
Description The maximum supply air temperature allowed during operation with fixed limitation.
Description Input of the max. difference between supply air temperature and room temperature with
shifting min.limitation.
Description Input of the max. difference between supply air temperature and room temperature with
shifting max.limitation.
Description Indicates the current setpoint for the supply air temperature.
Supplytemp -50.0...150.0 °C
Description Temperature setpoint for heating where the cooling setpoint is calculated by means of
deadzone economy.
Description Temperature setpoint for heating where the cooling setpoint is calculated by means of
deadzone comfort.
109/160
Description With external control selected as “ExtSetp0-10” or “ExtSetpNI1000” (see section 3.6 or
6.7), “BasicSetp” is overridden and summer/winter compensation has no function any
more.
110/160
Description Indicates the currently valid setpoint for the supply airflow or pressure, depending on
the selected control type.
ActStp SU l/s / Pa
Description Indicates the currently pressure in the supply airif this solution is selected under
external control, se section 3.6 or 6.7. If the solution is not selected “Disabled” are
displayed.
Pressure SU Pa
Description Indicates the currently flow or pressure in the supply air, depending on the selected
control type.
Flow SU l/s
Pressure SU Pa
Description Indicates the currently valid setpoint for the exhaust airflow or pressure, depending on
the selected control type.
ActStp EX l/s / Pa
111/160
Flow EX l/s
Pressure EX Pa
Description Max. setpoint for the supply air fan with fan compensation.
112/160
Description Max. setpoint for the exhaust air fan with fan compensation.
Description Selectable temperature deadzone before the fans start reducing their speed in
operation with fan compensation “heating”.
DeadzoneCompHtg o
C 1.0
Description Selectable temperature deadzone before the fans start increasing their speed in
operation with fan compensation “cooling”.
DeadzoneCompClg o
C 1.0
Comp ES Setp % 0
113/160
Description Setting of fixed signal for the supply air fan in low-speed operation.
Description Setting of fixed signal for the supply air fan in high-speed operation.
HighSpeed SA 0...100 % 80
Description Setting of fixed signal for the extract air fan in low-speed operation.
Description Setting of fixed signal for the extract air fan in high-speed operation.
114/160
Description Indicates currently selected type of posttreatment. For further information, see
“ControlFunctions”.
115/160
Description Indicates the last 15 alarms, active alarms as well as alarms attended to. The time
when the alarm came in is displayed, too.
Changing the parameter “No” to “Yes” will delete all the information from the list.
NB! To be able to see the current information again, you must re-enter the menu.
Reset No/Yes No
116/160
5.93 Log-in
Description Log-in with password for access to installation parameters. See also sections 4.9 and
2.4.5 Navigation default values.
Log In 1000
5.94 Log-out
Description Log-out to prevent unauthorized access to installation parameters. See also section
4.9.
Parameter name
Log Out
Description Change of the currently valid password. Only passwords with a lower level or the same
level as the one you are logged in to can be changed. See also section 4.9.
Parameter name
Change Password
117/160
Unit
Str
Town
118/160
Description A number of different factors may affect the measured values from a sensor, thus
making it incorrect. In such cases, the measured value can be corrected.
Effects Parallel displacement of the sensor’s characteristics with the adjusted value
After calibration, the respective measured value shows the adjusted temperature
119/160
Description All alarms can be configured here – contact function, alarm delay, alarm class etc.
NO (Normally Open)
The contact is normally open and closes at an alarm.
NC (Normally Closed)
The contact is normally closed and opens at an alarm.
FIRE/SMOKE - - -
Contact function NO / NC - NC
HRC - - -
Contact function NO / NC - NO
Alarmclass A/B/C - B
PUMP/HEAT - - -
Contact function NO / NC - NO
Alarmclass A/B/C - B
CHILLER - - -
Contact function NO / NC - NO
AUX - - -
Contact function NO / NC - NO
Alarmclass A/B/C - B
Delay 0…300 s 2
FILTER - - -
Contact function NO / NC - NO
Alarmclass A/B/C - B
Delay 0…300 m 15
SUPPLY FAN - - -
Contact function* NO / NC - NO
Alarmclass A/B/C - B
Delay 0…600 S 60
EXHAUST FAN - - -
Contact function* NO / NC - NO
Alarmclass A/B/C - B
Delay 0…600 s 60
DerivatSU/EX 0…200 Pa 100
DerivatSU/EX 0…1000 l/s 500
SUPPLYTEMP - - -
Alarmclass A/B/C - B
120/160
* At 1 or 2 speed fan combined with electric heater these parameters needs to be set to NC in order to
deliver the correct function for releasing digital output to the heater.
121/160
122/160
124/160
CommissioningDone No / Yes No
125/160
126/160
Description Setting of the time between damper open and exhaust air fan start.
This time is also used as damper stop delay to make sure that the fans will have
slowed down before the damper closes. At a triggered A alarm, the damper will,
however, close immediately.
Description Setting of the time between start of extract air fan and permitted start of supply air fan.
Description The CO2 control is used for automatic compensation of flow/pressure in relation to the
current air quality. In this, the basic setpoint for flow/pressure is shifted.
Legend
Functional diagram
w
FW Start point for CO2 compensation
EW End point for CO2 compensation
Ew SW Low-speed setpoint
Tw
TA [ppm] TW High-speed setpoint
TA Air quality
w Setpoint change
Fw
Sw
Description Setting of start point (air quality) for compensation of flow/pressure. IF 1-2 speed fan
usage, the fans return to low speed if the air quality should fall below this setting.
127/160
Description Setting of end point (air quality) for compensation of flow/pressure. 1 or 2 speed fan will
increase to highspeed at air quality above this setting.
Description Summer/winter compensation is used for automatic switch-over of the plant between
summer and winter operation mode. In this, the basic setpoint is shifted as a function of
the outside temperature.
Functional diagram
w [K] Legend
Ss FS Start point for summer compensation
3221D05
Sw ES End point for summer compensation
SS Delta (total shift) in K at end point ES
Fw Fs
FW Start point for winter compensation
Ew Es
EW End point for winter compensation
TA [°C] SW Delta (total shift) in K at end point EW
TA Outside temperature
w Setpoint change
General conditions Delta above 0.0 is a condition for activation of the summer/winter compensation
Description
The start temperature at FS at which the basic setpoint starts shifting (proportionally to
the rising outside temperature).
Description The end temperature at ES at which the basic setpoint has shifted 100% (in relation to
the total shift delta).
128/160
Description
The start temperature at Fw at which the basic setpoint starts shifting (proportionally to
the rising outside temperature).
Description The end temperature at ES at which the basic setpoint has shifted 100% (in relation to
the total shift delta).
129/160
Description At a triggered fire alarm combined with the condition set that one fan or both fans
should be running, the speed is forced to the set value. This function is only available
with the LB20 application.
6.27 Afterblowing
Description In connection with electric air heater, the fans run for afterblow (selectable time) at
normal stop of unit. This applies only when output signal for heat has been active.
There is no afterblowing at a fire alarm.
Fanoverrun 0 – 30 min 2
130/160
Powerup 0...900 s 0
Description An analog pressure sensor is used to control the respective fan. With flow control
selected, the (internal) measured pressure value is converted to a flow.
The conversion is made with a selectable K factor and the following formula:
(1 / K factor x square root of measured pressure (in Pascal)) x 1000 = current flow in l/s
131/160
Description Summer/winter compensation is used for automatic switch-over of the plant between
summer and winter operation mode. In this, the basic setpoint is shifted as a function of
the outside temperature.
3221D05
Sw ES End point for summer compensation
SS Delta (total shift) in K at end point ES
Fw Fs
FW Start point for winter compensation
Ew Es
EW End point for winter compensation
TA [°C] SW Delta (total shift) in K at end point EW
TA Outside temperature
w Setpoint change
General conditions
Delta above 0.0 is a condition for activation of the summer/winter compensation
Description
The start temperature at FS at which the basic setpoint starts shifting (proportionally to
the rising outside temperature).
Description The end temperature at ES at which the basic setpoint has shifted 100% (in relation to
the total shift delta).
132/160
Description The start temperature at Fw at which the basic setpoint starts shifting (proportionally to
the rising outside temperature).
Description The end temperature at ES at which the basic setpoint has shifted 100% (in relation to
the total shift delta).
Description With control type Casc/Supply (cascade control and supply air control) selected, the
control types will shift depending on the outside temperature. To avoid pendulating
between the control types, a selectable time must elapse before the change-over takes
place. In order to get the best result, the outside sensor should be placed on the façade
and not in the outside air duct, where the sensor may be warmed up when the unit is
switched off.
133/160
Description When the outside temperature falls below a set value, the control type changes to
supply air control after a preset time.
Delay 0...360 m 30
Description When the control type shifts from supply air control, the supply air set point value is
compensated with a set value from the default set point value.
Temp.Comp -10.0...10.0 K -2
134/160
Description Activates the cooling sequence at higher outside temperature than the set value.
Description A max limit for the output signal for cooling could be set. The function is activated if a
value <95% are set.
The sequence when the fans are changing from high too low speed and output signal
for cooling are above limit at activated solution, is that first reduces the cooling signal
too the limit and then after a 3 minutes delay fans changes too low speed.
Description Setting of the cooling signal at which DX cooling step 1 shall start. Not valid for DX-
binary.
135/160
Description Setting of the cooling signal at which DX cooling step 1 shall stop. Not valid for DX-
binary.
Description Setting of the cooling signal at which DX cooling step 2 shall start. Not valid for DX-
binary.
Description Setting of the cooling signal at which DX cooling step 2 shall stop. Not valid for DX-
binary.
Description Delay before restart of DX cooling may take place. This delay avoids unnecessary
switching of the DX steps off and on.
This parameter is valid for all DX steps.
MinTimeRestart 0...10 m 3
136/160
Description Hot-water air heaters are sensitive to frost. If the air treatment unit is switched off at
night and the outside temperature is low at start-up, the sudden intake of cold outside
air would make the water in the coils freeze. This problem is particularly obvious when
there are long pipes from the valve actuator to the air heater battery.
To get around this problem, the water circuit is pre-heated with hot water before the
outside damper and extract air damper are opened. At start-up and low outside
temperature, only the air heater heating circuit pump DO1 starts, and the heating valve
AO1 opens during a selectable time. The risk of freezing damage is eliminated, and the
unit then switches to normal control.
NB! When using a long pre-heating time, the result may be the opposite, i.e. the heater
battery may get too warm, which causes the heater battery and the heat exchanger to
close at start-up, since there is no longer any heat demand. This may cause great
variations in the start-up.
Preheating 0...50 s 0
Description Parameter for setting of minimum run time for the cooling pump and the circulation
pump.
Description Parameter for setting min. flow/pressure to allow output signal to the electric heater.
At 1-2 speed control, the pressure guard needs to signal in order for the electric heater
to release the output signal.
Description Setting of setpoint to prevent frost protection device from triggering. At risk of frost in
the heater battery, sensors in the return water control the valve actuator to open. This
setpoint is activated when the unit is in operation.
Description With the unit stopped, the temperature is controlled in the air heater to the hotkeeping
setpoint in order to prevent frost formation and facilitate start-up of the unit.
138/160
Description This parameter activates the function for cooling recovery. Cooling recovery means that
if there is a cooling need and if the outside temperature is higher than the extract air
temperature, full recovery starts (Rot-HRC or Plate-HRC) in order to make use of the
cooling energy from the room.
The outside temperature is compared with the room-/extract air temperature.
When the outside air is warmer than the room temperature, the heat recovery system
will be controlled to 100%.
If the outside air is colder than the room temperature, the HRC system is controlled in
the usual manner.
Description By controlling the exchanger to 100% at start-up, the exhaust air fan heats the heat
exchanger, thereby preventing a cold shock in the water battery. When the unit is
started at an outside temperature colder than 12oC, the output signal is set to 100%.
The heat exchanger starts at the same time as the exhaust air fan and then runs at
100%. The heat exchanger returns to automatic mode, when the supply air fan has
started and the and the selected start-up time has elapsed. The time is counted from
the time when the supply air fan has started. These function is only valid with Rot-HRC
or Plate-HRC selected. If the outside sensor is not connected, HRC will be controlled to
100% at each start-up occasion.
StartupTime 0...150 s 45
139/160
Effect When the setpoint is reached, the extract air will be transported away immediately
to allow the temperature in the exhaust air duct to rise, thereby preventing freezing.
Description This parameter sets the minimum amount of outside air to be mixed with the return air
at heat recovery demand. If Co2 control has been selected, the damper will open to the
outside air at increased Co2 level.
When the unit is stopped, the dampers close completely to the outside air (Does NOT
apply to return air damper function in extra heating sequence where stopped unit opens
dampers completely to the outside air).
MinPosDamper 0...100 % 20
Setp Co2 0...2000 ppm 800
Description When defrosting the heat exchanger, the output signal is reduced to 0%. If the air heat
does not manage to maintain the temperature, the output signal is increased for HRC to
the set value. Function description, see section 3.4.
MaxSpdDefrost 0...100 % 50
Description At triggered pressure switch or temperature below defrosting setpoint, defrosting of the
heat exchanger begins. This parameter sets the time for the duration of the defrosting.
DefrostTime 0...100 m 10
Description When the defrosting temperature falls below the set value, defrosting of plate heat
140/160
DefrostSetp
o
-10.0...30.0 C 10
141/160
Description Setting of value for min. setpoint via external signal, i.e. effective setpoint at 0V in to
UI5.
Description Setting of value for max. setpoint via external signal, i.e. effective setpoint at 10V in to
UI5.
142/160
Description Switching on / off and preselection of the fan speed can take place via an external
switch. For that purpose, the following status table is used:
If terminals DI1 and DI2 are not used, this function is in position Automatic, which
means that the plant is controlled by the internal timeswitch program.
Description In contrast to the external switch, the external button becomes active when a time is
entered under parameter TimerTime. At a pulse to DI1 or DI2, the corresponding fan
speed will start and run during the set time.
Effect Extended operation is active during the set time. When this time has elapsed, the
program returns to Automatic operation.
Parameter TimerInput TimerTime must be set to a value higher than 0.0
Description When using a pushbutton for extended operation, this parameter is used to set the
required run time.
When using a timer, this parameter must be set to 0, since the time function is then in
the timer itself.
TimerOnTime 0 – 12 h 0
Description This parameter sets the function to apply if both timer inputs are on.
143/160
Description Used to select the setpoint to be active at extended operation via timer input DI1 and
DI2. The selection is between Comfort mode and Economy mode.
144/160
Description This sets the fan speed that the fans shall assume in Night mode.
Description Night purging is used in the summer to save cooling energy by precooling the rooms
with cool outside air during the night. If only extract air sensors are used, a startup
takes place at night to determine if night cooling is required.
Note Night purging should be run several hours per night - minimum one hour. However, the
room temperature must not be allowed to fall below such a level that heating is required
in the morning.
General conditions Room temperature sensor or exhaust air sensor and outside sensor connected
Parameter for activation of night cooling must be in position On
Timeswitch program must be in position Off
Outside temperature > min. outside temperature
Outside temperature < room temperature + delta (SwitchingDifference)
Outside temperature > room temperature setpoint + hysteresis (condition for switch-on,
but not for switch-off!)
Night purge will be activated if these conditions are fulfilled. If one of the general
conditions is no longer met (with the exception of the last, which is only a switch-on
requirement), night cooling will be deactivated on completion of the min. run-time.
6.60.1 Activation
145/160
Description The minimum outside temperature can disable the night cooling function, if the outside
temperature is lower than the set value.
6.60.4 Hysteresis
Description A hysteresis is added to the room temperature setpoint as a switch-on but not switch-
off requirement. The total must be greater than the current room temperature.
6.60.5 Delta
Beskrivning If the outside temperature drops below the room temperature by the value of the
differential (delta) entered, night cooling will be activated, provided the limit values for
room and outside temperature have been reached.
Beskrivning Setting of a minimum operating time for the night cooling ensures that the plant is not
switched on and off too often.
146/160
At the end of the occupancy time, the plant is switched off (via timeswitch program).
The room temperature will then fall or rise, depending on the prevailing weather
conditions and internal loads. The «Unoccupied heating mode» or «Unoccupied cooling
mode» function is activated to ensure that no excessively low or high room
temperatures will occur.
Description If the room temperature drops below the set limit value (LimitHtg), «Unoccupied
heating mode» is started. In this case, heating is provided until the room temperature
lies 1 Kelvin above the limit value. If only extract air sensors are used, a startup takes
place at night to determine if unoccupied heating is required. Outside air dampers do
not open at start of “unoccupied heating mode” (selectable). A switch-on delay for
repeated switching on (MinTimeRestart) ensures that the plant does not switch on
too often.
Description If the room temperature rises above the set limit value (LimitClg), «Unoccupied
cooling mode» is started. In this case, cooling is provided until the room temperature
goes 1 K below the limit value. If only extract air sensors are used, a startup takes
place at night to determine if unoccupied cooling is required. Outside air dampers do
not open at start of “unoccupied cooling mode” (selectable).
A switch-on delay for repeated switching on (MinTimeRestart) ensures that the
plant is not switched on too often.
Description This parameter is used to activate / deactivate the function unoccupied heating mode.
Description This parameter is used to activate / deactivate the function unoccupied cooling mode.
Description In unoccupied heating mode, the outside air damper can be closed and the extract air
damper opened in order to circulate/cool only the extract air.
No: The unit starts without opening the damper. Exhaust air fan and HMI are blocked.
Yes: The unit starts in normal operation.
No+EF : The unit starts without opening the damper. The exhaust air fan is allowed to
start, but the HMI is blocked.
Description This parameter is used to set the temperature limit values for start of the function
unoccupied heating.
148/160
Description This parameter is used to set a minimum run time for the function Unoccupied mode. It
determines the minimum run time for each startup of unoccupied heating as well as
unoccupied cooling.
Description This parameter is used to set a delay before test of the function Night mode.
When no room sensor is being used, the temperature must be measured via the extract
air sensor. The unit therefore starts for 5 minutes during the night in order to determine
the extract air temperature. This is only done when unoccupied heating or cooling is
activated.
For unoccupied heating, the startup function is blocked during the month of July.
For unoccupied cooling or night cooling, the startup function is blocked October through
April.
149/160
Description Anti-seize operation means that the smoke dampers are run automatically at a set time.
Should a damper assume an incorrect position (detected via limit positions contacts),
an alarm will be issued (see SmokeDamper). Test of smoke dampers (anti-seize) can
also be executed via hand terminal.
Description Using the parameters below, an alarm delay time can be set for damper closing and
opening, respectively. These times should be chosen with good margin compared to
the damper’s open and close times.
STxx STxx
Closed
S2 S1 S2 Closed S1
DI3
Open Open
S6 S4 S6 S4
OpenTime 0… s 180
150/160
151/160
7.1.1 ACX52.22
7.1.2 ACX51.20
The Quadcom board handles up to four serial interfaces in parallel with communication
with, for example:
Frequency converters with USS communications
Analogue modems for remote operation via PC or palm computer (PDA).
GSM modems for remote operation via PC or palm computer (PDA); sends, in
addition, alarms via SMS.
Modbus RTU via RS485
7.1.3 ACX50.25
The LON board is used for integration in LON networks. The board has 64 standard
variables (SNVT) for important data.
152/160
Use of the tool Rainbow Loader makes it easy to load the required application into
process unit ACX32.000. Proceed as described below to load an application.
Install Rainbow Loader on your computer by clicking on ”Setup”, and follow the
instructions that appear on the screen.
Before start of Rainbow loader, the communications cable between PC and SAPHIR
must be connected and the SAPHIR be voltage-supplied.
When the Saphir has started DIL-switch 1 needs to be switched off/on. This will cause
the software to restart within a couple of seconds. At restart the Saphir will read default
values, passwords, schedules etc. and display the startup menu.
When all configurations has been made through the menu (control selection, choice of
HMI etc.), DIL-switch 2 needs to be switched off/on. As before, the Saphir will restart
and update the system according to the new configuration settings.
153/160
154/160
155/160
156/160
157/160