You are on page 1of 13

Fire Safety Journal, 14 (1988) 113 - 125 113

Quantification of Thermal Responsiveness of Automatic Sprinklers


Including Conduction Effects

GUNNAR HESKESTAD and R O B E R T G. BILL, JR.


Factory Mutual Research Corporation, 1151 Boston Providence Turnpike, Norwood, MA 02062
(U.S.A.)
(Received March 2, 1987)

SUMMARY Recently, the constancy of RTI has been


questioned b y Pepi [3] for fire situations
The response time index ( R T I ) represents where gas velocities are low at the sprinkler
the p r o d u c t o f the thermal time constant for location, as in slowly growing fires and at
the heat-responsive element o f an automatic distant sprinkler sites. Pepi found (a) that in
sprinkler and the square root o f the asso- plunge tests*, the RTI increased significantly
ciated gas velocity. The R T I and sprinkler with decreasing air velocity for b o t h conven-
temperature rating are usually sufficient to tional and fast-response sprinklers, and (b)
predict sprinkler reponse, provided gas tem- that in fire tests, response times increased
peratures and velocities generated by the fire more rapidly with distance from the fire than
at the sprinkler site are known. However, would be expected assuming constant RTI.
recent evidence has indicated that a compa- Furthermore, he found that these effects were
nion response parameter may be needed to enhanced when the thermal insulation was
quantify response for low gas temperatures reduced between the heat-responsive element
and velocities and for l o w - R T I sprinklers in and its support. Pepi attributed this behavior
growing fire situations. The companion param- to conductive heat loss from the heat-respon-
eter accounts for heat loss by conduction to sive element to its support structure. He sug-
the sprinkler mount. The technical basis and gested that a conductive heat loss might some-
m e t h o d s o f measurements o f the response times be desirable to reduce the probability
parameters are presented, along with prelim- that sprinklers operate remote from the fire
inary results o f room fire tests conducted to source.
verify the refined response model. This paper reviews the original thermal
response model leading to the RTI concept
and the plunge test devised for measuring
INTRODUCTION RTI. An attempt is then made to incorporate
conductive heat loss in the model and devise
The concept of the RTI, response time a method for characterizing this loss in the
index, for characterizing the thermal respon- laboratory. Finally, first results from a r o o m
siveness of automatic sprinklers has become fire test program to verify the modified
quite well k n o w n over the decade since it was response model are presented and certain
introduced [1], although the term was n o t consequences of the model explored.
used until later [2]. The RTI is the product
of the thermal time constant of the heat-
responsive element and the square r o o t of the ORIGINAL THERMAL RESPONSE MODEL
associated gas velocity. This parameter has The original model [1] assumes:
been claimed [1, 2] to be essentially constant (1) that the heat-responsive element of a
for a given sprinkler and orientation and to sprinkler is heated purely b y forced convec-
be sufficient, together with the sprinkler tem- tion until actuation;
perature rating, for predicting sprinkler res-
ponse for known gas temperatures and gas *Sudden immersion of sprinkler in flow of constant
velocities near the sprinkler. temperature and velocity.

0379-7112/88/$3.50 © Elsevier Sequoia/Printed in The Netherlands


114

(2) that all heat transferred to the element Experimental data on convective heating
is stored in the element with no conduction and cooling of bluff objects [4] (circular
loss to the supporting structure; cylinders, spheres) similar to typical sensing
(3) that the element heats isothermally; elements show that, for Reynolds numbers
(4) that no additional heat is required to expected in the fire environment:
actuate the element, such as heat of fusion Nu = B(Re)1/2 (4)
for solder-type sprinklers.
The heat balance on the element is: where B is a constant characteristic of the
element geometry. Using the definitions of
mc(dTe/dt) = h A ( T g - - Te) (1) N u and R e under eqn. (3), eqn. (4) gives:
where h = B ( k / p l / 2 ) u l / 2 L - 1/2 (5)
m = mass o f element
c = specific heat of element, assumed invariant Both k and v are sensitive to temperature.
with temperature However, using tabulated data on air, it turns
h = convective heat transfer coefficient o u t that k / v w2 is nearly independent of tem-
A = surface area of element perature. It follows from eqn. (5) that for a
Te = temperature o f element given sensing element (B and L constant):
Tg = gas (essentially air) temperature h oc u 1/2 (6)
t = time.
As a consequence, the time constant of a
Expressing temperatures relative to the
given element (r = m c / h A ) is proportional*
initial (ambient) temperature, To, and rear- to u -1/2 or, equivalently:
ranging, eqn. (1) becomes:
rUl/2 = constant (7)
d(ATe)/dt = T- I ( A T g - - ATe) (2)
The product r u ~/2 is a measure of the ther-
where mal inertia of a heat-responsive element, in
ATe = Te -- To principle independent of gas velocity and
ATg = T ~ - - To temperature, which is best determined experi-
r = mc/hA mentally. The term "response time index",
Equation (2) is the temperature-response or RTI, has been adopted [2] for the product,
equation of the sensing element, which can i.e.,
be solved once A T g ( t ) a n d r ( t ) are specified,
together with initial conditions (AT~(t = o) = RTI = r u 1/2 (8)
0). In terms of the RTI, the temperature-response
The quantity r has dimensions of time and relation, eqn. (2), can be written:
is referred to as the t i m e c o n s t a n t . For a given
d(ATe)/dt = (ul/2/RTI)(ATg - - ATe) (9)
heat-responsive element, the time constant
depends only on the convective heat transfer Hence, given the RTI, together with AT~ and
coefficient, h. In f o r c e d ~ o n v e c t i o n flows, the u as functions of time, the thermal response
nondimensional heat transfer coefficient, the ATe(t) can be calculated. Sprinkler actuation
Nusselt number (Nu), is uniquely related to occurs when ATe = ATea, where ATea is the
the Reynolds number ( R e ) for a given ele- actuation temperature of the heat-responsive
m e n t geometry: element above ambient.
The various assumptions of the response
Nu = f(Re) (3)
t h e o r y were originally examined in some
where detail [ 1], with the following conclusions:
N u = h L / k , Nusselt number (1) forced convection would indeed be
L = characteristic linear dimension of element the dominant mode of heat transfer to the
k = thermal conductivity of gas (assumed to heat-responsive element in most fire situations
have the properties of air) at film temperature relative to b o t h free-convection effects and
((Tg + Te)/2) radiation from the fire;
R e = u L / v , Reynolds number
u = gas velocity *The same velocity dependence of the convective
v = kinematic viscosity of the gas (air) at film heat transfer coefficient has been employed by
temperature. Pickard e t al. [5] and Alpert [6].
115

TABLE 1
U.S. s p r i n k l e r t e m p e r a t u r e r a t i n g s a n d m i n i m u m p l u n g e - t e s t t e m p e r a t u r e s [ 1 ]

Classification T e m p e r a t u r e r a t i n g range Min. air t e m p e r a t u r e

C°F) (°C) (°F) (°C)


Ordinary 135 - 170 57-77 245 118
Intermediate 175 - 225 79-107 360 182
High 250 - 300 121-149 530 277
E x t r a high 325 - 375 163-191 710 377
Very extra high 400 - 475 204-246 960 516
Ultra high 500 - 575 260-302 1180 638

(2) the element would most likely heat in from liquid bath test relative to ambient tem-
approximate isothermal manner, as assumed, perature prior to plunge) and ATg is the gas
in the sense that temperature differentials temperature relative to the ambient tempera-
within the element would generally be small ture. For the range of gas velocities covered,
compared to the average temperature rise of 1.5 - 5.2 m/s, it was determined in special
the element from ambient conditions; experiments [1] that the gas temperatures
(3) assuming negligible actuation heat m a y had to exceed certain limits, depending on the
be questionable for heavily solder-loaded, sprinkler temperature rating, in order to
heat-responsive elements, depending on the prevent radiant heat loss from the sprinkler
effective solder fraction which has to be fused to the tunnel walls (uninsulated at the test
before the element actuates; section) from affecting the RTI measurement.
(4) quantitative estimates of conduction The temperature limits are listed in Table 1.
heat loss from an element are so difficult that Above these limits, 10 different sprinkler
the errors associated with ignoring this loss models responded with fairly constant RTI
are n o t readily assessed. over the velocity range examined and up to
An experimental program was conducted the maximum attainable gas temperature,
to examine the constancy of RTI for com- 430 °C. Among the sprinkler models exam-
mercial sprinklers [1]. The sprinklers were of ined, RTI varied in the range 136 - 346
the conventional response, industrial type; m In s w2. In these tests the sprinklers were
fast-response sprinklers had n o t yet entered positioned near their most sensitive orienta-
the market. A plunge test* was adopted for tions in the test stream, the frame being in a
measuring RTI, wherein a sprinkler was sud- plane perpendicular to the flow. Other tests
denly immersed in the steady flow in the indicated that effects of orientation on RTI
(horizontal) test section of a hot,air tunnel. could occasionally be significant in the rela-
The test sprinkler was attached to a fitting in tively smooth test stream, always associated
a plate which was rapidly positioned over the with the heat-responsive element being in the
open t o p of the test section in the plunge wake of a frame arm (frame in a plane aligned
operation. The sprinkler was pressurized with with the flow). However, such effects were
air to a b o u t 35 kPa. For a plunge test, the smaller in the turbulent ceiling flow of a
solution of eqn. (9) can be written in the test fire, presumably because the wake no
following form for RTI: longer stayed fixed on the heat-responsive
--tr ul/2 element.
RTI = (10) The insensitivity of RTI to gas temperature
ln(1 -/XToa/aTg) in these experiments m a y be interpreted* to
where t~ is the response or actuation time; u mean that the heat of fusion of the solder for
is the gas (air) velocity in the test section; the solder-type sprinklers was not impor-
A T e a is A T e a t response (temperature rating tant**. Furthermore, none of the (small)
*With t h e aid of eqn. (17) in ref. 1.
*A r a m p t e s t h a s b e e n used b y o t h e r s [7 ], w h e r e * * E v a n s a n d M a d r z y k o w s k i [ 8 ] have since investi-
t h e test s p r i n k l e r is e x p o s e d t o a linear r a t e o f rise in g a t e d s e p a r a t e l y t h e c o n t r i b u t i o n of t h e h e a t o f
gas t e m p e r a t u r e . fusion to the RTI measurement.
116

variations observed in the RTI could be attri- ture relative to the set point. The plunge-test
buted to conduction heat loss. tunnel is capable of test-section velocities up
to approximately 3.5 m/s. Maximum obtain-
able air temperature is in excess of 400 °C,
FMRC PLUNGE TEST which makes it possible to test sprinklers up
to the "extra high" temperature rating (Table
Based on the first experimental program, a 1). The test sprinkler is m o u n t e d in a detached
special plunge-test tunnel was designed and cover which is inserted into a hinge m o u n t e d
calibrated for further work [ 1, 2]. This tun- on top of the upstream end of the test section.
nel still serves as FMRC's plunge-test appara- To perform a plunge operation, the operator
tus. Figure 1 illustrates the schematic design. removes an idling cover over the test-section
Air heated electrically by heating rods is di- opening and immediately closes the cover
rected into a mixing duct via an orifice. The with the test sprinkler. The plunge operation
orifice serves the dual functions of metering closes a mercury switch which starts a timer.
the flow (in conjunction with pressure taps The timer is stopped by a pneumatic switch
in the plenum and the mixing duct) and inter- when air pressure is released at the actuation
acting with the mixing duct to generate uni- of the sprinkler.
form temperature and velocity profiles suffi- An extensive test program [2] was con-
ciently far downstream of the orifice. The ducted in the FMRC plunge-test tunnel. First,
circular mixing duct is transformed to a duct four sprinkler models, two solder-type and
of rectangular cross section which serves as two bulb-type, and each at three temperature
a test section (300 mm wide X 150 mm high). ratings ("ordinary", "high", and "extra
Turbulence-reducing screens are installed at high"), were tested at combinations of five
the inlet to the test section. The return flow air temperatures in the range 127 - 400 °C and
is taken to the blower inlet via two right-angle three gas velocities of 1.54, 2.56 and 3.48 m/s.
bends. To reduce the heat load, the entire RTI values were quite uniform above the
apparatus, except the test section, is insulated; minimum plunge-test temperatures listed in
the test section is bare to prevent high wall Table 1. However, there was a slight tendency
temperatures from contributing excessive to higher RTI values at the lowest gas velocity
radiant heating to the sprinkler under test. which, in retrospect, may be attributed to
Flow is controlled with a sliding gate at the conduction effects as discussed in the next
blower exit. A temperature control thermo- Section. For subsequent work, nominal test
couple is m o u n t e d between the screens up- temperatures were standardized at the values
stream of the test section; this thermocouple listed in Table 2, combined with a standard
is connected to a temperature controller/ test velocity of 2.56 m/s. Twenty-three
power controller which feeds electric power sprinkler models, both solder and bulb types
to the heating rods to maintain test tempera- and each at three to seven temperature ratings
( " o r d i n a r y " through "extra high"), were
2.3m plunged-tested. Tests were conducted in tri-
Press. Diff. plicates for each model and temperature
,~w Rate
rating, and an average RTI was determined.
, Rectangular
Round Mixin~lDuct Test Section

TABLE 2
Standard, nominal plunge-test temperatures selected
for FMRC plunge-test tunnel

Classification Air temperature

........... f (°C) (°F)

Ordinary through 191 375


intermediate
Blower
High 282 54O
Fig. 1. Schematic design of FMRC plunge-test tunnel. Extra high 382 720
Test section is 300 mm wide X 150 mm high.
117

For a given sprinkler model, the average RTI where C Can be considered a conduction (loss)
generally did n o t vary much with the temper- parameter, a characteristic of the sprinkler. In
ature rating, consistent with expectations terms of C, eqn. (13) becomes:
assuming identical geometry and material d(ATe) u 1/2
of the heat-responsive element from one - [ATg - - ( 1 + C/ul/2)ATe] (15)
temperature rating to the next. Averaged over dt RTI
the available temperature ratings for each Hence, instead of a one-parameter response
sprinkler model, the smallest RTI was 125 equation in RTI, we now have a two-parameter
m 1/2 s 1/2 and the largest was 332 m 1/2 S 1/2, response equation in RTI and C. Conveniently,
nearly a threefold variation. The reproducibil- while the units of RTI are (length X time) 1/2,
ity of the RTI measurement in the particular the units of C are (length/time)1z2.
apparatus was estimated to be within +2 - Equation (15) can be transformed into a
+3%, depending on the temperature rating. very useful form whenever the gas velocity,
Variations in replicate tests can be larger u, is constant as in a plunge test, or does not
because of nonuniformities among sprinkler change sufficiently rapidly with time* (appears
samples. to be practically always the case in fire situa-
tions). Then:
(1 + C/u 1/2) d(ATe) _ d[(1 + C/ttl/2)ATe]
INCORPORATION OF CONDUCTIVE HEAT LOSS dt dt
IN R E S P O N S E M O D E L (16)
and eqn. (15) can be written:
On the first reports of definite effects of
conductive heat loss in the response of sprin- d ( A T e v ) / d t = ( u l n / R T I v ) [ A T g -- ATev] (17)
klers [3], efforts were made to incorporate where
such effects in the original response model.
The simplest possible form of conductive ATev = (1 + C/ul/2)ATe (18)
heat loss rate was assumed, proportional to RTI~ = RTI/(1 + C/u i n ) (19)
the temperature difference b e t w e e n the heat-
responsive element and the sprinkler fitting. Note that eqn. (17) is precisely in the form of
Assuming the sprinkler fitting is essentially at the original model response relation, eqn. (9),
ambient temperature, the conductive heat loss where ATe is replaced b y ATe~ and RTI is
rate would be proportional to the tempera- replaced b y RTI~. The quantity ATev can be
ture rise of the element. With a conductive considered as a virtual temperature rise of the
heat loss term, eqn. (1) becomes: heat-responsive element, and RTIv can be con-
sidered as a virtual RTI.
m c ( d T e / d t ) = hA(Tg -- Te) -- C'(Te -- To) (11) The solution of eqn. (17) for a plunge test
(or fire generating constant temperature and
where C' is a constant for a given sprinkler. velocity) is obtained from eqn. (10) b y replac-
The equivalent to eqn. (2) now becomes: ing RTI with RTIv and ATea with ATeva. The
result is:
d(ATe) C'
- v-l(ATg -- ATe) -- - - ATe (12) RTI --trttI/2
dt mc
1 + C/u 1/2 in(1 --ATea(1 + C / u i n ) / A T g )
or, rearranging and using eqn. (8): (20)

d tT e ) - U l /RT---I Generalizing the solution to any instant, t, of


d(A 2[ ATg-- ( 1+ E
C ' )R A
TIT
\_ e l ]
the heating process, the solution for ATe is:
(13)

Now, if C' and RTI are constants for a sprin- *Turbulent fluctuations axe not considered here.
kler, so is C'RTI/(rnc). Consequently, define: Turbulent fluctuations in u and A T g will cause small
A T e ripples in the element response and these are
C = C'RTI/(mc) (14) ignored.
118

ATg greatly with the gas temperature and gas


ATe 1 + C/u 1/2 [1 - - e x p velocity.
In the example of Fig. 2, it is implicitly
-- ( t u l / 2 ( 1 + C / u a J 2 ) / R T I ) ] (21) assumed that the sprinkler fitting remains at
As an illustration, consider a sprinkler with the ambient temperature during the exposure,
RTI = 200 m 1/z s 1/2, exposed to fire gases at an assumption used in the derivation of eqn.
1 m/s velocity and a temperature above am- (17). In a real fire situation, one may expect
bient of 110 °C. The thermal response now some heating of the fitting, either directly by
depends on the conduction parameter, C. hot gases or indirectly by heat conducted
Figure 2 shows the temperature rise ATe as a away from the sprinkler. This situation can
function of time, calculated from eqn. (21) be easily handled if the temperature rise of
for C = 0 (no conduction heat loss) and for the sprinkler m o u n t or fitting is known. Re-
C = 1 (m/s) 1/2 (a realistic value). For C = 0, turning to eqn. (11), the conduction term is
the element reaches an actuation temperature now - - C ' ( T e - - T f ) , where Tf is the fitting
rise of 50 °C at 120 s; for C = I (m/s) 1/2, temperature. The new form can be written:
actuation occurs much later, at 240 s. In fact, - - C ' ( T e -- Tf) = - - C ' A T ~ + C ' A T f (22)
it is readily verified from eqn. (21) that had
the conduction parameter been larger than where ATf = Tf -- To, the rise in temperature
1.2, the sprinkler would never have actuated. of the sprinkler fitting. The correction term,
Alternatively, there would have been no C ' A T f , produces in eqn. (15) an additive term
actuation if the gas velocity had been lower inside the square brackets:
than 0.69 m/s. If the gas velocity had been dATe u 1/2
2 m/s instead of 1 m/s, response times for - -- [(AT~ + ( C / u l / 2 ) A T f )
dt RTI
C = 0 and C = 1 (m/s) 1/2 would have been
86 s and 126 s, respectively, considerably -- (1 + C/ul/2)/XTe] (23)
closer than for 1 m/s. If the gas temperature Similarly, the revised form of eqn. (17) be-
had been 200 °C above ambient rather than
comes:
110 °C, response times for C = 0 and C = 1
(m/s) 1/: would have been 58 s and 69 s, res- d( A T ~ v ) / d t = (u x/Z/RTIv)
pectively, again considerably closer than in × [(ATg + ( C / u l / 2 ) A T f ) -- ATev] (24)
the base case. Clearly the conductive heat loss
effect associated with a given value of C varies From these forms it is clear that in order to
accommodate a temperature rise in the sprin-
kler fitting, the instantaneous fitting tempera-
120 J I I l I ture function ( C / u l / 2 ) A T f is added to the
instantaneous gas temperature rise ATg, to
~'~ 100
produce a pseudo gas temperature rise.

IuJ
o~ 8o P R E L I M I N A R Y T E S T OF M O D I F I E D M O D E L

n,, 60 An experimental program is now underway


at FMRC to investigate the efficacy of the
response model as modified to accommodate
n conductive heat loss from the heat-responsive
IM element. A few results obtained to date are
I---- 20 reviewed in this Section.
The program consist of two parts, (1) a
O0 I i I I L laboratory determination of the RTI value
50 100 150 200 250 300
and conduction parameter C using the FMRC
TIME (s)
plunge test tunnel, and (2) room fire tests
Fig. 2. T e m p e r a t u r e rise o f a h y p o t h e t i c a l (RTI = 200
m 1/2 s xt2 sprinkler in e n v i r o n m e n t o f c o n s t a n t t e m p -
comparing actual response times to predic-
p e r a t u r e (ATg = 110 °C) and velocity (1 m/s) for t w o tions based on the model and laboratory
d i f f e r e n t values o f the c o n d u c t i o n p a r a m e t e r . values of RTI and C. Attention in this paper
119

will be focused on measurements involving which can be solved for C. In order to deter-
t w o solder-type, pendent sprinklers: a conven- mine Uc, a series of standard test velocities
tional response model, sprinkler A; and a fast- were selected for the plunge-test tunnel, the
response model, sprinkler B. Both of these square r o o t of the ratio of sequential test
sprinklers were rated at 74 °C, although their velocities being fixed at 1.10. For each test
liquid-bath operating temperatures (slightly velocity, a sprinkler was exposed for 10 min-
lower) were used in the calculations. utes (deemed sufficient to establish steady-
The selected sprinklers are of "ordinary" state element temperature) until actuation
temperature rating, and the nominal air tem- was bracketed between t w o successive test
perature listed in Table 2 for this temperature velocities. The conduction parameter was
rating, 191 ~C, was used in the FMRC plunge- taken as the average of the values C calculated
test tunnel, together with the standard air for the bracketing velocities, using eqn. (25).
velocity of 2.56 m/s, to determine the RTI Hence, the conduction parameter in this pro-
values of the sprinklers. RTI values were cedure can be assumed to have been estab-
determined b y two methods: (a) first ignor- lished to an accuracy of 10%. In order n o t to
ing the existence of a conduction heat loss require unreasonably low air velocities, the
using eqn. (10), termed "apparent R T I " , fairly low test temperature of 127 °C was
(2) then incorporating the conduction param- chosen, which is still above the (radiation)
eter, C, and calculating RTI according to limit in Table 1 for "ordinary" temperature
eqn. (20). However, first, the conduction rating.
parameter had to be determined. The results of the plunge tests and the
The conduction parameter, C, was mea- prolonged-exposure tests are summarized in
sured in a specially devised test in the plunge- Table 3. It is seen that the RTI of sprinkler B
test tunnel, where the sprinkler m o u n t (fitting) is only 1/8 of that for sprinkler A, while the
was held at constant temperature over a pro- conduction parameter of sprinkler B is a b o u t
longed period b y circulating cold (tap) water 1/3 of that for sprinkler A.
through the mount. The m o u n t temperature, The r o o m fire tests employed a test r o o m
measured with a thermocouple, was carefully within a larger test building, Fig. 3. The r o o m
monitored. According to the response model, measured 3.66 m × 7.32 m × 2.44 m high and
the steady~tate temperature rise (referenced was made from w o o d studs and ½-in. gypsum
to the m o u n t temperature) of the heat- board. There was only one opening to the
responsive element in a prolonged response is room, an open door at one end. A fire source
given b y the factor in front of the square was placed near the opposite end, and ceiling
brackets in eqn. (21), i.e., b y hTg/(1 + C/ul/2). sprinklers together with associated instru-
As the gas velocity is increased to a higher ments were located at distances from the fire
value from one prolonged exposure to the source of 1.63 and 4.55 m. Each ceiling
next, the steady-state temperature rise of the station incorporated a sprinkler A and a
element increases. For a sufficiently high air sprinkler B, screwed into ~-m.1 • (steel) pipe
velocity, Uc, the element will just actuate in a couplings extending d o w n 0.038 m from the
prolonged exposure. At that point: ceiling, attached to pipe nipples above the
roof. Each nipple was fitted to the center of
ATg/(1 + C/Uc 1,2) -~ ATea (25) a 1.6-m-long, 1-in.<lia. horizontal steel pipe

TABLE 3
Response parameters for tested sprinklers

Sprinkler Operating* Apparent** RTI RTI C


temp. (°C) (m 1/2 s 1/2) (m I/2 s 1/2 ) (mt/2js t/2)

A 72.1 249 200 1.56


B 72.7 27 25 0.54

*From liquid bath tests.


**According to eqn. (10) using measurements at standard plunge-test conditions for " o r d i n a r y " temperature
rating: 191 °C temperature, 2.56 m/s velocity.
120

-'- 3.66

t
Y~
FIRE SOURCE

! ! •

NEAR STATION
SPRINKLER /
\ \THE 0uP

~- 0.076

FAR STATION

I I
OPEN DOOR
(1.18 x 2.06 HIGH)
Fig. 3. Fire r o o m w i t h t w o sprinkler a n d i n s t r u m e n t s t a t i o n s at t h e ceiling. The fire source, e i t h e r a h e p t a n e p o o l
o r w o o d crib, r e s t e d o n a weighing p l a t f o r m o n t h e floor. All d i m e n s i o n s are in meters.

above the r o o f with 0.13-m-high risers open sensing level of 0.076 m beneath the ceiling,
t o the atmosphere at b o t h ends. After a sprin- very nearly the level of the center of the
kler had been installed for testing, the pipe to heat-responsive element of each sprinkler.
which it was m o u n t e d was filled with water. The fire source used was either a 0.46-m-
A thermocouple monitored the water temper- dia. pool of heptane floated on water, or a
ature within the water-way of each sprinkler. wood crib {pine) measuring 0.51 m X 0.51 m
To record actuation times, metal electrodes X 0.38 m high made from 19-mm square
were positioned in the path of the weak spray sticks (8 sticks per layer, 20 sticks high).
produced when the sprinklers actuated, the Remote ignition with an electric match was
spray completing an electric circuit which was employed, in the case of the wood crib, via a
monitored. Along with the two sprinklers at a 0.10-m-dia. pan of heptane underneath the
ceiling station, there were two thermocouples central shaft of the crib. Both fire sources
to measure gas temperature and one bidirec- were continuously weighed on load platforms
tional flow probe (connected to an electronic to monitor the mass-loss rate. The ceiling
manometer) to measure gas velocity, all at a clearances above the fire sources were 2.24 m
121

20O
for the heptane pool and 1.90 m for the w o o d r
crib.
One heptane pool fire, test 8, and one w o o d ~ lO0

crib fire, test 19, will be considered here;


detailed calculations have not y e t been made,
0 , • j
at this writing, for other tests. In test 8, the • 0 150 SECONDS 300
mass-loss rate of the heptane pool attained a (a) SPRINKLER RESPONSE TEST S

steady value of 3.50 g/s after 25 s, which cor- 3


responds to a heat release rate of 133 kW
when a combustion efficiency for heptane of 2

85% is assumed [9]. For the w o o d crib fires,


which employed a different load platform N i

than the pool fires, the load platform was


damaged b y water at the end of the first test
with this fuel, test 17. In test 17, the mass- .!
. . . . . . . . . :1~ . . . . sE~o~'os' ~oo'
loss rate, together with an assumed actual (b) SPRINKLER RESPONSE TEST S
heat of combustion [9] of 12 500 kJ/kg, indi-
cated that the fire growth could be repre- S

sented by: ~2
Q (kW) = 1 0 0 0 [ ( t -- to)/tg] 2 (26)
where* the "growth time", tg, was 256 s and
the effective ignition time, to, was 29 s. The > 0 o

temperature data under the ceiling for test 19 _|

closely matched the data for test 17 when the 0 "150 SECONDS 300
(C) SPRINKLER RESPONSE TEST S
time axis for test 19 was shifted 22 s to smaller
times. Hence, it may be assumed that test 19 Fig. 4. Heptane pool fire (test 8): gas temperatures
and velocities at ceiling instrument stations. (a)Tem-
also behaved according to eqn. {26), with perature at near station (top) and far station (bot-
tg = 256 s and to = 2 9 - - 22 = 7 s. tom); (b) velocity at near station; (c) velocity at far
Figure 4 presents gas temperatures and station.
velocities measured at the instrument stations
(sprinkler sites) for the heptane pool fire. In Response times were calculated from eqn.
Fig. 4(a), it can be seen that the two thermo- (24), with eqns. (18) and (19), using RTI and
couples at each station indicated very similar C values from Table 3, the data in Figs. 4 and
temperatures. The spikes on the curves were 5, as well as the ATf data. Each temperature
due to electronic noise. The velocity data in curve (Figs. 4(a) and 5(a)), " c o r r e c t e d " for
Figs. 4(b) and 4(c) also exhibit a few elec- ( C / u l / 2 ) A T ~ (see eqn. (23)), was approxi-
tronic noise spikes. Data for the w o o d crib mated b y a sequence of linear segments*
fire are presented in Fig. 5. This time, the t w o over which u 1/2 was considered constant at
thermocouples at the near station {Fig. 5(a)) the average value for the interval. An analy-
indicated slightly different temperatures, and tical solution exists for eqn. (24) over such
no electronic noise can be discerned in the a linear segment, according to which the res-
velocity data (Figs. 5(b) and 5(c)). In addi- ponse of the heat responsive element can be
tion to the measurements in Figs. 4 and 5, followed from one segment into the next
data on the fitting temperatures (measured until response occurs (ATe = ATea).
as temperatures in sprinkler water-ways) were Calculated response times are compared to
available; ATf until sprinklers operated ranged experimental response times in Fig. 6. All the
from 0 °C to 22 °C for the heptane pool fire
and from 3 °C to 17 °C for the crib fire. *For the heptane pool fire, the following time end
points were selected for the linear segments: 0, 69,
144, 240 s (near station) and 0, 7.5, 71, 144, 240,
300 s (far station). The time end points selected for
*It is implied in eqn. (26) that the growth time, tg, the wood crib fire were: 0, 24, 54, 98, 116, 150 s
is the time required for a fire, growing in heat release (near station) and 0, 35, 61.5, 88, 140, 190 s (far
rate with the square of time, to exceed 1000 kW. station).
122

500 300
, , //
400
/
bJ
=J /
300
i-
200
/
¢n
200 z
o
(n ,/
100
r, /
0
= i , , , , , , , : 100. . . . . . SECONDSa = 2"00 p ::D
1 O0 2
(a) SPRINKLER RESPONSE TEST t 9 q

3
/
0 I i
1O0 200 300
EXPERIMENTAL RESPONSE TIME ( e )

Fig. 7. Like Fig. 6, except calculated response times


based on C = 0 and apparent RTI (Table 3).
~o-

-!
data fall near the dashed line representing
. . . . . . :io~ .... SE~ONbS' 200'
SPRINKLER RESPONSE TEST 19
perfect correlation. At the upper right corner
(b) is shown a triangle (far station in heptane
3 pool fire) with an arrow; in this case, the
sprinkler did not operate in the test interval
and neither did the calculation indicate that
it would.
i'
~o
Suppose one ignores the conduction effect
(C = 0) and calculates response according to
the apparent RTI listed in Table 3. Figure 7
• , , , , . . . . . . • , , , , ,
-I
'lO0 SECONDS 200 gives the results in the same form as Fig. 6.
(c) SPRINKLER RESPONSE TEST 19
The crib fire data {solid symbols) exhibit
Fig. 5. Wood crib fire (test 19): gas temperatures and only slightly worse correlation, calculated
velocities at ceiling instrument stations. (a) Tempera- versus experimental, than in Fig. 6, whereas
ture at near station (top) and far station (bottom};
(b) velocity at near station; (c) velocity at far station.
the pool fire data exhibit considerably less
favorable correlation. For example, whereas
sprinkler A at the far station did not operate
, , // in the pool fire, it did operate in the calcula-
tion (at 255 s).
i.i
Many pairs of data, laboratory (RTI, C)
=
I--
A and fire tests, remain to be analyzed. It might
,., 200 / be of interest to point out that the C value
pertaining to sprinkler A, 1.56 ml/2/s 1/2
(Table 3), is the largest value observed to date
among eleven sprinkler models examined, the
° 100 / lowest being about 0.5 m1/2/sl/2.
q

SOME MODEL PREDICTIONS


/
0 i l
1 O0 200 300 Most accidental fires grow with time and
EXPEmMENTALRESPONSETiME (=)
the growth model represented by eqn. (26),
Fig. 6. C o m p a r i s o n o f c a l c u l a t e d a n d e x p e r i m e n t a l
where the heat release rate grows with the
sprinkler response times for sprinkler A (triangles)
and sprinkler B (circles). Open symbols pertain to square of time, is quite realistic. The growth
heptane pool fire and solid symbols pertain to wood time to 1000 kW output, t~, may vary from
crib fire. The dashed line represents perfect correlation. less than 10 s to more than 500 s in industrial
123

fires [10]. The typical home fire m a y be in tg, to a new value in Fig. 8 is to change the
the tg range 150 - 300 s. RTI corresponding to a given QR b y the ratio
Response calculations have been paramet- of new value tg to original value tg. Hence, the
rized in the variable RTI and C for a given curves for a larger tg (slower fire growth)will
fire scenario: tg= 146 s; ceiling clearance be flatter, and effects of C at a given RTI will
above the fire source of 2.44 m; distance be larger than before. Conversely, the curves
under the ceiling from the fire axis of 2.15 m; for a smaller tg (faster fire growth) will be
an ambient temperature of 24 °C and a sprin- steeper, and effects of C at a given RTI will
kler temperature rating of 74 °C. Using simpli- be smaller than before. Overall then, effects
fied formulas [11] which assume large flat of C b e c o m e increasingly more important as
ceilings and quasi-steady fires (flow under RTI decreases and fire growth becomes slower.
ceiling adjusts to instantaneous heat release Each combination o f RTI and C in Fig. 8
rate), the temperature and velocity can be gives rise to an apparent RTI, i.e., the RTI
calculated at the sprinkler site. Response is measured in a standard plunge test (Table 3)
then predicted in the manner of the preceding assuming C = 0. In Fig. 9 the heat release
Section, using predicted temperature and rates at response in Fig. 8 have been plotted
velocity instead of experimental values. How- as a function of the apparent RTI. The effect
ever, instead of response time, the more of C is quite large at low apparent RTI, b u t is
meaningful measure for a growing fire of heat less significant at the higher values of apparent
release rate at response, QR, is adopted as a RTI. For instance, for apparent RTI in the
criterion of sprinkler responsiveness. range 125 - 332 m 1/2 s 1/2, the ffect of increas-
Figure 8 presents the heat release rate at ing C from 0 to 2 ml/2/sl/2 varies from a 30%
response as a function of RTI for three con- increase in QR at the lower RTI to practically
duction parameters: C = 0, 1, and 2 ml/2/s 1/2. no effect on QR at the higher RTI. The appar-
Although there is a clear effect throughout of ent RTI range, 125 - 332 m 1/2 s 1/2, pertains
the conduction parameter, the relative effect to the 23 "conventional response" sprinkler
is strong only at low values of RTI. For in- models investigated in the FMRC test pro-
stance, at RTI = 25 ml/2/s ~/2, the heat release gram [2] discussed previously.
at response more than doubles as C ranges The finding that the conduction parameter
from 0 to 2 ml/2/s 1/2. is important primarily for low-RTI sprinklers
It can be shown from the basic equations pertains to growing fires, hence would apply
that the effect of changing the growth time, to the operation of the first sprinkler in most
fire scenarios. After the first sprinkler oper-
2000 L I I I I ates, the heat o u t p u t of the fire m a y begin to
decrease or at least not increase. In a leveled-
I
.C=2 mL/2/! x/2
I S00 // • c-]. ml/Z/Bl/2
t " .."
// ..... c=o 2000 J ~ a
/, ,..."
/. .,-
1200 / -"
~: //...""
,.~ / ,..' 1600
/ .."
./ ..'
O 800 // ......
A 1200 f

~ 7,+.'"
400
0 800 /
1" ...'

.."

I I I I
0 100 200 300 400 500
400
RTI (mi/25 I/2)
Fig. 8. P r e d i c t e d h e a t release rates at sprinkler res-
p o n s e as f u n c t i o n o f R T I f o r various c o n d u c t i o n I r ] I

p a r a m e t e r s C a n d a given, growing-fire scenario: tg =


o Ioo 200 300 +oo 500
146 s; ceiling clearance = 2.44 m ; d i s t a n c e o f sprin- APPARENT RTI (ml/251/2)
kler f r o m fire = 2.15 m; e l e m e n t t e m p e r a t u r e rise t o Fig. 9. P r e d i c t e d h e a t release rates at sprinkler res-
a c t u a t e = 50 °C. p o n s e in Fig. 8 p l o t t e d as a f u n c t i o n o f a p p a r e n t RTI.
124

off heat-release-rate situation, additional using RTI from standard plunge tests in the
sprinklers may or may not operate, and here FMRC plunge-test tunnel, and conduction
the conduction parameter will be important parameters, C, from "prolonged exposure"
for both low- and conventional-RTI sprinklers. tests at different velocities in the plunge-test
tunnel.

CONCLUSIONS
LIST OF SYMBOLS
(1) Of the several assumptions entering the
original sprinkler response theory leading to A surface area of heat-responsive ele-
the concept of constant RTI, two assump- ment
tions could not be justified a priori: (a) negli- B nondimensional constant
gible actuation heat for the heat-responsive C conduction parameter; see eqn. (14)
element (as associated with solder, for in- C' conduction coefficient
stance), and (b) insignificant conductive heat C specific heat of heat-responsive ele-
loss from element. ment
(2) The first experimental program con- h convective heat transfer coefficient
ducted at FMRC to study the constancy of k thermal conductivity of heat-respon-
RTI for industrial type sprinklers, incorporat- sive element
ing gas velocities of 1.5 m/s and higher, sug- L characteristic linear dimension of
gested that the actuation heat was not impor- heat-responsive element
tant. Furthermore, variations observed in RTI m mass of heat-responsive element
could not be attributed to conductive heat Nu hL/k, Nusselt number
loss. Q heat release rate
(3) RTI values measured subsequently in QR Q at sprinkler response
the FMRC plunge-test tunnel for velocities in Re uL/v, Reynolds number
the range 1.5 - 3.5 m/s and several air temper- RTI ru ' n , response time index of heat-
atures, selected above a limit to preclude responsive element
significant radiation effects, were found to be RTIv virtual KTI
quite uniform, although with some tendency Te temperature of heat responsive ele-
to increase at the lowest velocity investigated. ment
(4) Triggered by recent reports on signifi- T~ temperature of sprinkler fitting or
cant effects of conductive heat loss in certain mount
fire situations, modifications have been pro- gas or air temperature
posed for the original response theory to To initial or ambient temperature
accommodate such effects. The conductive ATe Te -- To
heat loss rate has been assumed proportional ATea ATe at actuation of sprinkler
to the difference in temperature between the ATev virtual temperature rise of heat-
heat-responsive element and the sprinkler responsive element
fitting. In the modified model, the response ATeva ATev at actuation of sprinkler
of a sprinkler for a given fire environment and ATf Tf -- To
temperature rating depends on two param- Tg -- To
eters, the RTI and a conduction parameter, C. t time
(5) According to the modified sprinkler tg growth time of fire to I000 k W for
response model, conductive heat loss effects fire growing with square of time
are primarily important at low gas tempera- to effective ignition time
tures and velocities. For rising temperatures tr response or actuation time of sprin-
and velocities, as in growing fires, conduction kler
effects become increasingly more important U gas or air velocity
as RTI decreases and fire growth becomes Uc limiting air velocity for sprinkler
slower. response
(6) Response times of sprinklers in specially V kinematic viscosity
designed room fires were found to be consis- T time constant of heat responsive
tent with calculations according to the model, element
125

REFERENCES ceiling-mounted fire detectors, Fire Technol., 8


(1972) 181 - 195.
1 G. Heskestad and H. F. Smith, Investigation o f a 7 FRS Wind Tunnel for Sprinkler Evaluation, BRE
New Sprinkler Sensitivity Approval Test: The Research for Industry, Building Research Estab-
Plunge Test, FMRC 22485, F a c t o r y Mutual Re- lishment, Department of the Environment, U.K.,
search Corporation, Norwood, MA, December, 1984.
1976. 8 D. D. Evans and D. Madrzykowski, Characterizing
2 G. Heskestad and H. F. Smith, Plunge Test for the Thermal Response of Fusible-Link Sprinklers,
Determination of Sprinkler Sensitivity, FMRC NBSIR 81-2329, National Bureau of Standards,
3AIE2.RR, Factory Mutual Research Corpora- Washington, DC, August, 1981.
tion, Norwood, MA, December, 1980. 9 G. Heskestad, A Fire Products Collector for
3 J. S. Pepi, Design Characteristics of Quick Res- Calorimetry into the MW Range, FMRC 0C2E1.
ponse Sprinklers, Grinnel Fire Protection Sys- RA, Factory Mutual Research Corporation, Nor-
tems Company, Providence, Rhode Island, May, wood, MA, June, 1981.
1986. 10 Guide for Smoke and Heat Venting, NFPA
4 W. H. McAdams, Heat Transmission, McGraw-Hill 204M-1982, National Fire Codes, Vol. 15, Na-
Book Co., New York, 1954, pp. 266 - 267. tional Fire Protection Association, Quincy, MA,
5 R. W. Pickard, D. Hird and P. Nash, The Thermal p. 204M-1.
Testing of Heat-Sensitive Fire Detectors, Fire 11 G. Heskestad, Similarity Relations for the Initial
Res. Note No. 247, Fire Research Station, Bore- Convective Flow Generated by Fire, Paper No.
hamwood, January, 1957. 72-WA/HT-17, American Society of Mechanical
6 R. L. Alpert, Calculations of response times of Engineers, November, 1972.

You might also like