Professional Documents
Culture Documents
Quantification of Thermal Responsiveness of Automatic Sprinklers Including Conduction Effects
Quantification of Thermal Responsiveness of Automatic Sprinklers Including Conduction Effects
(2) that all heat transferred to the element Experimental data on convective heating
is stored in the element with no conduction and cooling of bluff objects [4] (circular
loss to the supporting structure; cylinders, spheres) similar to typical sensing
(3) that the element heats isothermally; elements show that, for Reynolds numbers
(4) that no additional heat is required to expected in the fire environment:
actuate the element, such as heat of fusion Nu = B(Re)1/2 (4)
for solder-type sprinklers.
The heat balance on the element is: where B is a constant characteristic of the
element geometry. Using the definitions of
mc(dTe/dt) = h A ( T g - - Te) (1) N u and R e under eqn. (3), eqn. (4) gives:
where h = B ( k / p l / 2 ) u l / 2 L - 1/2 (5)
m = mass o f element
c = specific heat of element, assumed invariant Both k and v are sensitive to temperature.
with temperature However, using tabulated data on air, it turns
h = convective heat transfer coefficient o u t that k / v w2 is nearly independent of tem-
A = surface area of element perature. It follows from eqn. (5) that for a
Te = temperature o f element given sensing element (B and L constant):
Tg = gas (essentially air) temperature h oc u 1/2 (6)
t = time.
As a consequence, the time constant of a
Expressing temperatures relative to the
given element (r = m c / h A ) is proportional*
initial (ambient) temperature, To, and rear- to u -1/2 or, equivalently:
ranging, eqn. (1) becomes:
rUl/2 = constant (7)
d(ATe)/dt = T- I ( A T g - - ATe) (2)
The product r u ~/2 is a measure of the ther-
where mal inertia of a heat-responsive element, in
ATe = Te -- To principle independent of gas velocity and
ATg = T ~ - - To temperature, which is best determined experi-
r = mc/hA mentally. The term "response time index",
Equation (2) is the temperature-response or RTI, has been adopted [2] for the product,
equation of the sensing element, which can i.e.,
be solved once A T g ( t ) a n d r ( t ) are specified,
together with initial conditions (AT~(t = o) = RTI = r u 1/2 (8)
0). In terms of the RTI, the temperature-response
The quantity r has dimensions of time and relation, eqn. (2), can be written:
is referred to as the t i m e c o n s t a n t . For a given
d(ATe)/dt = (ul/2/RTI)(ATg - - ATe) (9)
heat-responsive element, the time constant
depends only on the convective heat transfer Hence, given the RTI, together with AT~ and
coefficient, h. In f o r c e d ~ o n v e c t i o n flows, the u as functions of time, the thermal response
nondimensional heat transfer coefficient, the ATe(t) can be calculated. Sprinkler actuation
Nusselt number (Nu), is uniquely related to occurs when ATe = ATea, where ATea is the
the Reynolds number ( R e ) for a given ele- actuation temperature of the heat-responsive
m e n t geometry: element above ambient.
The various assumptions of the response
Nu = f(Re) (3)
t h e o r y were originally examined in some
where detail [ 1], with the following conclusions:
N u = h L / k , Nusselt number (1) forced convection would indeed be
L = characteristic linear dimension of element the dominant mode of heat transfer to the
k = thermal conductivity of gas (assumed to heat-responsive element in most fire situations
have the properties of air) at film temperature relative to b o t h free-convection effects and
((Tg + Te)/2) radiation from the fire;
R e = u L / v , Reynolds number
u = gas velocity *The same velocity dependence of the convective
v = kinematic viscosity of the gas (air) at film heat transfer coefficient has been employed by
temperature. Pickard e t al. [5] and Alpert [6].
115
TABLE 1
U.S. s p r i n k l e r t e m p e r a t u r e r a t i n g s a n d m i n i m u m p l u n g e - t e s t t e m p e r a t u r e s [ 1 ]
(2) the element would most likely heat in from liquid bath test relative to ambient tem-
approximate isothermal manner, as assumed, perature prior to plunge) and ATg is the gas
in the sense that temperature differentials temperature relative to the ambient tempera-
within the element would generally be small ture. For the range of gas velocities covered,
compared to the average temperature rise of 1.5 - 5.2 m/s, it was determined in special
the element from ambient conditions; experiments [1] that the gas temperatures
(3) assuming negligible actuation heat m a y had to exceed certain limits, depending on the
be questionable for heavily solder-loaded, sprinkler temperature rating, in order to
heat-responsive elements, depending on the prevent radiant heat loss from the sprinkler
effective solder fraction which has to be fused to the tunnel walls (uninsulated at the test
before the element actuates; section) from affecting the RTI measurement.
(4) quantitative estimates of conduction The temperature limits are listed in Table 1.
heat loss from an element are so difficult that Above these limits, 10 different sprinkler
the errors associated with ignoring this loss models responded with fairly constant RTI
are n o t readily assessed. over the velocity range examined and up to
An experimental program was conducted the maximum attainable gas temperature,
to examine the constancy of RTI for com- 430 °C. Among the sprinkler models exam-
mercial sprinklers [1]. The sprinklers were of ined, RTI varied in the range 136 - 346
the conventional response, industrial type; m In s w2. In these tests the sprinklers were
fast-response sprinklers had n o t yet entered positioned near their most sensitive orienta-
the market. A plunge test* was adopted for tions in the test stream, the frame being in a
measuring RTI, wherein a sprinkler was sud- plane perpendicular to the flow. Other tests
denly immersed in the steady flow in the indicated that effects of orientation on RTI
(horizontal) test section of a hot,air tunnel. could occasionally be significant in the rela-
The test sprinkler was attached to a fitting in tively smooth test stream, always associated
a plate which was rapidly positioned over the with the heat-responsive element being in the
open t o p of the test section in the plunge wake of a frame arm (frame in a plane aligned
operation. The sprinkler was pressurized with with the flow). However, such effects were
air to a b o u t 35 kPa. For a plunge test, the smaller in the turbulent ceiling flow of a
solution of eqn. (9) can be written in the test fire, presumably because the wake no
following form for RTI: longer stayed fixed on the heat-responsive
--tr ul/2 element.
RTI = (10) The insensitivity of RTI to gas temperature
ln(1 -/XToa/aTg) in these experiments m a y be interpreted* to
where t~ is the response or actuation time; u mean that the heat of fusion of the solder for
is the gas (air) velocity in the test section; the solder-type sprinklers was not impor-
A T e a is A T e a t response (temperature rating tant**. Furthermore, none of the (small)
*With t h e aid of eqn. (17) in ref. 1.
*A r a m p t e s t h a s b e e n used b y o t h e r s [7 ], w h e r e * * E v a n s a n d M a d r z y k o w s k i [ 8 ] have since investi-
t h e test s p r i n k l e r is e x p o s e d t o a linear r a t e o f rise in g a t e d s e p a r a t e l y t h e c o n t r i b u t i o n of t h e h e a t o f
gas t e m p e r a t u r e . fusion to the RTI measurement.
116
variations observed in the RTI could be attri- ture relative to the set point. The plunge-test
buted to conduction heat loss. tunnel is capable of test-section velocities up
to approximately 3.5 m/s. Maximum obtain-
able air temperature is in excess of 400 °C,
FMRC PLUNGE TEST which makes it possible to test sprinklers up
to the "extra high" temperature rating (Table
Based on the first experimental program, a 1). The test sprinkler is m o u n t e d in a detached
special plunge-test tunnel was designed and cover which is inserted into a hinge m o u n t e d
calibrated for further work [ 1, 2]. This tun- on top of the upstream end of the test section.
nel still serves as FMRC's plunge-test appara- To perform a plunge operation, the operator
tus. Figure 1 illustrates the schematic design. removes an idling cover over the test-section
Air heated electrically by heating rods is di- opening and immediately closes the cover
rected into a mixing duct via an orifice. The with the test sprinkler. The plunge operation
orifice serves the dual functions of metering closes a mercury switch which starts a timer.
the flow (in conjunction with pressure taps The timer is stopped by a pneumatic switch
in the plenum and the mixing duct) and inter- when air pressure is released at the actuation
acting with the mixing duct to generate uni- of the sprinkler.
form temperature and velocity profiles suffi- An extensive test program [2] was con-
ciently far downstream of the orifice. The ducted in the FMRC plunge-test tunnel. First,
circular mixing duct is transformed to a duct four sprinkler models, two solder-type and
of rectangular cross section which serves as two bulb-type, and each at three temperature
a test section (300 mm wide X 150 mm high). ratings ("ordinary", "high", and "extra
Turbulence-reducing screens are installed at high"), were tested at combinations of five
the inlet to the test section. The return flow air temperatures in the range 127 - 400 °C and
is taken to the blower inlet via two right-angle three gas velocities of 1.54, 2.56 and 3.48 m/s.
bends. To reduce the heat load, the entire RTI values were quite uniform above the
apparatus, except the test section, is insulated; minimum plunge-test temperatures listed in
the test section is bare to prevent high wall Table 1. However, there was a slight tendency
temperatures from contributing excessive to higher RTI values at the lowest gas velocity
radiant heating to the sprinkler under test. which, in retrospect, may be attributed to
Flow is controlled with a sliding gate at the conduction effects as discussed in the next
blower exit. A temperature control thermo- Section. For subsequent work, nominal test
couple is m o u n t e d between the screens up- temperatures were standardized at the values
stream of the test section; this thermocouple listed in Table 2, combined with a standard
is connected to a temperature controller/ test velocity of 2.56 m/s. Twenty-three
power controller which feeds electric power sprinkler models, both solder and bulb types
to the heating rods to maintain test tempera- and each at three to seven temperature ratings
( " o r d i n a r y " through "extra high"), were
2.3m plunged-tested. Tests were conducted in tri-
Press. Diff. plicates for each model and temperature
,~w Rate
rating, and an average RTI was determined.
, Rectangular
Round Mixin~lDuct Test Section
TABLE 2
Standard, nominal plunge-test temperatures selected
for FMRC plunge-test tunnel
For a given sprinkler model, the average RTI where C Can be considered a conduction (loss)
generally did n o t vary much with the temper- parameter, a characteristic of the sprinkler. In
ature rating, consistent with expectations terms of C, eqn. (13) becomes:
assuming identical geometry and material d(ATe) u 1/2
of the heat-responsive element from one - [ATg - - ( 1 + C/ul/2)ATe] (15)
temperature rating to the next. Averaged over dt RTI
the available temperature ratings for each Hence, instead of a one-parameter response
sprinkler model, the smallest RTI was 125 equation in RTI, we now have a two-parameter
m 1/2 s 1/2 and the largest was 332 m 1/2 S 1/2, response equation in RTI and C. Conveniently,
nearly a threefold variation. The reproducibil- while the units of RTI are (length X time) 1/2,
ity of the RTI measurement in the particular the units of C are (length/time)1z2.
apparatus was estimated to be within +2 - Equation (15) can be transformed into a
+3%, depending on the temperature rating. very useful form whenever the gas velocity,
Variations in replicate tests can be larger u, is constant as in a plunge test, or does not
because of nonuniformities among sprinkler change sufficiently rapidly with time* (appears
samples. to be practically always the case in fire situa-
tions). Then:
(1 + C/u 1/2) d(ATe) _ d[(1 + C/ttl/2)ATe]
INCORPORATION OF CONDUCTIVE HEAT LOSS dt dt
IN R E S P O N S E M O D E L (16)
and eqn. (15) can be written:
On the first reports of definite effects of
conductive heat loss in the response of sprin- d ( A T e v ) / d t = ( u l n / R T I v ) [ A T g -- ATev] (17)
klers [3], efforts were made to incorporate where
such effects in the original response model.
The simplest possible form of conductive ATev = (1 + C/ul/2)ATe (18)
heat loss rate was assumed, proportional to RTI~ = RTI/(1 + C/u i n ) (19)
the temperature difference b e t w e e n the heat-
responsive element and the sprinkler fitting. Note that eqn. (17) is precisely in the form of
Assuming the sprinkler fitting is essentially at the original model response relation, eqn. (9),
ambient temperature, the conductive heat loss where ATe is replaced b y ATe~ and RTI is
rate would be proportional to the tempera- replaced b y RTI~. The quantity ATev can be
ture rise of the element. With a conductive considered as a virtual temperature rise of the
heat loss term, eqn. (1) becomes: heat-responsive element, and RTIv can be con-
sidered as a virtual RTI.
m c ( d T e / d t ) = hA(Tg -- Te) -- C'(Te -- To) (11) The solution of eqn. (17) for a plunge test
(or fire generating constant temperature and
where C' is a constant for a given sprinkler. velocity) is obtained from eqn. (10) b y replac-
The equivalent to eqn. (2) now becomes: ing RTI with RTIv and ATea with ATeva. The
result is:
d(ATe) C'
- v-l(ATg -- ATe) -- - - ATe (12) RTI --trttI/2
dt mc
1 + C/u 1/2 in(1 --ATea(1 + C / u i n ) / A T g )
or, rearranging and using eqn. (8): (20)
Now, if C' and RTI are constants for a sprin- *Turbulent fluctuations axe not considered here.
kler, so is C'RTI/(rnc). Consequently, define: Turbulent fluctuations in u and A T g will cause small
A T e ripples in the element response and these are
C = C'RTI/(mc) (14) ignored.
118
IuJ
o~ 8o P R E L I M I N A R Y T E S T OF M O D I F I E D M O D E L
will be focused on measurements involving which can be solved for C. In order to deter-
t w o solder-type, pendent sprinklers: a conven- mine Uc, a series of standard test velocities
tional response model, sprinkler A; and a fast- were selected for the plunge-test tunnel, the
response model, sprinkler B. Both of these square r o o t of the ratio of sequential test
sprinklers were rated at 74 °C, although their velocities being fixed at 1.10. For each test
liquid-bath operating temperatures (slightly velocity, a sprinkler was exposed for 10 min-
lower) were used in the calculations. utes (deemed sufficient to establish steady-
The selected sprinklers are of "ordinary" state element temperature) until actuation
temperature rating, and the nominal air tem- was bracketed between t w o successive test
perature listed in Table 2 for this temperature velocities. The conduction parameter was
rating, 191 ~C, was used in the FMRC plunge- taken as the average of the values C calculated
test tunnel, together with the standard air for the bracketing velocities, using eqn. (25).
velocity of 2.56 m/s, to determine the RTI Hence, the conduction parameter in this pro-
values of the sprinklers. RTI values were cedure can be assumed to have been estab-
determined b y two methods: (a) first ignor- lished to an accuracy of 10%. In order n o t to
ing the existence of a conduction heat loss require unreasonably low air velocities, the
using eqn. (10), termed "apparent R T I " , fairly low test temperature of 127 °C was
(2) then incorporating the conduction param- chosen, which is still above the (radiation)
eter, C, and calculating RTI according to limit in Table 1 for "ordinary" temperature
eqn. (20). However, first, the conduction rating.
parameter had to be determined. The results of the plunge tests and the
The conduction parameter, C, was mea- prolonged-exposure tests are summarized in
sured in a specially devised test in the plunge- Table 3. It is seen that the RTI of sprinkler B
test tunnel, where the sprinkler m o u n t (fitting) is only 1/8 of that for sprinkler A, while the
was held at constant temperature over a pro- conduction parameter of sprinkler B is a b o u t
longed period b y circulating cold (tap) water 1/3 of that for sprinkler A.
through the mount. The m o u n t temperature, The r o o m fire tests employed a test r o o m
measured with a thermocouple, was carefully within a larger test building, Fig. 3. The r o o m
monitored. According to the response model, measured 3.66 m × 7.32 m × 2.44 m high and
the steady~tate temperature rise (referenced was made from w o o d studs and ½-in. gypsum
to the m o u n t temperature) of the heat- board. There was only one opening to the
responsive element in a prolonged response is room, an open door at one end. A fire source
given b y the factor in front of the square was placed near the opposite end, and ceiling
brackets in eqn. (21), i.e., b y hTg/(1 + C/ul/2). sprinklers together with associated instru-
As the gas velocity is increased to a higher ments were located at distances from the fire
value from one prolonged exposure to the source of 1.63 and 4.55 m. Each ceiling
next, the steady-state temperature rise of the station incorporated a sprinkler A and a
element increases. For a sufficiently high air sprinkler B, screwed into ~-m.1 • (steel) pipe
velocity, Uc, the element will just actuate in a couplings extending d o w n 0.038 m from the
prolonged exposure. At that point: ceiling, attached to pipe nipples above the
roof. Each nipple was fitted to the center of
ATg/(1 + C/Uc 1,2) -~ ATea (25) a 1.6-m-long, 1-in.<lia. horizontal steel pipe
TABLE 3
Response parameters for tested sprinklers
-'- 3.66
t
Y~
FIRE SOURCE
! ! •
NEAR STATION
SPRINKLER /
\ \THE 0uP
~- 0.076
FAR STATION
I I
OPEN DOOR
(1.18 x 2.06 HIGH)
Fig. 3. Fire r o o m w i t h t w o sprinkler a n d i n s t r u m e n t s t a t i o n s at t h e ceiling. The fire source, e i t h e r a h e p t a n e p o o l
o r w o o d crib, r e s t e d o n a weighing p l a t f o r m o n t h e floor. All d i m e n s i o n s are in meters.
above the r o o f with 0.13-m-high risers open sensing level of 0.076 m beneath the ceiling,
t o the atmosphere at b o t h ends. After a sprin- very nearly the level of the center of the
kler had been installed for testing, the pipe to heat-responsive element of each sprinkler.
which it was m o u n t e d was filled with water. The fire source used was either a 0.46-m-
A thermocouple monitored the water temper- dia. pool of heptane floated on water, or a
ature within the water-way of each sprinkler. wood crib {pine) measuring 0.51 m X 0.51 m
To record actuation times, metal electrodes X 0.38 m high made from 19-mm square
were positioned in the path of the weak spray sticks (8 sticks per layer, 20 sticks high).
produced when the sprinklers actuated, the Remote ignition with an electric match was
spray completing an electric circuit which was employed, in the case of the wood crib, via a
monitored. Along with the two sprinklers at a 0.10-m-dia. pan of heptane underneath the
ceiling station, there were two thermocouples central shaft of the crib. Both fire sources
to measure gas temperature and one bidirec- were continuously weighed on load platforms
tional flow probe (connected to an electronic to monitor the mass-loss rate. The ceiling
manometer) to measure gas velocity, all at a clearances above the fire sources were 2.24 m
121
20O
for the heptane pool and 1.90 m for the w o o d r
crib.
One heptane pool fire, test 8, and one w o o d ~ lO0
sented by: ~2
Q (kW) = 1 0 0 0 [ ( t -- to)/tg] 2 (26)
where* the "growth time", tg, was 256 s and
the effective ignition time, to, was 29 s. The > 0 o
closely matched the data for test 17 when the 0 "150 SECONDS 300
(C) SPRINKLER RESPONSE TEST S
time axis for test 19 was shifted 22 s to smaller
times. Hence, it may be assumed that test 19 Fig. 4. Heptane pool fire (test 8): gas temperatures
and velocities at ceiling instrument stations. (a)Tem-
also behaved according to eqn. {26), with perature at near station (top) and far station (bot-
tg = 256 s and to = 2 9 - - 22 = 7 s. tom); (b) velocity at near station; (c) velocity at far
Figure 4 presents gas temperatures and station.
velocities measured at the instrument stations
(sprinkler sites) for the heptane pool fire. In Response times were calculated from eqn.
Fig. 4(a), it can be seen that the two thermo- (24), with eqns. (18) and (19), using RTI and
couples at each station indicated very similar C values from Table 3, the data in Figs. 4 and
temperatures. The spikes on the curves were 5, as well as the ATf data. Each temperature
due to electronic noise. The velocity data in curve (Figs. 4(a) and 5(a)), " c o r r e c t e d " for
Figs. 4(b) and 4(c) also exhibit a few elec- ( C / u l / 2 ) A T ~ (see eqn. (23)), was approxi-
tronic noise spikes. Data for the w o o d crib mated b y a sequence of linear segments*
fire are presented in Fig. 5. This time, the t w o over which u 1/2 was considered constant at
thermocouples at the near station {Fig. 5(a)) the average value for the interval. An analy-
indicated slightly different temperatures, and tical solution exists for eqn. (24) over such
no electronic noise can be discerned in the a linear segment, according to which the res-
velocity data (Figs. 5(b) and 5(c)). In addi- ponse of the heat responsive element can be
tion to the measurements in Figs. 4 and 5, followed from one segment into the next
data on the fitting temperatures (measured until response occurs (ATe = ATea).
as temperatures in sprinkler water-ways) were Calculated response times are compared to
available; ATf until sprinklers operated ranged experimental response times in Fig. 6. All the
from 0 °C to 22 °C for the heptane pool fire
and from 3 °C to 17 °C for the crib fire. *For the heptane pool fire, the following time end
points were selected for the linear segments: 0, 69,
144, 240 s (near station) and 0, 7.5, 71, 144, 240,
300 s (far station). The time end points selected for
*It is implied in eqn. (26) that the growth time, tg, the wood crib fire were: 0, 24, 54, 98, 116, 150 s
is the time required for a fire, growing in heat release (near station) and 0, 35, 61.5, 88, 140, 190 s (far
rate with the square of time, to exceed 1000 kW. station).
122
500 300
, , //
400
/
bJ
=J /
300
i-
200
/
¢n
200 z
o
(n ,/
100
r, /
0
= i , , , , , , , : 100. . . . . . SECONDSa = 2"00 p ::D
1 O0 2
(a) SPRINKLER RESPONSE TEST t 9 q
3
/
0 I i
1O0 200 300
EXPERIMENTAL RESPONSE TIME ( e )
-!
data fall near the dashed line representing
. . . . . . :io~ .... SE~ONbS' 200'
SPRINKLER RESPONSE TEST 19
perfect correlation. At the upper right corner
(b) is shown a triangle (far station in heptane
3 pool fire) with an arrow; in this case, the
sprinkler did not operate in the test interval
and neither did the calculation indicate that
it would.
i'
~o
Suppose one ignores the conduction effect
(C = 0) and calculates response according to
the apparent RTI listed in Table 3. Figure 7
• , , , , . . . . . . • , , , , ,
-I
'lO0 SECONDS 200 gives the results in the same form as Fig. 6.
(c) SPRINKLER RESPONSE TEST 19
The crib fire data {solid symbols) exhibit
Fig. 5. Wood crib fire (test 19): gas temperatures and only slightly worse correlation, calculated
velocities at ceiling instrument stations. (a) Tempera- versus experimental, than in Fig. 6, whereas
ture at near station (top) and far station (bottom};
(b) velocity at near station; (c) velocity at far station.
the pool fire data exhibit considerably less
favorable correlation. For example, whereas
sprinkler A at the far station did not operate
, , // in the pool fire, it did operate in the calcula-
tion (at 255 s).
i.i
Many pairs of data, laboratory (RTI, C)
=
I--
A and fire tests, remain to be analyzed. It might
,., 200 / be of interest to point out that the C value
pertaining to sprinkler A, 1.56 ml/2/s 1/2
(Table 3), is the largest value observed to date
among eleven sprinkler models examined, the
° 100 / lowest being about 0.5 m1/2/sl/2.
q
fires [10]. The typical home fire m a y be in tg, to a new value in Fig. 8 is to change the
the tg range 150 - 300 s. RTI corresponding to a given QR b y the ratio
Response calculations have been paramet- of new value tg to original value tg. Hence, the
rized in the variable RTI and C for a given curves for a larger tg (slower fire growth)will
fire scenario: tg= 146 s; ceiling clearance be flatter, and effects of C at a given RTI will
above the fire source of 2.44 m; distance be larger than before. Conversely, the curves
under the ceiling from the fire axis of 2.15 m; for a smaller tg (faster fire growth) will be
an ambient temperature of 24 °C and a sprin- steeper, and effects of C at a given RTI will
kler temperature rating of 74 °C. Using simpli- be smaller than before. Overall then, effects
fied formulas [11] which assume large flat of C b e c o m e increasingly more important as
ceilings and quasi-steady fires (flow under RTI decreases and fire growth becomes slower.
ceiling adjusts to instantaneous heat release Each combination o f RTI and C in Fig. 8
rate), the temperature and velocity can be gives rise to an apparent RTI, i.e., the RTI
calculated at the sprinkler site. Response is measured in a standard plunge test (Table 3)
then predicted in the manner of the preceding assuming C = 0. In Fig. 9 the heat release
Section, using predicted temperature and rates at response in Fig. 8 have been plotted
velocity instead of experimental values. How- as a function of the apparent RTI. The effect
ever, instead of response time, the more of C is quite large at low apparent RTI, b u t is
meaningful measure for a growing fire of heat less significant at the higher values of apparent
release rate at response, QR, is adopted as a RTI. For instance, for apparent RTI in the
criterion of sprinkler responsiveness. range 125 - 332 m 1/2 s 1/2, the ffect of increas-
Figure 8 presents the heat release rate at ing C from 0 to 2 ml/2/sl/2 varies from a 30%
response as a function of RTI for three con- increase in QR at the lower RTI to practically
duction parameters: C = 0, 1, and 2 ml/2/s 1/2. no effect on QR at the higher RTI. The appar-
Although there is a clear effect throughout of ent RTI range, 125 - 332 m 1/2 s 1/2, pertains
the conduction parameter, the relative effect to the 23 "conventional response" sprinkler
is strong only at low values of RTI. For in- models investigated in the FMRC test pro-
stance, at RTI = 25 ml/2/s ~/2, the heat release gram [2] discussed previously.
at response more than doubles as C ranges The finding that the conduction parameter
from 0 to 2 ml/2/s 1/2. is important primarily for low-RTI sprinklers
It can be shown from the basic equations pertains to growing fires, hence would apply
that the effect of changing the growth time, to the operation of the first sprinkler in most
fire scenarios. After the first sprinkler oper-
2000 L I I I I ates, the heat o u t p u t of the fire m a y begin to
decrease or at least not increase. In a leveled-
I
.C=2 mL/2/! x/2
I S00 // • c-]. ml/Z/Bl/2
t " .."
// ..... c=o 2000 J ~ a
/, ,..."
/. .,-
1200 / -"
~: //...""
,.~ / ,..' 1600
/ .."
./ ..'
O 800 // ......
A 1200 f
~ 7,+.'"
400
0 800 /
1" ...'
•
.."
I I I I
0 100 200 300 400 500
400
RTI (mi/25 I/2)
Fig. 8. P r e d i c t e d h e a t release rates at sprinkler res-
p o n s e as f u n c t i o n o f R T I f o r various c o n d u c t i o n I r ] I
off heat-release-rate situation, additional using RTI from standard plunge tests in the
sprinklers may or may not operate, and here FMRC plunge-test tunnel, and conduction
the conduction parameter will be important parameters, C, from "prolonged exposure"
for both low- and conventional-RTI sprinklers. tests at different velocities in the plunge-test
tunnel.
CONCLUSIONS
LIST OF SYMBOLS
(1) Of the several assumptions entering the
original sprinkler response theory leading to A surface area of heat-responsive ele-
the concept of constant RTI, two assump- ment
tions could not be justified a priori: (a) negli- B nondimensional constant
gible actuation heat for the heat-responsive C conduction parameter; see eqn. (14)
element (as associated with solder, for in- C' conduction coefficient
stance), and (b) insignificant conductive heat C specific heat of heat-responsive ele-
loss from element. ment
(2) The first experimental program con- h convective heat transfer coefficient
ducted at FMRC to study the constancy of k thermal conductivity of heat-respon-
RTI for industrial type sprinklers, incorporat- sive element
ing gas velocities of 1.5 m/s and higher, sug- L characteristic linear dimension of
gested that the actuation heat was not impor- heat-responsive element
tant. Furthermore, variations observed in RTI m mass of heat-responsive element
could not be attributed to conductive heat Nu hL/k, Nusselt number
loss. Q heat release rate
(3) RTI values measured subsequently in QR Q at sprinkler response
the FMRC plunge-test tunnel for velocities in Re uL/v, Reynolds number
the range 1.5 - 3.5 m/s and several air temper- RTI ru ' n , response time index of heat-
atures, selected above a limit to preclude responsive element
significant radiation effects, were found to be RTIv virtual KTI
quite uniform, although with some tendency Te temperature of heat responsive ele-
to increase at the lowest velocity investigated. ment
(4) Triggered by recent reports on signifi- T~ temperature of sprinkler fitting or
cant effects of conductive heat loss in certain mount
fire situations, modifications have been pro- gas or air temperature
posed for the original response theory to To initial or ambient temperature
accommodate such effects. The conductive ATe Te -- To
heat loss rate has been assumed proportional ATea ATe at actuation of sprinkler
to the difference in temperature between the ATev virtual temperature rise of heat-
heat-responsive element and the sprinkler responsive element
fitting. In the modified model, the response ATeva ATev at actuation of sprinkler
of a sprinkler for a given fire environment and ATf Tf -- To
temperature rating depends on two param- Tg -- To
eters, the RTI and a conduction parameter, C. t time
(5) According to the modified sprinkler tg growth time of fire to I000 k W for
response model, conductive heat loss effects fire growing with square of time
are primarily important at low gas tempera- to effective ignition time
tures and velocities. For rising temperatures tr response or actuation time of sprin-
and velocities, as in growing fires, conduction kler
effects become increasingly more important U gas or air velocity
as RTI decreases and fire growth becomes Uc limiting air velocity for sprinkler
slower. response
(6) Response times of sprinklers in specially V kinematic viscosity
designed room fires were found to be consis- T time constant of heat responsive
tent with calculations according to the model, element
125