You are on page 1of 3

NEXA Series,

Rotork Actuator Control for pump installed on


Package 300-BD-8040B: Actuator S/N: 6A2058620104,
Pump S/N: 221292
BEFORE REMOVING THE OPERATING
ACTUATOR FROM THE PUMP

Bring the electric adjustment @100%


and check that the mechanism is also at
the same percentage

REMOVE THE ACTUATOR FROM THE


PUMP

Connect it electrically and test the


actuator in solo condition.

A. You should be already at 100%

B. Type a mark with the marker on


the actuator shaft, and another
on the actuator flange; check the
working condition.

C. Bring the actuator at ZERO%


counting the number of complete
turns for the proper size of
mechanism: N0 = 10 Turns

D. Bring back the actuator at 100%


counting if the actuator will
THIS ILLUSTRATION IS ONLY DEMONSTRATIVE
perform the 10 Turns

WARNING:

If the actuator is not performing the


above indicated turns, kindly advise SEKO
immediately
Before installing the actuator on the
pump, be sure that also the mechanism is
at the same percentage as the actuator.

If not, in order to reach the 100% of the


pump stroke adjustment, we suggest you
to rotate (using a screwdriver and
connect in place of the actuator spindle)
in clockwise direction till the stroke
stops; then do 1 turn in the opposite
direction.

NOW THE PUMP MECHANISM WILL BE


AT 100%:
You can reinstall the actuator on the
pump mechanism, tightening the screws

END