You are on page 1of 1

NORTH

R1
NEW CORRUGATED METAL CLADDING
METAL CLADDING
SPANDEK COLORBOND 0.5mm Thk.
EXTERIOR PAINT AIR
FIN. TERMINAL
H = 1.500mm
EXISTING LOUVER RADIUS = 20 m
EXISTING WALL WITH
NEW PAINT FINISH

NEW CORRUGATED METAL


FASCIA SPANDEK COLORBOND
0.5mm Thk.
NEW CORRUGATED METAL FASCIA
SPANDEK COLORBOND 0.5mm Thk.

ROOF PLAN
EL. +8.590 R1
R1 EL.+8.300 R1

615
EL. +8.360

2250
HANDRAIL HOT DIP GALV Ø 2" NEW DOWNPIPE
+ PAINT FINISH WITH KICK
EL. +6.110 PLATE
NEW CORRUGATED METAL
EL. +5.725 F6 F6 CLADDING SPANDEK

900
COLORBOND 0.5mm Thk.

- ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE

8300
- ALL LEVELS ARE IN METERS UNLESS NOTED OTHERWISE

5825
LOADING

5400
DOCK

BUNDWALL W=200mm,
GROUND FLOOR PLAN
Clamp
EL. +0.500 H=500mm

EL.+0.000
CHILLER BATTERY TRUCK LOADING
LEGEND :
EL. -0.100 02-00-01
EL. -0.100
F7 AREA CHARGING AREA
EL. -0.300
= AIR TERMINAL COPPER ROD Ø16mm,
4451 600 1500mm HEIGHT
CONTROL BOCK AND EARTH ELECTRODE
400 X 400 X 400 = EARTH PIT
5 6 4143 4260 4280 4260 4400 4260 4280 4260
34143
= EARTHING BONDING BAR (COPPER BAR)
40X3MM THK, LENGTH AS REQUIRED C/W
ISOLATOR
1 2 3 4 5 6 7 8 9
= BARE COPPER LIGHTNING DOWN
CONDUCTOR 50m
= MAIN GROUNDING RING BC 70mm2/ SHALL BE
BURIED 600mm BELOW GRADE AND
APROXIMATELY 1,000mm FROM BUILDING
PERIMETER.

NOTES :

1. DISTANCE BETWEEN EARTH PIT ±20m LENGTH


2. RESISTANCE IS 3 Ω MEASURE AT 3 DAYS RAIN OFF.
3. FOR GROUNDING POINT BUILDING SEE DWG ON
EVERY BUILDINGS.
4. USE CABLE BC TO EQUIPMENT AS FOLLOW
- TO PIPING 10mm²
- TO DUCTING 10mm²
- TO CABLE TRAY 16mm²
- TO STEEL STRUCTURE 16mm²
- TO TANK
- TO PANEL (VARIOUS) FOLLOW TO NYA CABLE
DIMENSION OF LEADER INSTALLATION AT EVERY
PANELS

RADIUS = 20 m RADIUS = 20 m
R1
AIR TERMINAL
H = 1.500mm

= REVISION CLOUD
R1
R1

ROOF PLAN
EL.+8.300

AIR TERMINAL
H = 1.500mm

3800
NEW CORRUGATED METAL
CLADDING SPANDEK
COLORBOND 0.5mm Thk. FIRST FLOOR PLAN 0 ISSUED FOR CONSTRUCTION BU IK IK 10.02.2023
EL.+4.500 NO. DESCRIPTION BY CHKD APVD DATE
THIS DRAWING IS A PRIVATE AND CONFIDENTIAL

8300
COMMUNICATION AND THE PROPERTY OF CLIENT.IT MUST
NOT BE COPIED OR LENT WITHOUT THE COMMENT OF
CLIENT AND MUST BE RETURNED WITH TENDER AND/OR

6000
ON COMPLETION OF ORDER.

4500
APPROVED BY CLIENT
FFL +0.450 GROUND FLOOR PLAN
FFL -0.100 EL.+0.000
FFL -0.300

6000 6000 6000 6000 6000 6000 6000 6000 6000 6000 8875
Menara 165, 12th Floor
60000
Jl. TB Simatupang Kav. 1 Cilandak Timur
GROUP Jakarta Selatan 12560 Indonesia
Shaping Tomorrow tel +62 21 2940 6840 - fax +62 2940 6841
A B C D E F G H I J K
BATI - DETAIL DESIGN

DRAWING TITLE :

35 ELECTRICAL & ELECTRONICAL


LIGHTNING PROTECTION INSTALLATION LAYOUT -
SECTION
SCALE : As indicated FORMAT SIZE : A3
PROJECT DRAWING NO. REV
P-21-018 BAT-DWG-DD-ME-01-AL-1601.02 0