You are on page 1of 1

NORTH

PP-WWTP SYSTEM
380/220V, 50Hz, 3Ph, 4W+E, Isc=16kA-1 Sec, IP 31, FORM 2A LOAD IN WATT
GROUP TOTAL
DESCRIPTION REMARKS
T NO WATT
R S T
S DM

R MCB 16A/3∅ /3P NYY 4C x 4mm² + NYA 4mm² 01 EQUALIZATOR PUMP A 750 250 250 250
DOL

3x2A MCB 16A/3∅ /3P NYY 4C x 4mm² + NYA 4mm² 02 EQUALIZATOR PUMP B 750 250 250 250
DOL
MCB 16A/3∅ /3P NYY 4C x 4mm² + NYA 4mm² 03 NEUTRALIZATION PUMP A 750 250 250 250
DM DOL
MCB 16A/3∅ /3P NYY 4C x 4mm² + NYA 4mm² 04 NEUTRALIZATION PUMP A 750 250 250 250
DOL
MCCB MCB 20A/3∅ /3P NYY 4C x 4mm² + NYA 4mm² 05 BLOWER AERATION SYSTEM 2,000 666,6 666,7 666,7
DOL
63A/3∅ /3P
MCB 16A/3∅ /3P NYY 4C x 4mm² + NYA 4mm² 06 SLUDGE COLLECTOR 1000 333,4 333,3 333,3
DOL
MCB 16A/3∅ /3P SPARE

MCB 16A/3∅ /3P SPARE


- ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE
MCB 20A/3∅ /3P SPARE - ALL LEVELS ARE IN METERS UNLESS NOTED OTHERWISE
NYY 4C x 16mm² + NYA 16mm²
FROM DB BUILDINGN 32

NOTE : 6,000 2000 2000 2000

ARRESTER DETAIL PP.WWTP SCOPE BY WWTP


SYSTEM WATT VA AMPHERE

TOTAL INSTALLED LOAD 6,000 7,500 10.20


DIVERSITY FACTOR 0.8
TOTAL OPERATION LOAD 4,800 6,000 8.16
TOTAL

PP-WTP SYSTEM
380/220V, 50Hz, 3Ph, 4W+E, Isc=16kA-1 Sec, IP 31, FORM 2A LOAD IN WATT
GROUP TOTAL
DESCRIPTION REMARKS
T NO WATT
R S T
S DM

R MCB 20A/3∅ /3P NYY 4C x 4mm² + NYA 4mm² 01 PROCESS WATER PUMP A 3,000 1000 1000 1000
DOL

3x2A MCB 20A/3∅ /3P NYY 4C x 4mm² + NYA 4mm² 02 PROCESS WATER PUMP B 3,000 1000 1000 1000
DOL
MCB 16A/1∅ /1P NYY 3C x 4mm² 03 DOSING PUMP A 500 500
DM DOL
MCB 16A/1∅ /1P NYY 3C x 4mm² 04 DOSING PUMP B 500 500
DOL
= REVISION CLOUD
MCCB MCB 20A/3∅ /3P NYY 4C x 4mm² + NYA 4mm² 05 RO 1 2,500 833.3 833.3 833.4
DOL
63A/3∅ /3P
MCB 20A/3∅ /4P NYY 4C x 4mm² + NYA 4mm² 06 RO 2 2,500 833.3 833.4 833.3
DOL
MCB SPARE

MCB SPARE

MCB SPARE
NYY 4C x 16mm² + NYA 16mm²
FROM DB BUILDINGN 32

0 ISSUED FOR CONSTRUCTION BU IK IK 24.02.2023


NO. DESCRIPTION BY CHKD APVD DATE
THIS DRAWING IS A PRIVATE AND CONFIDENTIAL
COMMUNICATION AND THE PROPERTY OF CLIENT.IT MUST
NOT BE COPIED OR LENT WITHOUT THE COMMENT OF
12,000 4,166.6 4,166.7 3,666.7 CLIENT AND MUST BE RETURNED WITH TENDER AND/OR
ON COMPLETION OF ORDER.

NOTE : APPROVED BY CLIENT


ARRESTER
DETAIL PP.WTP SCOPE BY WTP WATT VA AMPHERE
SYSTEM
TOTAL INSTALLED LOAD 12,000 15,000 20,40
DIVERSITY FACTOR 0.8
TOTAL OPERATION LOAD 9,600 12,000 16,32
TOTAL Menara 165, 12th Floor
Jl. TB Simatupang Kav. 1 Cilandak Timur
GROUP Jakarta Selatan 12560 Indonesia
Shaping Tomorrow tel +62 21 2940 6840 - fax +62 2940 6841

NOTE :
BATI - DETAIL DESIGN
-PANEL MAKER SHOP DRAWINGS AS REQUIRE FOR
DETAILS CONSTRUCTION OF CUBICLE DRAWING TITLE :
-DETAIL OF LOAD WTP & WWTP SHOEL BE FOLLOWED TO 35 ELECTRICAL & ELECTRONICAL
LOAD FROM WTP & WWTP VENDOR LOAD SCHEDULE DIAGRAM OF PP WWTP SYSTEM &
PP.WTP SYSTEM
SCALE : 1 : 100 FORMAT SIZE : A3
PROJECT DRAWING NO. REV
P-21-018 BAT-DWG-DD-ME-00-EP-6005 0