You are on page 1of 1

One-Line Diagram - OLV1 (Load Flow Analysis)

POWER GRID
1250 MVAsc

4510
Bus1 j5732 100 %
13.8 kV
3498 8008
-j224.2 j5508

T1 T3
20 MVA 20 MVA

3500 7991
%
Bus2 -j187.4 100 % Bus3 j5225 99.43
4.16 kV 4.11 kV
4000 7500 4019 3972
j3000 j2813 j2246 j2979

Open

Cable1 Cable2
Lump2
Lump1 7.5 MW 5 MVA
5 MVA Gen1

T2 T4
3 MVA 3 MVA

3854
Bus4 93.4
Bus5
7% j1798 96.79
%
Open
0.466 kV 0.45 kV
320.4 280.5 1326 1927 1326 320.4 280.5
j136.6 j120 j642.3 j898.9 j642.3 j136.6 j120

Syn1 Mtr1 Lump3 Lump4 Syn2


400 HP 350 HP Mtr2
1.5 MVA 1.5 MVA 350 HP
400 HP

page 1 11:58:38 Apr 13, 2023 Project File: TEST NETWORK