You are on page 1of 1

One-Line Diagram - OLV1 (Load Flow Analysis)

POWER GRID
1250 MVAsc

11928
Bus1 j8299 100 %
13.8 kV
5964 5964
j4150 j4150

T1 T3
20 MVA 20 MVA

5955 5955
%
Bus2 j3991 98.67
% Bus3 j3991 99.87
4.16 kV 4.11 kV
3979 1976 1976 3979
j2984 j1007 j1007 j2984

Open

Cable1 Cable2
Lump2
Lump1 7.5 MW 5 MVA
5 MVA Gen1

T2 T4
3 MVA 3 MVA

1938 1938
%
Bus4 j904.2 98 %
Bus5 j904.2 101.5
0.466 kV 0.45 kV
320.4 280.5 1337 1337 320.4 280.5
j136.6 j120 j647.6 j647.6 j136.6 j120

Open

Syn1 Mtr1 Lump3 Lump4 Syn2


400 HP 350 HP Mtr2
1.5 MVA 1.5 MVA 350 HP
400 HP

page 1 11:57:04 Apr 13, 2023 Project File: TEST NETWORK