“Substation automation system

guideline with IEC 61850 for oil refinery


industry in Mexico”
Presentador: Luis Ivan Ruiz Flores
Senior Member

Septiembre 5, 2013
Introduction

• Energy systems in refinery


industry in Mexico are
increasing their energy
demand.
• It is necessary to modernize
and upgrades the main
electrical equipment and
automation system.
• The electrical system is being upgrading on their main buses
electrical network and the automation equipment IED (Intelligent
Electronic Devices) or relay and acquisition equipment is
upgrading based on IEC-61850 technology.
Electrical System

High Voltage Medium Voltage

Transformers

Power System Control Costumer

Protection & Substations


Systems Control
Electrical System Conceptual (Typical Refinerie)

GRID 1 GRID 2 GRID 3


TG-1 TG-2 TG-271
32 MW 32 MW 115 kV 18 MW 230 kV 230 kV

16 ohms

T- 1 T- 2 T- 3
16 ohms 115/13.8 kV 230/13.8 kV 230/13.8 kV
15/20 MVA 75/84 MVA 75/84 MVA
Z=17% Z=17% Z=17%
16 ohms 16 ohms 16 ohms
In 2500 A

In 2500 A

In 2500 A

In 2500 A

In 3150 A

In 3150 A

In 3150 A
s s s s s s s
TD-1 TD-2 TD-3 TD-A TD-B
In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A
Isc3Ø=31.5 kA Isc3Ø=31.5 kA Isc3Ø=31.5 kA Isc3Ø=31.5 kA Isc3Ø=31.5 kA
2500 A 2500 A 2500 A 3150 A 3150 A
13.8 kV 13.8 kV 13.8 kV 13.8 kV 13.8 kV
measured

measured

measured
Slot

Slot

Slot
18 18 4 25 25
MW MW MW MW MW
LOAD LOAD LOAD LOAD LOAD

In 1200 A

In 1200 A
0.3 ohms

0.3 ohms

0.3 ohms

IS- B
IS- A
RA 1

RA 2

RA 3
measured

In 1250 A

In 1250 A

In 1250 A
In 1250 A

In 1250 A

In 1250 A
Slot

Isc3Ø=31.5 kA
2500 A
TD-BS
s s s s s s 13.8 kV
Concepts

Typical requirement (70’s)


Installed Capacity 25 MW
with 12.5 MW (Load
demand)
3 x 5 MW + 1 x 10 MW @
4.16 kV

Aztcapotzalco Refinerie (México)


One Concept: Generator

Modern Refineries (77’s-


G1 G2
79’s)
• Salina Cruz
• Tula
• Cadereyta

Installed Capacity
• 50 MW @ 13.8 kV
• 25 MW de carga

2 X 25 MW @ 13.8 kV, bi-bar,


switchgear of 500 MVA
One Concept: Utility
CFE CFE
115 KV 230 KV

115 KV

22.4 22.4 26 44
MVA MVA MVA MVA

13.8 KV

TG1 TG2 TG3 TG4


25 MW 25 MW 32 MW 32 MW

13.8 KV

M M M M M

HDR
System Architecture of Refinery
GRID 1 GRID 2 GRID 3
TG-1 TG-2 TG-271
32 MW 32 MW 115 kV 18 MW 230 kV 230 kV

16 ohms

T- 1 T- 2 T- 3
16 ohms 115/13.8 kV 230/13.8 kV 230/13.8 kV
15/20 MVA
Z=17%
16 ohms
75/84 MVA
Z=17%
16 ohms
75/84 MVA
Z=17%
Currently
16 ohms

Electrical system on 13.8 kV


synchronization bus
In 2500 A

In 2500 A

In 2500 A

In 2500 A

In 3150 A

In 3150 A

In 3150 A
s s s s s s s
TD-1 TD-2 TD-3 TD-A TD-B
In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A

In 1250 A
Isc3Ø=31.5 kA Isc3Ø=31.5 kA Isc3Ø=31.5 kA Isc3Ø=31.5 kA Isc3Ø=31.5 kA
2500 A 2500 A 2500 A 3150 A 3150 A
13.8 kV 13.8 kV 13.8 kV 13.8 kV 13.8 kV
measured

measured

measured
Slot

Slot

Slot
18 18 4 25 25
MW MW MW MW MW
LOAD LOAD LOAD LOAD LOAD

In 1200 A

In 1200 A
0.3 ohms

0.3 ohms

0.3 ohms

IS- A

IS- B
RA 1

RA 2

RA 3
measured

In 1250 A

In 1250 A

In 1250 A
In 1250 A

In 1250 A

In 1250 A
Slot

Isc3Ø=31.5 kA
2500 A
TD-BS
s s s s s s 13.8 kV

GRID 1 GRID 2 GRID 3


TG-1 TG-2 TG-271
32 MW 32 MW 115 kV 18 MW 230 kV 230 kV

16 ohms 16 ohms T- 1 16 ohms T- 2 T- 3


115/13.8 kV 230/13.8 kV 230/13.8 kV
15/20 MVA 75/84 MVA 75/84 MVA
TT-1 TT-2 Z=17% Z=17% Z=17%
16 ohms 16 ohms 16 ohms

TG-1 Isc3Ø=40 kA TG-2 Isc3Ø=40 kA


In 2500 A In 2500 A In 2500 A In 2500 A 3150 A
3150 A
13.8 kV 13.8 kV

TP'S TP'S TP'S TP'S TP'S TP'S TP'S TP'S

TD-1 TP'S s In 2500 A In 2500 A s TD-2 s In 2500 A In 2500 A s TP'S TD-3 s In 2000 A TP'S s In 2000 A TD-A s In 3150 A TD-B s In 3150 A

Proposal In 2500 A In 2500 A s


TP'S
Isc3Ø=40 kA
3150 A
13.8 kV
In 2500 A In 2500 A s
TP'S
Isc3Ø=40 kA
3150 A
13.8 kV
In 2500 A In 2500 A s
TP'S
Isc3Ø=31.5 kA
2500 A
13.8 kV
In 2500 A In 2500 A In 2500 A Isc3Ø=31.5 kA
3150 A
13.8 kV
In 2500 A In 2500 A Isc3Ø=31.5 kA
3150 A
13.8 kV

Electrical power system on


20.5 20.5 4 32 32
MW MW MW MW MW
LOAD LOAD LOAD LOAD LOAD
ES ES ES ES ES
IT-T-7 IT-T-8 IT-T-4

34.5 kV synchronization bus 16 ohms


T- 7
13.8/34.5 kV
25/35 MVA
Z=9.5%
16 ohms
T- 8
13.8/34.5 kV
25/35 MVA
Z=9.5%
16 ohms
T- 4
13.8/34.5 kV
15/35 MVA
Z=9.5%
16 ohms
T- 5
13.8/34.5 kV
45/55 MVA
Z=13%
16 ohms
T- 6
13.8/34.5 kV
45/55 MVA
Z=13%

TP'S TP'S
FUT-TG-3 FUT-TG-4
In 1250 A In 1250 A In 1250 A In 1250 A In 1250 A s In 1250 A s In 1250 A
TD-BS

Isc3Ø=31.5 kA
2500 A
T-SP1 T-SP2 34.5 kV
In 1250 A 34.5/0.480 kV 13.8/0.48 kV
TR-N
1 MVA 1 MVA

TR-N
TD-BA TD-BB
Challenges

• One of the challenge is improvement


parameters of service quality,
competitiveness and energy efficiency.

• The use of IEDs devices under IEC 61850 standard should allow
more critical application, requiring time responding in
deterministic real time less than 50 ms.
• Before a power failure event must be isolated before their effect
cause serious deterioration to the electrical system and
consequently the production process of oil refinery.
• We need algorithms to decide the flow energy on the electrical
system in contingency.
IEC-61850 / Station bus / Bay Bus / Process Bus

• In refineries, is feasible to implement the station bus, bay bus (IED’s) and
Process Bus with merging units actually (Conventional Primary Equipment
with interface IEC 61850).

• A restriction to implement this project is: The integrator must have many
experience on power system and automation with IEC 61850 and
Generation system and legacy system.

• The station bus refers to monitoring and taking decision with information
system in real time.

• The bay bus refers to protection, measurement and control supervising


the electrical process and taking action in failure case.

• The process bus refers to integrate the primary electrical equipment with
automation system
Architecture of IEC 61850 Electric Power Refinery System

Level 3 Operation Advanced Control System (SCOA)

Level 2– Substation SAS HMI GATEWAY


Router

61850 Station Bus


Client- Server, GOOSE

Level 1 – Bays switch


IED’s IED IED IED IED IED IED

61850 Process Bus


Sampled Values, GOOSE

switch
Level 0 – Process
Intelligent Switchyard MU Brkr IED Brkr IED MU
Sensors, I/Os
Brkr IED MU
COMMUNICATIONS

• Communication topology must be with optical fiber network based on redundant


infrastructure.

• Data and messages communication systems must be operate at 100% on reliability,


and the traffic networks are essential.

• The communication for any each IED which integrate the protection, metering and
control network on system must be connected ensuring selfhealing and any failure
must not affect the functionality.

• The architecture configuration system network must avoid the breaking


communication link.

• The communications services abstract must support multiple communications


protocols base on IEC 61850 as MMS (Manufacturing Message Specification),
GOOSE, SMV as well as web services (FTP conceptual scheme proposed of
communication system to be implemented in the refinery.
Distribution equipment in Refinery
Software Tools for configuration IEC-61850

• The information and the data files generated by the


IED’s must be interoperable.
• We must have software tools for getting information.
• The IEDs functions should be configured by the
software tools IEC 61850 provided for following file
types.
– ICD (IED Capability Description).
– SSD (System Specification Description).
– SED (System Exchange Description).
– SCD (System Configuration Description)
– IID (Instantiated IED Description).
– CID (Configured IED Description).
Model for configuration IED’s based on IEC- 61850
SYSTEM SPECIFICATION (UNIFILAR
IEDs CAPABILITIES OF DIAGRAMS, LOGIAL NODES,
PROTECTION LOGICAL .SSD LOGICAL DEVICES, …)
IED NODES, MEASUREMENT,
DATA CONTROL
.SED
BASE .ICD SYSTEM SYSTEM
EXCHANGE WITH
CONFIGURATOR OTHER SYSTEMS CONFIGURATOR
ASSOCIATION AND RELATIONSHIP OR EQUIPMENT
WITH PRE-CONFIGURATION INITIALIZATION IED
.SCD .IID .SCD
REPORTS, UNIFILARS, BUSES,
DIFFERENTIAL LINE ...
OTHER PROJECTS
CONFIGURATOR IEC 61850
STATION ENGINEERING IED
ENGINEERING/OPERATING STATION

.CID FILE TRANSFER REMOTE

FILE TRANSFER FILE TRANSFER AND


LOCAL SWITCH/ PARAMETERIZATION
SAS DATA WITH IEC 61850

IED IED IED


IEC-61850 monitoring system

• Hardware for the operator and maintenance


interface substation is integrate by server
equipment, IHM display and communications
system.
• This system monitoring protection, measuring
and control functions.
• The server must be with redundancy in all the
components.

• The operator interface display the line diagrams of power system.


• From this system we execute open/close command for breakers.
• The operation must has security access through the user passwords.
• It is important to have software tools for editing and customization the line
diagrams.
• The software should include graphics object libraries required for future
upgrades to the electrical system.
CONCLUSIONS
• The concepts of IEC 61850 in refineries goes beyond the
whole concept of substation. The framework for refineries in
power electrical systems should considering Generation and
Distribution system application

• In all those cases of electrical systems for refineries, should be


considered an alternative supply by the utility, additional
energy to the Generation produced by the refinery, this makes
the system a micro-dynamic system of smart grid.

• In refineries the application of process bus must be fully


robust application taking a variation with respect to the
utilities which applies different schemes and try to validate
the standard gradually.

CONCLUSIONS
• The interoperability is the most important issue for refineries,
considering that the new automation system has to interact
with the currently automation system on information
technology legacy.

• In the next future the refinery power systems could interact


with utility super-grids, considering the possibility, that the
exceeded energy could transfer according the demand of its
own consumption.
END