Midos Type MVTP

Busbar Supervision Relay

Features
l Integral buswire shorting facility
l Low ac burden
l No external resistors required
l Alarm contacts provided

Application
The MVTP relay is available in two
types:
l Type MVTP 11 - single phase relay.

l Type MVTP 31 - three phase relay.

Providing continuous supervision of the


buswires in high impedance type
busbar protection schemes, detecting
open-circuited buswires as well as
open-circuited main current
transformers. In phase and earth fault
busbar protection schemes the three Figure 1: Type MVTP relay withdrawn from case.
phase relay may be used, or
alternatively three single-phase units
may be preferred.
In earth-fault only busbar protection Operation reset contacts of the output relay are
schemes, the single-phase relay is normally connected across the
Isolation from the main CTs is buswires of the busbar protection thus
employed.
achieved by a relay transformer whose short-circuiting the busbar protection
primary winding is connected in series relay and rendering the protection of
Description with a high value resistor. the zone concerned inoperative. On
MVTP relays have a setting range of The secondary output signal of this the same output relay are hand reset
2-14V in 7 equal steps, adjusted by isolating transformer is fed into a contacts for alarm purposes.
means of a plug bridge on the relay current to voltage converter, then Operation of the relay is indicated by
front panel. Relays are continuously rectified for comparison with a pre-set a hand resettable mechanical flag.
rated at 600V rms and no external value.
Associated Publication:
components are required. The ac voltage input is continuously R6006 MSTZ 02.
The relays have a ventilated enclosure monitored and when it exceeds the Power supply unit (dc/dc converter).
fitted to the rear of each case to level pre-set by means of the plug
provide extra thermal dissipation for setting, the output relay is actuated
the auxiliary supply components. after a three second delay. The hand
A

P1 S1 P1 S1 C B
Phase rotation
See note 3
S2 S2
P2 P2
a 1
b Power +
c supply 3 Vx
circuits –
n 23
RL1-1 1
VA 24
3
Alarm
RL1-2 2
25 contacts
87 87 87
A B C 4
v v v VB 26
Output RL1 RL1-3 5
Case earth t
27 >Vs circuits 6
RL1-4
1 2 VC 28 7
3 4
5 6 RL1-5 6
7 8 13
+ve
9 10 See note 3 Power 8
14
11 12 –ve supply RL1-6 9
13 14 22 circuits
15 16 11
17 18
19 20 Case earth connection
21 22
23 24
25 26
27 28
Notes
1 (a) CT shorting links make 2 Earthing connections as shown are typical only
Module terminal before (b) & (c) disconnect. 3 CT connections are typical only.
block viewed (b) Short terminals break before (c)
from rear (c) Long terminals

Figure 2: Application diagram: static modular buswires voltage supervision relay, type MVTP 31.

Technical Data
Burdens
Measuring circuit – typical burdens
Applied voltage Vac 2 8 14 600
Burden VA 0.04x10-3 0.7x10-3 2.2x10-3 4.0
Auxiliary supply – typical burdens at the upper rated voltage
Vx rated voltage Output relay Output relay
not energised energised
(V dc) mA W mA W
30/34 24 0.82 90 3.06
48/54 24 1.3 90 4.86
110/125 24 3.0 35 4.37
220/250 24 6.0 35 8.75
Settings
Setting range (VS) 2-14V rms adjusted by means of a
plug bridge in 7 equal steps.
2, 4, 6, 8, 10, 12, 14V
Auxiliary supplies (VX) Rating (V dc) Operative range (V dc)
24/27* 19.2-30.2
30/34 24 -37.5
48/54 37.5-60
110/125 87.5-137.5
220/250 175 -275
* Use a 30/30V relay with a separate
MSTZ 02 dc/dc converter. All relays
are rated continuously at the
maximum voltage in the operative
range.
Frequency 50 and 60 Hz
Operative range 47-61 Hz
Operating time Fixed at 3 seconds
Contact disengaging time <150ms
Drop off/pick up ratio >85% after 3 second delay
>98% before 3 second delay

Accuracy
Setting ± 5% under reference conditions.
Variation with frequency ± 2% over operative range
Variation with temperature ± 1%/58C change
Variation with auxiliary supply Nil
Timer ± 5% under reference conditions.
Variation with frequency ± 2% over operative range
Variation with temperature ± 1%/5ºC change
Variation with auxiliary supply Nil
Contacts Hand reset
MVTP 11
MVTP 31 } 5

All contacts are normally open

Contact ratings
Make and carry Make and carry Break
continuously for 3 seconds
AC 1250VA with maxima 7500VA with maxima 1250VA with maxima
of 5 amps and of 30 amps and of 5 amps and
300V 300V 300V
DC 1250 watts with 7500 watts with 100 watts (resistive)
maxima of 5 amps maxima of 30 amps 50 watts (inductive)
and 300V and 300V and maxima of
5 amps and 300V
The hand-reset contacts will carry 150A rms for 0.5 seconds.

Thermal rating
Continuous 600V rms per phase on all three phases
simultaneously (at any setting).
Short time The relay will withstand 2kV rms per
phase, for 3 seconds on all three
phases simultaneously (at any setting).

Voltage withstand
Insulation 2kV rms for 1 minute between all case
IEC 255-5 terminals connected together and the
case earth terminal.
2kV rms for 1 minute between
independent circuits including contact
circuits.
1kV rms for 1 minute across normally
open outgoing contact pairs.
High voltage impulse 5kV peak, 1.2/50µs, 0.5J between all
IEC 255-5 terminals and case earth and between
adjacent terminals.
High voltage disturbance 2.5kV peak between independent
IEC 255-22-1 Class III circuits. circuits
2.5kV between circuits and case earth.
1 MHz bursts decaying to 50% peak
value after 3 to 6 cycles.
Repetition rate: 400 per second.
Environmental withstand
Temperature
IEC 68-2-1 Storage and transit –25ºC to +70ºC
IEC 68-2-2 Operating -25ºC to +55ºC
Humidity 56 days (at 93% RH and +40ºC)
IEC 68-2-3
Enclosure protection IP50 (dust protected)
IEC 529
Vibration 0.5g between 10 and 150Hz
IEC 255-21-1

Mechanical durability
Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum
Cases
52
Types MVTP 11 and MVTP 31 are 4 holes 4.4
97 23.5
supplied in size 4 and size 6 cases
respectively, as shown in Figures 3
and 4.
168 159

Information required with Push button


order projection 10 max. 99
Panel cut-out:
Flush mounting fixing details
Relay type (See models available).
DC auxiliary voltage.
32 212 25 min.

177 157 max.

Reset

77 Flush mounting 11
All dimensions in mm

Figure 3: MVTP 11. Case outline size 4.

103.6
149 4 holes 4.4 24

168 159

Push button
projection 10 max. 151
Panel cut-out:
Flush mounting fixing details

32 212 25 min.

177 157 max.

Reset

155 Flush mounting 11


All dimensions in mm

Figure 4: MVTP 31. Case outline size 6.