You are on page 1of 4

www.joongwon.co.

kr

ISO9001 ISO14001

15kV - 38kV Recloser


Polymer Insulated Type

Type of Recloser : JWREC -6A

td
CopyrightⒸ 2015 JOONGWON Corporation All rights reserved

Rev. 2015/ 1 /REC


Introduction
The Joongwon Recloser is designed to meet increasing requirement of the electric utility industry,
providing a safe, maintenance free, long life, economical device to perform fault current interrupting
and reclosing on overhead distribution lines. The Joongwon Recloser is applicable to 12(max.15)kV, 24(max.27)kV,
36(max.38)kV power distribution systems and substation. It can be operated manually(if applicable) or
electrically via controller with FTU and should be mounted to the pole and substation mounting base.

Features
- Proven design rated for 10,000 full load operations
- Hydrophobic Cyloaliphatic Epoxy (HCEP) insulation provides industry leading reliability
- Air insulation for an environmentally friendly design
- Minimal maintenance required for the high voltage unit
- Web Human Machine Interface (web HMI) software for field configuration
- Remote Communication : MODBUS, DNP3.0, DNP3.0 over TCP/IP, IEC 60870-5-101, IEC 60870-5-104 over TCP/IP

Recloser Design

• Magnetic actuator : 10,000 full load operations


• Vacuum interrupters : Lasting quality with 10,000 full load operations
• Pole assembly
- UV protected for environmental durability
- Molded design reduces risk of tampering
• HCEP insulating material
- The Recloser insulating material is Hydrophobic Cycloaliphatic Epoxy(HCEP).
Hydrophobic means resistant to water. This capability is advantageous because it prevents
water from developing completely wetted, resistively conductive surfaces on outdoor insulation.

BUSHING
TERMINAL
LIFTING LUG

GROUND
CONNECTOR
TRIP HANDLE
CLOSING
HANDLE RECEPTACLE

Front View Of Recloser Rear View Of Recloser

td
CopyrightⒸ 2015 JOONGWON Corporation All rights reserved
15kV - 38kV Polymer Insulated Outdoor Vacuum Recloser
for Distribution Automation
Ratings
Ratings and technical data

ITEM RATINGS

RATED SYSTEM VOLTAGE 12 (max. 15) 24 (max. 27) 36 (max. 38) kV

RATED CONTINUOUS CURRENT 630 A

RATED INTERRUPTING CURRENT 12.5 / 16 12.5 / 16 12.5 / 16 kA

POWER FREQUENCY WITHSTAND VOLTAGE

DRY (1 MIN.) 50 60 70 kV

WET (10 SEC.) 45 50 60 kV

LIGHTNING IMPULSE WITHSTAND VOLTAGE 110 150 170 kV

RATED FREQUENCY 50 / 60 Hz
PHASE SPACING 320 320 394 mm

EXTERNAL CREEP DISTANCE, H2-GROUND 1 486 1 486 1 502 mm

EXTERNAL CREEP DISTANCE, H1-H2 1 344 1 344 1 376 mm

MIN. EXTERNAL STRIKE DISTANCE 284 284 448 mm

MIN. INTERRUPTING TIME 0.050 sec

MAX. CLOSING TIME 0.070 sec

INSULATING MATERIAL Epoxy

AMBIENT TEMPERATURE -25 to 70 °C

HUMIDITY ≤100 %

ALTITUDE ≤ 2,000 m

DEGREE OF PROTECTION IP X 8

RATED STANDARD OPERATION DUTY O - 0.3s - CO - 1s - CO - 1s - CO - lockout

MECHANICAL ENDURANCE 10,000 times

RATED CONTROL VOLTAGE AC 110 - 220 V / DC 24 V

WEIGHT (BODY) 120 150 230 kg

WEIGHT (CONTROLLER) 40 kg

APPLIED STANDARD IEC 62271-111, ANSI C37.60 & KEPCO spec.

Note : According to the user’s demand, Joongwon can supply Recloser with different ratings not indicated above.

td
CopyrightⒸ 2015 JOONGWON Corporation All rights reserved
15kV - 38kV Polymer Insulated Outdoor Vacuum Recloser for Distribution Automation

Recloser control
RATINGS

RATED FREQUENCY 50 or 60 Hz
CONTROL VOLTAGE AC 110 - 220 V / DC 24 V

ENVIRONMENTAL

AMBIENT TEMPERATURE RANGE STORAGE -40°C TO +85°C, OPERATION -25°C TO +70°C

OUTDOOR (HUMIDITY) 100%

DEGREE OF PROTECTION IP65


.

INSULATION TEST VOLTAGE 2 kV 50/60Hz, ONE MINUTE

IMPULSE VOLTAGE WITHSTAND 6 kV PEAK, 1.5/50µs, ANSI C62.45, IEC61000-4-5

INTERFERENCE TEST WITHSTAND SWC ANSI C37.90.1, IEC 61000-4-4

RADIO FREQUENCY INTERFERENCE IEC 255-22-3 CLASS III, ANSI C37.90.2

GENERAL PROTECTION ( CT RATIO 1000 : 1 A)

PHASE TIME OVERCURRENT CT RATIO X (0.005 ̴ 1.60), (5 ̴ 1600A)

PHASE INSTANTANEOUS OVER CURRENT CT RATIO X (1.00 ̴ 20.00), (1000 ̴ 20000A)

GROUND TIME OVER CURRENT CT RATIO X (0.0025 ̴ 0.80), (2.5 ̴ 800A)

GROUND INSTANTANEOUS OVER CURRENT CT RATIO X (1.00 ̴ 20.00), (1000 ̴ 20000A)

SENSITIVE EARTH FAULT CT RATIO X (0.0025 ̴ 0.160), (2.5 ̴ 160A)

PHASE AND GROUND TIME CURVE IEEE C37.112, IEC 60225-3, USER PROGRAMMABLE CURVE 37

RECLOSER

RECLOSER TIMES PROGRAMMABLE FROM 1 TO 4


RECLOSING ( DEAD ) TIMES 1st RECLOSER : 0.3-600SEC IN 0.01SEC STEPS.
2nd RECLOSER : 1.0-600SEC IN 0.01SEC STEPS.
3rd RECLOSER : 1.0-600SEC IN 0.01SEC STEPS.
4th RECLOSER : 1.0-600SEC IN 0.01SEC STEPS.

RESET (RECLAIM) TIME 1-600SEC IN 1SEC STEPS

METERING ( AT RATED VOLTAGE AND CURRENT )

CURRENT ±1%

VOLTAGE ±2.5%

WATT HOURS ±5%

VARS HOURS ±3%

DEMANDS ±3%

POWER FACTOR ±0.05%

FREQUENCY ±0.05Hz

RECORDING

WAVEFORM CAPTURE LAST 32 EVENTS WITH 20 cycles & 128 SAMPLES

SYSTEM EVENT LAST 2048 EVENTS

DIAGNOSTIC EVENT LAST 512 EVENTS

LOAD PROFILE LAST 1024 EVENTS, 42 DAYS / 60 Min. (5,10,15,20,30,60 Min INTERVAL)

COUNTER TRIP, FAULT, SYSTEM RESTART, PQM

RECLOSER WEAR PHASE A,B,C

PQM LAST 100 EVENTS

JOONGWON CO. Ltd.


727-9 , Wonsi-dong, Danwon-gu, Ansan-si, Gyeonggi-do, Korea
Tel :82-31-492-6863 〜 4 / 82-31-492-6866(DIR.)
Fax:82-31-492-2620 http//www.joongwon.co.kr
E-mail:joongwon@joongwon.co.kr