WDZ-5271
TV management relay
Technical instruction
V1.02
I
WDZ-5271 TV management relay(V1.02)
Preface
Thank you very much for purchasing WDZ-5271 manufactured by Wiscom(Stock code:
002090).
This technical instruction is for order only and has slight difference with the actual product.
Thus if needed, please ask our design engineers for relative design drawings for engineering.
For more product information, instruction manual updates and services, please visit the
Wiscom website http://www.wiscom.com.cn/.
Copyright © Wiscom System Co., Ltd, All rights reserved Version: V 1.02 This instruction is
for reference only.
II
WDZ-5271 TV management relay(V1.02)
Table of contents
1 Application ................................................................................................................................ 1
2 Protection functions and principles ........................................................................................... 1
2.1 TV fuse-loss alarm ........................................................................................................ 1
2.1.1 Logic diagram ................................................................................................... 1
2.1.2 Criterion ............................................................................................................ 1
st
2.2 1 zone under-voltage protection .................................................................................. 1
2.2.1 Logic diagram ................................................................................................... 2
2.2.2 Criterion ............................................................................................................ 2
nd
2.3 2 zone under-voltage protection ................................................................................. 2
2.3.1 Logic diagram ................................................................................................... 2
2.3.2 Criterion ............................................................................................................ 2
rd
2.4 3 Under-voltage protection ......................................................................................... 2
2.4.1 Logic diagram ................................................................................................... 2
2.4.2 Criterion ............................................................................................................ 3
2.5 Bus overvoltage alarm................................................................................................... 3
2.5.1 Logic diagram ................................................................................................... 3
2.5.2 Criterion ............................................................................................................ 3
2.6 Zero sequence overvoltage alarm.................................................................................. 3
2.6.1 Logic diagram ................................................................................................... 3
2.6.2 Criterion ............................................................................................................ 3
2.7 Non-electrical quantity alarm ........................................................................................ 3
2.7.1 Logic diagram ................................................................................................... 4
2.8 Winding 2 TV fuse-loss alarm ...................................................................................... 4
2.8.1 Logic diagram ................................................................................................... 4
2.8.2 Criterion ............................................................................................................ 4
2.9 Protection parameters .................................................................................................... 4
2.10 Soft strap ....................................................................................................................... 4
3 Measurement and control function............................................................................................ 5
3.1 Measurement function................................................................................................... 5
3.2 DI .................................................................................................................................. 5
3.3 DO ................................................................................................................................. 5
3.4 DCS output.................................................................................................................... 5
4 Backboard terminals and connection diagram .......................................................................... 5
4.1 Analog inputs ................................................................................................................ 5
4.2 Backboard terminals ..................................................................................................... 6
4.3 Terminal connection diagram ........................................................................................ 8
4.3.1 Analog input connection diagram ..................................................................... 8
4.3.2 DI、Central signal、network and AO circuit connection diagram ................ 10
4.3.3 DO circuit connection diagram ....................................................................... 11
5 Order information ................................................................................................................... 11
6 Setting explanation.................................................................................................................. 12
6.1 Note ............................................................................................................................. 12
III
WDZ-5271 TV management relay(V1.02)
IV
WDZ-5271 TV management relay(V1.02)
1 Application
Uab<Ud1
Ubc<Ud1 ≥
TV1 fuse-loss(alarm signal) TV
Uca'<Ud1 fuse-
& 10s Warn
Uab>Ud1 loss
Ubc>Ud1 ≥ alarm
Uca'>Ud1
2.1.2 Criterion
U max > U d 1
U min < U d 1
Where, Umax:the maximum value of phase-to-phase voltage(Uab、Ubc、Uca’)(V)
Umin:the minimum value of phase-to-phase voltage(Uab、Ubc、Uca’)(V)
Ud1:action value of 1st zone Under-voltage protection(V)
1
WDZ-5271 TV management relay(V1.02)
Uab<Ud1
Ubc<Ud1 & 1st zone UV protection Trip 1st zone
Uca'<Ud1 (Trip) UV
& t1 protecti
Switch position Signal on
2.2.2 Criterion
U max < U d 1
t > t1
DIswitchpositionisclosed
Where, t1: action time(s)
Uab<Ud2
Ubc<Ud2 & 2nd zone UV protection Trip 2nd zone
Uca'<Ud2 (Trip) UV
& t2 protecti
Switch position Signal on
2.3.2 Criterion
U max < U d 2
t > t12
DIswitchpositionisclosed
Where, Ud2: action value(V)
t2: action time(s)
Uab<Ud3
Ubc<Ud3 & 3rd zone UV protection Trip 3rd zone
Uca'<Ud3 (Trip) UV
& t3 protectio
Switch position Signal n
2
WDZ-5271 TV management relay(V1.02)
2.4.2 Criterion
U max < U d 3
t > t3
DIswitchpositionisclosed
Where, Ud3: action value(V)
t3: action time(s)
Bus
Uab>Ugy Bus overvoltage (alarm over-
signal)
Ubc>Ugy ≥1 tgy Warn voltage
Uca'>Ugy alarm
2.5.2 Criterion
ZS
Zero sequence overvoltage
(alarm signal) overvolt
3U0>U0dz t0dz Warn age
alarm
2.6.2 Criterion
3U 0 > U 0 dz
t > t0 dz
Where, U0dz: action value(V)
t0dz: action time(s)
3
WDZ-5271 TV management relay(V1.02)
Alarm signal
Non-
Non-electrical electrical
tki Warn
quantity quantity
alarm
Uab2<Ud1
Ubc2<Ud1 ≥ Winding 2 TV fuse-loss (alarm Windin
Uca2'<Ud1 signal) g2 TV
& 10s Warn fuse-
Uab2>Ud1
loss
Ubc2>Ud1 ≥
alarm
Uca2'>Ud1
2.8.2 Criterion
U 2 max > U d 1
U 2 min < U d 1
Where, U2max:the maximum value of Uab2、Ubc2 and Uca2’(V)
U2min:the minimum value of Uab2、Ubc2 and Uca2’(V)
Ud1:the action value of 1st zone UV protection(V)
4
WDZ-5271 TV management relay(V1.02)
3.2 DI
Standard 24 channel digital inputs.
3.3 DO
Standard 20 channels of relay outputs with 24 DO contacts and 8 channels of signal outputs
5
WDZ-5271 TV management relay(V1.02)
Slot 1: AI board
Terminal 101、103 and 105: TV fuse-end phase-to-phase voltage input;
6
WDZ-5271 TV management relay(V1.02)
7
WDZ-5271 TV management relay(V1.02)
8
WDZ-5271 TV management relay(V1.02)
109 110
ZS voltage
1YHa 1RD 注1
101
voltage
1YHb 2RD TV bus voltage
103
1YHc 3RD
105
4RD 注2
2YHa 5RD
circuit
111
winding 2
2YHb 6RD
TV bus voltage
113
2YHc 7RD
115
8RD
winding 2
117 118 TV fuse-forepart voltage
Note1:1RD、2RD and 3RD as well as 5RD、6RD and 7RD fuse can be replaced by integrated 3-phase CB
Note2:the rated current of 4RD/8RD should be larger by 2 levels than 1RD、2RD and 3RD/5RD、6RD and 7RD
9
WDZ-5271 TV management relay(V1.02)
531
device blocking
532
central
503 source
DI1 331
507 ZS overvoltage
332
DI2
508
225
switch position Non-electrical alarm
509 226
DI4
510 227
TV fuse-loss alarm
DI5
telesignal
511 228
l
signa
DI6 229
512 winding2
DI7 TV fuse-loss alarm
513 230
DI8 231
514 standby signal
DI9 232
515
acquisition
DI10 NET1-A
516
401
DI11 Fieldbus1
517 NET1-B
DI12 402
518
communication
signal earth
DI13 403
519
DI14 NET2-A
520 404 Fieldbus2
DI15 NET2-B
521
405
DI16
network
522 GPS+
DI17 406
523
GPS- GPS synchronization
DI18 407
524
DI19 signal earth
525 408
DI20
526
注1
Analog
DI21 AO1
527
414
DI22
528 AO 2
415
output
DI23
529
common output
DI24 416
530
common DI
506 note1: R is external resisitance,(< 500ohm, 250ohm is suggested)
10
WDZ-5271 TV management relay(V1.02)
301 201
304 204
305 205
5 Order information
WDZ-5271 0 0 0
Network configuration
1:CAN
2:ProfiBus
DC power source
1:110V
2:220V
11
WDZ-5271 TV management relay(V1.02)
6 Setting explanation
6.1 Note
This part is for reference only.
12