WDZ-5271
TV management relay

Technical instruction

V1.02

Wiscom System Co., Ltd.

I
WDZ-5271 TV management relay(V1.02)

Preface

Thank you very much for purchasing WDZ-5271 manufactured by Wiscom(Stock code:
002090).

This technical instruction is for order only and has slight difference with the actual product.
Thus if needed, please ask our design engineers for relative design drawings for engineering.

For more product information, instruction manual updates and services, please visit the
Wiscom website http://www.wiscom.com.cn/.

Copyright © Wiscom System Co., Ltd, All rights reserved Version: V 1.02 This instruction is
for reference only.

II
WDZ-5271 TV management relay(V1.02)

Table of contents

1 Application ................................................................................................................................ 1
2 Protection functions and principles ........................................................................................... 1
2.1 TV fuse-loss alarm ........................................................................................................ 1
2.1.1 Logic diagram ................................................................................................... 1
2.1.2 Criterion ............................................................................................................ 1
st
2.2 1 zone under-voltage protection .................................................................................. 1
2.2.1 Logic diagram ................................................................................................... 2
2.2.2 Criterion ............................................................................................................ 2
nd
2.3 2 zone under-voltage protection ................................................................................. 2
2.3.1 Logic diagram ................................................................................................... 2
2.3.2 Criterion ............................................................................................................ 2
rd
2.4 3 Under-voltage protection ......................................................................................... 2
2.4.1 Logic diagram ................................................................................................... 2
2.4.2 Criterion ............................................................................................................ 3
2.5 Bus overvoltage alarm................................................................................................... 3
2.5.1 Logic diagram ................................................................................................... 3
2.5.2 Criterion ............................................................................................................ 3
2.6 Zero sequence overvoltage alarm.................................................................................. 3
2.6.1 Logic diagram ................................................................................................... 3
2.6.2 Criterion ............................................................................................................ 3
2.7 Non-electrical quantity alarm ........................................................................................ 3
2.7.1 Logic diagram ................................................................................................... 4
2.8 Winding 2 TV fuse-loss alarm ...................................................................................... 4
2.8.1 Logic diagram ................................................................................................... 4
2.8.2 Criterion ............................................................................................................ 4
2.9 Protection parameters .................................................................................................... 4
2.10 Soft strap ....................................................................................................................... 4
3 Measurement and control function............................................................................................ 5
3.1 Measurement function................................................................................................... 5
3.2 DI .................................................................................................................................. 5
3.3 DO ................................................................................................................................. 5
3.4 DCS output.................................................................................................................... 5
4 Backboard terminals and connection diagram .......................................................................... 5
4.1 Analog inputs ................................................................................................................ 5
4.2 Backboard terminals ..................................................................................................... 6
4.3 Terminal connection diagram ........................................................................................ 8
4.3.1 Analog input connection diagram ..................................................................... 8
4.3.2 DI、Central signal、network and AO circuit connection diagram ................ 10
4.3.3 DO circuit connection diagram ....................................................................... 11
5 Order information ................................................................................................................... 11
6 Setting explanation.................................................................................................................. 12
6.1 Note ............................................................................................................................. 12

III
WDZ-5271 TV management relay(V1.02)

6.2 1st zone under-voltage protection ................................................................................ 12


6.3 2nd zone under-voltage protection ............................................................................... 12
6.4 3rd zone under-voltage protection................................................................................ 12
6.5 Zero sequence overvoltage alarm................................................................................ 12

IV
WDZ-5271 TV management relay(V1.02)

WDZ-5271 TV management relay

1 Application

WDZ-5271 TV management relay is mainly applied to 10KV/6KV/380V system in power


plant for Y/Y/open delta or Y/Y/Y type TV protection, measurement and control function.

2 Protection functions and principles

2.1 TV fuse-loss alarm


If at least one phase voltage is normal but one phase voltage value is smaller than the setpoint of
1st zone UV protection, the device will block under-voltage protection instantaneously and issue
TV fuse-loss alarm signals after 10s delay.
In order to avoid the mal-operation of UV protection due to simultaneous 3-phase fuse-loss, the
device replaces Uca (fuse-end voltage) by Uca’(fuse-forepart voltage) for logic discrimination.

2.1.1 Logic diagram

Uab<Ud1
Ubc<Ud1 ≥
TV1 fuse-loss(alarm signal) TV
Uca'<Ud1 fuse-
& 10s Warn
Uab>Ud1 loss
Ubc>Ud1 ≥ alarm
Uca'>Ud1

2.1.2 Criterion

U max > U d 1

U min < U d 1
Where, Umax:the maximum value of phase-to-phase voltage(Uab、Ubc、Uca’)(V)
Umin:the minimum value of phase-to-phase voltage(Uab、Ubc、Uca’)(V)
Ud1:action value of 1st zone Under-voltage protection(V)

2.2 1st zone under-voltage protection


The device supplies 3 zones of under-voltage protections.
In order to avoid a mal-operation of UV protection when TV fuse-loss occurs, the UV
protection will be blocked by switch position DI instantaneously. When the TV works well, the
DI-switch position is closed, namely this is a break contact. When the TV fault occurs, the DI will
be opened, the UV protection will be blocked and alarm signal will be issued.

1
WDZ-5271 TV management relay(V1.02)

2.2.1 Logic diagram

Uab<Ud1
Ubc<Ud1 & 1st zone UV protection Trip 1st zone
Uca'<Ud1 (Trip) UV
& t1 protecti
Switch position Signal on

2.2.2 Criterion

U max < U d 1

t > t1
 DIswitchpositionisclosed

Where, t1: action time(s)

2.3 2nd zone under-voltage protection


2.3.1 Logic diagram

Uab<Ud2
Ubc<Ud2 & 2nd zone UV protection Trip 2nd zone
Uca'<Ud2 (Trip) UV
& t2 protecti
Switch position Signal on

2.3.2 Criterion

U max < U d 2

t > t12
 DIswitchpositionisclosed

Where, Ud2: action value(V)
t2: action time(s)

2.4 3rd Under-voltage protection


2.4.1 Logic diagram

Uab<Ud3
Ubc<Ud3 & 3rd zone UV protection Trip 3rd zone
Uca'<Ud3 (Trip) UV
& t3 protectio
Switch position Signal n

2
WDZ-5271 TV management relay(V1.02)

2.4.2 Criterion

U max < U d 3

t > t3
 DIswitchpositionisclosed

Where, Ud3: action value(V)
t3: action time(s)

2.5 Bus overvoltage alarm


2.5.1 Logic diagram

Bus
Uab>Ugy Bus overvoltage (alarm over-
signal)
Ubc>Ugy ≥1 tgy Warn voltage
Uca'>Ugy alarm

2.5.2 Criterion

U max > U gy



t > t gy
Where, Ugy: action value(V)
tgy: action time(s)

2.6 Zero sequence overvoltage alarm


2.6.1 Logic diagram

ZS
Zero sequence overvoltage
(alarm signal) overvolt
3U0>U0dz t0dz Warn age
alarm

2.6.2 Criterion

3U 0 > U 0 dz

t > t0 dz
Where, U0dz: action value(V)
t0dz: action time(s)

2.7 Non-electrical quantity alarm


The device supplies 3 non-electrical quantity protections, which are associated with
non-electrical quantity DIs. The DI for switch position is break contact, namely, when the DI is
opened, alarm signal will be issued. The other 2 DIs are make contacts, when the relative DI is
closed, the corresponding protection will be triggered.

3
WDZ-5271 TV management relay(V1.02)

2.7.1 Logic diagram

Alarm signal
Non-
Non-electrical electrical
tki Warn
quantity quantity
alarm

2.8 Winding 2 TV fuse-loss alarm


This function is for Y/Y/Y type TV only.

2.8.1 Logic diagram

Uab2<Ud1
Ubc2<Ud1 ≥ Winding 2 TV fuse-loss (alarm Windin
Uca2'<Ud1 signal) g2 TV
& 10s Warn fuse-
Uab2>Ud1
loss
Ubc2>Ud1 ≥
alarm
Uca2'>Ud1

2.8.2 Criterion

U 2 max > U d 1

U 2 min < U d 1
Where, U2max:the maximum value of Uab2、Ubc2 and Uca2’(V)
U2min:the minimum value of Uab2、Ubc2 and Uca2’(V)
Ud1:the action value of 1st zone UV protection(V)

2.9 Protection parameters


No. Name Symbol Unit Range
st
1 1 zone UV protection action value Ud1 V 10.00-100.00
st
2 1 zone UV protection action time t1 s 0.10-30.00
nd
3 2 zone UV protection action value Ud2 V 10.00-100.00
nd
4 2 zone UV protection action time t2 s 0.10-30.00
rd
5 3 zone UV protection action value Ud3 V 10.00-100.00
rd
6 3 zone UV protection action time t3 s 0.10-30.00
7 Bus overvoltage action value Ugy V 100.00-120.00
8 Bus overvoltage action time tgy s 0.10-100.00
Zero sequence overvoltage action U0dz
9 V 2.00-80.00
value
10 Zero sequence overvoltage action time t0dz s 0.10-100.00
11 Non-electrical quantity1 alarm time tKI1 S 0.10-650.00
12 Non-electrical quantity2 alarm time tKI2 S 0.10-650.00
13 Switch position alarm time tKI3 S 0.10-650.00

2.10 Soft strap


During the soft strap on/off process, virtual telesignal status-change information about soft

4
WDZ-5271 TV management relay(V1.02)

strap will be made.


No. Name Symbol Range
st
1 1 zone UV protection On/Off
nd
2 2 zone UV protection On/Off
rd
3 3 zone UV protection On/Off
4 TV fuse-loss alarm On/Off
5 Bus overvoltage alarm On/Off
Zero sequence overvoltage On/Off
6
alarm
7 Non-electrical quantity1 alarm On/Off
8 Non-electrical quantity2 alarm On/Off
9 Switch position alarm On/Off
10 Winding 2 TV fuse-loss alarm On/Off

3 Measurement and control function

3.1 Measurement function


3-phase voltage, fuse-forepart voltage, zero sequence voltage and frequency.

3.2 DI
Standard 24 channel digital inputs.

3.3 DO
Standard 20 channels of relay outputs with 24 DO contacts and 8 channels of signal outputs

3.4 DCS output


1 channel of 4~20mA output is supplied and 2 4~20mA outputs are optional.

4 Backboard terminals and connection diagram

4.1 Analog inputs


Ua、Ub、Uc: TV bus voltage (fuse-end voltage: 100V rated voltage), for protection and
measurement functions. Phase-to-phase voltage connection.
3U0: TV open delta voltage(zero sequence voltage).
uA、uC: phase A and phase C voltage ( fuse-forepart voltage).
Ua2、Ub2 and Uc2: bus voltage of winding2 TV( rated: 100V), for protection and measurement
functions together. Phase-to-phase voltage.
uA2、uC2: phase A and phase C voltage ( winding2 TV fuse-forepart voltage).

5
WDZ-5271 TV management relay(V1.02)

4.2 Backboard terminals


From the front view, the slots are arranged with number from 1 to 5 from left to right.
Terminal number has 3 digits. The first digit is the slot number and the last two digits are the
terminal series number from above to below. Take 201 for example, it means the first terminal in
slot2.

Slot 1: AI board
Terminal 101、103 and 105: TV fuse-end phase-to-phase voltage input;

6
WDZ-5271 TV management relay(V1.02)

Terminal 107: TV fuse-forepart phase-A voltage input;


Terminal 108: TV fuse-forepart phase-C voltage input;
Terminal 109~110: TV zero sequence voltage input, (3U0);
Terminal 111、113 and 115: winding2 TV fuse-end phase-to-phase voltage input;
Terminal 117: winding2 TV fuse-forepart phase-A voltage input;
Terminal 118: winding2 TV fuse-forepart phase-C voltage input.
Slot 2: DO board
Terminal 201~204: DO15, can be associated with 3 zones of UV protections. 201~202:
one pair of contact output;203~204: the other pair of contact output.
Terminal 205~208: DO16. 205~206: one pair of contact output;207~208: the other pair
of contact output.
Terminal 209~210: DO 17
Terminal 211~212: DO 18
Terminal 213~214: DO 19
Terminal 215~216: DO 20
Terminal 217~218: DO 21
Terminal 219~220: DO 22
Terminal 221~222: DO 23
Terminal 223~224: DO 24
Terminal 225~226: Non-electrical quantity alarm signal output;
Terminal 227~228: TV fuse-loss alarm signal output;
Terminal 229~230: winding2 TV fuse-loss alarm signal output;
Terminal 231~232: DO28, standby signal output.
Slot3:DO board
Terminal 301~304: DO1. 301~302: one pair of contact output;303~304: the other pair
of contact output.
Terminal 305~308: DO2. 305~306: one pair of contact output;307~308: the other pair
of contact output.
Terminal 309~310: DO3
Terminal 311~312: DO4
Terminal 313~314: DO5
Terminal 315~316: DO6
Terminal 317~318: DO7
Terminal 319~320: DO8
Terminal 321~322: DO9

7
WDZ-5271 TV management relay(V1.02)

Terminal 323~324: DO10


Terminal 325~326: Device fault alarm signal output;
Terminal 327~328: UV protection action signal output;
Terminal 329~330: Bus overvoltage alarm signal output;
Terminal 431~432: Zero sequence overvoltage alarm signal output.
Slot 4: DI board
Terminal 401~402: Fieldbus1 input, 401: positive, 402: Negative. CAN or ProfiBus
interface is ok.
Terminal 403: Signal earth;
Terminal 404~405: Fieldbus2 input,404: positive,405: Negative. CAN or ProfiBus
interface is ok.
Terminal 406~407: GPS synchronization input port, connected to 485 differential level.
Terminal 408: Signal earth;
Terminal 414~416: 2 channels of 4~20mA outputs. 414~416: the first channel of 4~
20mA output,414: positive, 416: Negative;415~416: the other channel of 4~20mA
output,415: positive, 416: Negative.
Grounding screw must be connected to earth mat reliably and tightly.
Slot 5:PWR board
Terminal 503~504: Device power source input, DC/AC220V or DC/AC110V. 503:
negative device power source input,504: Positive device power source input;
Terminal 506~530: 24 channels of DC 110V or DC220V strong current inputs. 506:
-common DI, 507~530: 24 channels of digital inputs. 507,508 and 509: the defaulted 3
non-electrical quantity protections, among which, 509 is the switch position.
Terminal 531~532: Device blocking output, break contact. When the device 24V power is
lost or internal CPU fails, the contact will be closed.

4.3 Terminal connection diagram


4.3.1 Analog input connection diagram

8
WDZ-5271 TV management relay(V1.02)

109 110
ZS voltage

1YHa 1RD 注1

101

voltage
1YHb 2RD TV bus voltage

103

1YHc 3RD

105
4RD 注2

107 108 TV fuse-forepart voltage

2YHa 5RD

circuit
111
winding 2
2YHb 6RD
TV bus voltage
113

2YHc 7RD

115
8RD
winding 2
117 118 TV fuse-forepart voltage

Note1:1RD、2RD and 3RD as well as 5RD、6RD and 7RD fuse can be replaced by integrated 3-phase CB
Note2:the rated current of 4RD/8RD should be larger by 2 levels than 1RD、2RD and 3RD/5RD、6RD and 7RD

9
WDZ-5271 TV management relay(V1.02)

4.3.2 DI、Central signal、network and AO circuit connection diagram

531
device blocking
532

-KM +KM 325


small bus device fault
3 1 326
1Q air switch
4 2 327
UV protection act
Device 328
L/DC+
504 329
power bus overvoltagea
L/DC- 330

central
503 source

DI1 331
507 ZS overvoltage
332
DI2
508
225
switch position Non-electrical alarm
509 226
DI4
510 227
TV fuse-loss alarm
DI5
telesignal
511 228

l
signa
DI6 229
512 winding2
DI7 TV fuse-loss alarm
513 230

DI8 231
514 standby signal
DI9 232
515
acquisition

DI10 NET1-A
516
401
DI11 Fieldbus1
517 NET1-B
DI12 402
518

communication
signal earth
DI13 403
519
DI14 NET2-A
520 404 Fieldbus2
DI15 NET2-B
521
405
DI16

network
522 GPS+
DI17 406
523
GPS- GPS synchronization
DI18 407
524
DI19 signal earth
525 408
DI20
526
注1
Analog

DI21 AO1
527
414
DI22
528 AO 2
415
output

DI23
529
common output
DI24 416
530
common DI
506 note1: R is external resisitance,(< 500ohm, 250ohm is suggested)

10
WDZ-5271 TV management relay(V1.02)

4.3.3 DO circuit connection diagram

301 201

302 DO1 202 DO15


303 203

304 204

305 205

306 DO2 206 DO16


307 207
UV UV
308 208

309 DO3 209 DO17


310 210

311 DO4 211 DO18


312 212

313 DO5 213 DO19


314 214
output output
315 DO6 215 DO20
316 216

317 DO7 217 DO21


318 218

319 DO8 219 DO22


320 220

321 DO9 221 DO23


322 222

323 DO10 223 DO24


324 224

5 Order information

WDZ-5271 0 0 0
Network configuration
1:CAN
2:ProfiBus

DC power source
1:110V
2:220V

(1)Network interface can be CAN or ProfiBus, redundancy configuration; if RS485 is wanted,


please make note especially;

11
WDZ-5271 TV management relay(V1.02)

(2)DC110V and DC220V are for DI power source only.


(3)The device is equipped with 1 channel of 4~20mA output, if no such output is needed or 2
channels 4~20mA are needed, please order it specially;
(4)The device secondary rated voltage is 100V、50Hz,phase-to-phase voltage input;
(5)The device is not equipped with hardware energy board and operating circuit.

6 Setting explanation

6.1 Note
This part is for reference only.

6.2 1st zone under-voltage protection


In order to ensure that the key motor can self-start, the under-voltage protection of some
unnecessary motors can be disabled after a time delay of 0.5s. The settings are as follows:
Action value: Ud1 =(0.6~0.7)Un
Action time: t1=0.5s
The protection output can be set as any one through trip matrix.

6.3 2nd zone under-voltage protection


The protection is applied to the motors that are not permitted self-startup at power-on when
they are stopped completely.
Action value:Ud2 =(0.4~0.45)Un
Action time: t2 =9s
The protection output can be set as any one through trip matrix.

6.4 3rd zone under-voltage protection


It’s the standby under-voltage protection.
Action value: Ud3 =(0.4~0.45)Un
Action time: t3 =(0.5~9)s
The protection output can be set as any one through trip matrix.

6.5 Zero sequence overvoltage alarm


Basically the action value U0dz=(15~30)V, to avoid the TV unbalanced voltage under normal
operation condition.

12