Professional Documents
Culture Documents
ground source heat pumps This version is expanded to the larger HVAC
industry to provide alternative perspectives to traditional HVAC
publications. The editor is author of two widely sold ASHRAE
publications, HVAC Simplified (2006) and Geothermal Heating and
Cooling (2014). He has presented over 160 seminars to 5000 attendees.
Steve Kavanaugh, Ph.D., Fellow ASHRAE and Fellow ASME
Previous issues available at www.geokiss.com.
E-mail geokisseis@gmail.com to be on the distribution list.
An Alternative Publication for Skeptics of Conventional HVAC & GSHP Wisdom – Volume 9, Number 4 – Fall 2022
Commercial Building Energy Consumption Updates and New furnaces and package heating units) mimicked cooling type
Heat Pump Rating Improvements and Loopholes results using between 70 and 76 kBtu/ft2-yr.
Good News: Small Decline in Commercial Building Energy Use…1
Bad News: High-Efficient Systems Aren’t, Btu/Person the Same..2
2010-2018 Buildings Use Less Energy than 2000-2009 Buildings
but More Energy than 1980-1999 Buildings…………..………………….2
Good News: Heat Pump Rating at 5°F & ESP=0.5 Inches Water.…3
Bad News: Seasonal Rating Shenanigans Remain………………….….3
Estimating Performance at Extreme Temperatures………………..…4
Figure 1 and 2 shows results for the three most recent Commercial
Building Energy Consumption Surveys (CBECS) conducted by
the US Energy Information Administration (EIA). Figure 1 lists
the annual thousands of Btus used per year square foot of floor
space categorized by the cooling equipment type. Although
systems typically used in larger buildings (variable air volume
(VAV), central chillers and district cooling) remain the highest
consumers, their improvements between 2013 and 2018 are the
most dramatic. Unitary equipment also improved to values
between 70 and 76 kBtu/ft2-yr.
The 5°F rating point for capacity and COP can be coupled with Table 1. AHRI Std. 210/240 HSPF Bin Temperatures
the existing 47°F and 17°F ratings to estimate performance at HSPF and HSPF2 Fraction of Outdoor Temperature
slightly lower temperatures (but not all the way to -13°F). Heating Region 4 Region 5
Hopefully, the standard will require the airflow to be held OAT( °F) 2017 2023 2023
constant for all three rating temperatures. A shenanigan some 67 0.132 0 0
manufacturers employ is to increase the airflow below 17°F 62 0.111 0 0
temperatures to improve COP in published performance data. 57 0.103 0.103 0.086
With the formerly required external static pressure (ESP) of only 52 0.093 0.093 0.076
0.1 to 0.2 inches of water gauge (in. w.g.), the added fan power 47 0.100 0.100 0.078
was small compared to what is required in the field. The updated 42 0.109 0.109 0.087
37 0.126 0.126 0.102
standard ESP is 0.5 in. w.g. for units up to 65,000 Btu/h. Filter
27 0.087 0.087 0.094
loss remains at a measly 0.08 inches, which is typical of a clean
22 0.055 0.055 0.074
low MERV fiberglass filter at a low face velocity.
17 0.036 0.036 0.055
12 Total = 0.95 0.026 0.047
7 0.013 0.038
2 0.006 0.029
-3 0.002 0.018
-8 0.001 0.010
-13 Total = 0.76 0.005
-18 0.002
-23 Total Fraction < 1.0 ??? 0.001
Total = 0.802
than the building heat loss. Exact predictions require field 100 Overspeeed 4
measurements during local extreme weather conditions.
75 No Overspeeed 3
Figure 10. Integrated Heating Capacity (IHC) and TH COP
COP
COP of 3-Ton 16 SEER/8.0 HSPF Heat Pump 50 2
60 IHC includes the deduction for defrost but not COP with Overspeed
Heating Cap. (kBtu/h)
30 3 -20 -13 0 20 40 60
Outdoor Air Temperature (°F)
20 2 www.ahridirectory.org/NewSearch?programId=72&searchTypeId
TH COP
10 1
-20°C -10°C 0°C 10°C The challenges of creating high COP heat pumps using low OAT
0
as the heat source are enormous. Consider a unit using R32
-20 -10 0 10 20 30 40 50 60
Outdoor Air Temperature (°F)
refrigerant at -13°F OAT delivering 90°F indoor air (IAT) to the
space. The refrigerant temperature would have to be several
degrees below -13°F OAT to extract heat and several degrees
Testing heat pumps for heating capacity (HC) and coefficient of above 90°F to deliver heat to the space. At -23°F the suction
performance (COP) at very low temperatures requires pressure of R32 is 39 psia and the discharge pressure is 340 psia
specialized laboratories. Determining HC and COP below 17°F at 100°F. The compression ratio (CR) = 8.7 (340÷39) which
(-8°C) requires extended extrapolation that limits accuracy. The would likely require 2-stage compression or vapor re-injection.
5°F (-15°C) rating point will improve this accuracy. Figure 11
provides an example using pre-2023 information from the AHRI Compare this with a vertical loop GSHP using ground at 50°F
Certified Directory to estimate the results of an 8-ton variable (central New York, Wisconsin, Montana). The liquid in the
refrigerant flow (VRF) unit. Some proponents of this technology ground loop would decline several degrees below 50°F and the
claim 80% capacity at -13°F (-25°C). R32 inlet temperature would be near 30°F. The suction pressure
would be 114 psia and the CR = 3.0 (340÷114). The power to
This technology incorporates a variable-speed compressor in ASHP compressor(s) would nearly 3 times the GSHP power.
which a portion of the condensed refrigerant is by-passed to a
Page 4