TEST REPORT

No. : SZIN1803003541SC
Date : Mar 26, 2018
Page: 1 of 7

CUSTOMER NAME: FOAMTECH POLYURETHANE FOAM MANUFACTORY


ADDRESS: LIANGBIAN INDUSTRIAL ESTATE, LIAOBU TOWN, DONGGUAN,
GUANGDONG, CHINA

Sample Name : FOAM


Above information and sample(s) was/were submitted and confirmed by the client. SGS, however,
assumes no responsibility to verify the accuracy, adequacy and completeness of the sample
information provided by client.
***********
SGS Ref. No. : SDHL1803004198FB
Date of Receipt : Mar 26, 2018
Testing Start Date : Mar 26, 2018
Testing End Date : Mar 26, 2018
Test result(s) : For further details, please refer to the following page(s)
(Unless otherwise stated the results shown in this test report refer only to
the sample(s) tested)

Signed for
SGS-CSTC Standards Technical
Services Co., Ltd. Shenzhen Branch
Testing Center

Helen_Xiong
Authorized signatory
TEST REPORT
No. : SZIN1803003541SC
Date : Mar 26, 2018
Page: 2 of 7

Test Result Summary


No. Test(s) Requested Result(s) Comments

Schedule 1 PartⅠ of Furniture and Furnishings

1 (Fire) (Safety) Regulations 1988 With PASS /


Amendments In 1989, 1993 and 2010 of United
Kingdom
2 California Technical Bulletin 117-2013 Section 3 PASS /

Test 1

Test Conducted:

The Test, Specified in Schedule 1 Part Ⅰof the Furniture and Furnishings (Fire) (Safety)

Regulations, is based on BS 5852: Part 2: 1982.

To assess the ignitability of polyurethane foam in slab used in upholstered components when
subjected to ignition source 5.

General Information:
Approximately
Materials Foam Density 3
32.9 kg/m
Actual Thickness of
Specified Thickness of Specimen (75±2) mm 77 mm
Specimen

Precondition Indoor Ambient Condition 72 h

Conditioning of Test Specimen


Temperature:(23±2)℃;Relative Humidity: (50±5) Duration:24 h;
and Ignition Source(s)
Testing Enclosure (fume
22 ℃ RH 40  ---
cupboard / room)
TEST REPORT
No. : SZIN1803003541SC
Date : Mar 26, 2018
Page: 3 of 7

Test Results:

The following test results relate only to the ignitability of the combination of materials under the
particular condition of test. They are not intended as a means of assessing the full potential fire hazard
of the materials or products in use.
Results
Test Criteria st
1 test 2
nd
test
(A) Progressive smouldering (Clause 4.1 of BS 5852: Part 2: 1982)
4.1 b) Any composite that product externally detectable amounts of smoke, heat or
NO NO
glow 60 min after ignition of the crib.
4.1 c) Any composite that displays escalating combustion behaviour so that it is
NO NO
unsafe to continue the test and requires forcible extinction.
4.1 d) Any composite that smoulders until it is essentially consumed within the test
NO NO
duration relevant to the source
4.1 e) Any composite that smoulders to the extremities of the specimen viz upper or
NO NO
lower margins, either side or to its full thickness, within the duration of the test.
4.1 f) Any composite that, on the final examination, shows evidence of charring other
than discolouration, more than 100 mm in any direction apart from upwards from the NO NO
nearest part of the original position of the source.
TEST REPORT
No. : SZIN1803003541SC
Date : Mar 26, 2018
Page: 4 of 7

Results
Test Criteria st
1 test 2
nd
test
(B) Flaming (Clause 4.2 of BS 5852: Part 2 :1982)
4.2 b) Any composite that continues to flame for more than 10 minutes after the
NO NO
ignition of the crib.
4.2 d) Any composite that displays escalating combustion behaviour so that it is
NO NO
unsafe to continue the test and forcible extinction is required.
4.2 e) Any composite that burns until it is essentially consumed within the test duration
NO NO
relevant to the source.
4.2 f) Any composite on which any flame front reaches the lower margin, either side or
NO NO
passes through the full thickness of the specimen within the duration of the test.
(C) Mass Loss (Clause 5 in Schedule 1 Part1 of UK Regulations)
If failure against the criteria of clause 4 of BS 5852:Part 2 has occurred but only by
way of damage exceeding the limits defined in clause 4.1(e), 4.1(f) and 4.2(f) and
26 g 33 g
provided that the resultant mass loss is less than 60g the foam passes the ignitability
test.
TEST REPORT
No. : SZIN1803003541SC
Date : Mar 26, 2018
Page: 5 of 7

Test Details:
The cover materials for this test were 100 percent flame retardant polyester fibres specified in
Schedule 1, Part I of the Regulations.

Test No. 1st 2nd

Ignition source (min, sec) 02min06s 02min18s

Duration of Flames (min, sec) 02min35s 03min11s

Smoke (min, sec) 06min24s 07min05s

Extent of damage of Foam - Width (mm) 85 96


horizontal
component Foam - Length (mm) 127 135

Foam - Depth (mm) 62 65

Extent of damage of Foam - Length (mm) 145 153


vertical component
Foam - Depth (mm) 65 70

The initial mass of the sample composite (g) 6139 6184

The final mass of sample composite(g) 6113 6151

The final mass loss of the composite(g) 26 33

Rating, comments & observations #1 #1

Conclusion: PASS
Remark: N/A--Not Applicable; N/C--Not Conduct;
#1—Pass, flaming but self-extinguishment, the resultant mass loss is less than 60g;
#2—Fail, flaming but self-extinguishment, the resultant mass loss is more than 60g;
#3—Fail, extinguished by operator, escalating flaming combustion;
#4—The first test failed, so retest was not conducted;
TEST REPORT
No. : SZIN1803003541SC
Date : Mar 26, 2018
Page: 6 of 7

Test 2
Test Conducted:

TB117 Requirements, Test Procedure and Apparatus for Testing the Smolder Resistance of Materials
Used in Upholstered Furniture-2013 Section 3-Resilient Filling Material Test

I. Sample Details

3
Material: Foam Density of sample: 27.2 kg/m

II. Test Condition


Temperature Relative humidity Duration
Conditioning of test
(21±3)°C RH < 55  24h
samples and cigarettes

III. Acceptance Criteria:


1. A single mock-up test specimen fails to meet the requirements of this test procedure if any of the
following criteria occurs:
a) The mock-up test specimen continues to smolder after the 45 minute test duration;
b) A vertical char length of more than 1.5 inches develops on the cover fabric.
c) The mock-up test specimen transitions to open flaming.
2. The resilient filling material passes the test if three mock-up specimens pass the test.
3. If more than one specimen fails, the resilient filling material fails the test.
4. If any one of the three initial specimens fails, repeat the test on additional three specimens.
5. If all three additional specimens pass the test, the resilient filling material passes the test. If any one
of the additional three specimens fails, the resilient filling material fails the test.
TEST REPORT
No. : SZIN1803003541SC
Date : Mar 26, 2018
Page: 7 of 7

IV. Test Result


Duration of smouldering Open flaming Vertical Char Length
Specimen # Rating
( min : sec.) (YES/NO) (inches)
1 31min17s NO 0.6 PASS
2 32min24s NO 0.6 PASS
3 31min49s NO 0.6 PASS
Conclusion: PASS

Photo Appendix:

Foam for test 1 Foam for test 2

Appendix information:
1.The above tests were carried out by SGS-CSTC Standards Technical Services Co.,

Ltd. ShunDe Branch.

2. The test results are copied from report No.: SZIN1803002755SC.


******** End of report********