Professional Documents
Culture Documents
ENGINEERING
TRANSFORMER DESIGN
1. The work contained in this report is original and has not been taken in any other sources available
anywhere either in similar design projects or in the internet.
3. In cases where we have used relevant information from various sources, we have given due credit
to them in the text of the report and giving their full details in the reference list.
4. This report has not been submitted for any other degree or examination at any other University.
5. This report does not contain other previous reports data, pictures, graphs or any other information,
unless acknowledged as being sourced from other reports or persons.
i
Abstract
This report presents results obtained in the design of a three phase core-type delta-star distribution
transformer using Finite Element Method Magnetics (FEMM) software tool. The design is broken into four
sub-sections which includes the Magnetic design section, Thermal design section, Short circuit design
section and Electrical Insulation design section. In the magnetic design section, a confirmation of the
transformer design dimensions against theoretical calculations is presented, the short circuit design section
presents findings based on the radial and axial forces experienced by the transformer windings, the thermal
design section confirms the current density and losses of the transformer at full load and lastly the electrical
insulation design section confirms that under the influence of an electric field, different type of materials
have different insulation capabilities to prevent charges flowing freely between the high voltage (HV) side
and the low voltage (LV) side of a transformer. A brief summary is presented at the end of the report on
how to improve the design in order to meet the transformer design specification.
ii
Table of Contents
Declaration……………………………………………………………………………………………………………………………………..i
Abstract…………………………………………………………………………………………………………………………………………ii
List of symbols………………………………………………………………………………………………………………………………..v
1. Introduction ........................................................................................................................................... 1
2. Magnetic Circuit Design Section (Lungelo Zindela) ............................................................................ 2
2.1 The core design procedure .................................................................................................................. 2
2.2 The winding design procedure............................................................................................................ 3
2.3 Results and comparison to theoretical design.................................................................................... 4
2.3.1 Magnetic flux density ................................................................................................................... 5
2.3.2 Magnetizing Current .................................................................................................................... 6
2.4 Correlation to Other sub-project ........................................................................................................ 7
2.5 Discussion and recommendations ...................................................................................................... 7
3. Thermal Design (Ayanda Sibiya) ................................................................................................... 8
3.1 Design procedure ...................................................................................................................... 8
3.2 Results and comparison to theoretical design .......................................................................... 9
3.2.1 Result under heat generation ............................................................................................... 9
3.2.2 Result of transformer under cooling effect ........................................................................ 10
3.3 Correlation to Other sub-project ............................................................................................ 11
3.4 Discussion and recommendations .......................................................................................... 11
3.5 Calculations ............................................................................................................................. 12
3.6 Improvements ......................................................................................................................... 12
4 Insulation design(Simphiwe Dubazana) ......................................................................................... 13
4.1 Design procedure ........................................................................................................................ 13
4.2 Material description .................................................................................................................... 14
4.3 Discussion of results ................................................................................................................... 15
4.4 Improvements ............................................................................................................................. 17
5 Short circuit Design (Nkosinathi Majozi) ....................................................................................... 17
5.1 Design procedure ........................................................................................................................ 17
5.1.1 Currents in the primary limbs. ............................................................................................ 18
5.1.2 Currents in the secondary limbs. ......................................................................................... 18
5.2.1 Forces .................................................................................................................................. 19
5.2.2 Radial force ............................................................................................................................. 19
iii
5.2.3 AXIAL FORCE ...................................................................................................................... 20
6.conclusion……………………………………………………………………………….22
7.references………………………………………………………………………………………………………………….23
Appendix A ......................................................................................................................... 24
A.1Process of group work and version control ................................................................... 24
Meeting 1 ............................................................................................................................ 25
Meeting 2 ............................................................................................................................ 26
Meeting 3 ............................................................................................................................ 27
Meeting 4(final)................................................................................................................... 28
iv
List of symbols
v
1. Introduction
Almost all of our modern conveniences are electrically powered, thus the need for electricity has become
one of the most essential tool for living. The question that most of us ask ourselves today is that how does
the electricity that we consume distributed across the country? And the answer to that is simply based on
transformers. Transformers are generally devices with no internal moving parts referred to as being static,
these electric devices transfers energy from one circuit to another by means of electromagnetic induction
[1]. They are typically used because a change in voltage is needed and there are two main types of
transformers namely the power transformer and distribution transformer. Power transformers are used in
transmission networks with higher voltages for step-up and step-down applications, they are generally rated
above 200MVA whereas in the other hand distribution transformers are used for lower voltage distribution
networks for residential and small business consumption which are generally rated below 200MVA [2].
Our design problem was to design a three phase core-type distribution transformer using FEMM software
tool to understand the basic operation of a transformer under different internal and external loading effects
as described in the main body of this report. FEMM is an application which consist of several types of
programs to assist a user in solving electromagnetic problems of low frequency on two dimensional planer
and axisymmetric domains, this application also facilitates in solving problems which include linear and
nonlinear magneto-static, linear and nonlinear time harmonic, liner electromagnetic problems and steady
state heat flow problems [3].
FEMM software tool is suitable for obtaining measures such as magnetic field energy, hysteresis losses,
resistive losses, total current of the transformer, forces and other quantities. Obtaining these measurements
will help measure the transformers performance capability in meeting specifications and in being
competitive in today’s market environment. Our transformer was designed to be 11kV/400V step down
with a 30KVA power rating and is plane tank, the transformer’s frequency is 50Hz and is delta-star
configured with a clearance of not less than 14mm between adjacent windings. The operating temperature
of the transformer is 40° with a coefficient of 𝛼 = 0.00392/°𝐶 and a power factor of 0.8 lagging.
1
2. Magnetic Circuit Design Section (Lungelo Zindela)
i. Calculated the voltage turn from the given rated voltage via this formula:
𝐸𝑡 = 𝐾 × √𝑄 (1)
ii. From the above result maximum flux was determined via the following formula
𝐸𝑡
𝜙= (2)
4.44𝑓
iii. We chose a value in a given range for magnetic flux which was then used in determining the area
of the core section.
iv. The grass core area was then determined and then from the ratio of the gross core area to that of
the net area the diameter of the circumscribing circle was then obtained via the equation.
𝐴𝑔𝑖
𝑟𝑎𝑡𝑖𝑜 = 𝑑2
(3)
𝜋×
4
v. Then we chose a suitable value of the current density to calculate the area of the window.
103
𝐴𝑤 = 𝑄 × 3.33𝑓.𝐵.𝜌.𝐾𝑤.𝐴𝑖 (4)
vi. From the above value we determined the height and width of the window of the magnetic core
𝐻𝑤
𝑊𝑤
=2 (5)
vii. We then proceeded to the yoke section of the core by determining the area of yoke, yoke depth and
its height.
viii. And then we completed the core by calculating its overall dimensions using the previous values
calculated with the two following formula where (H) is the overall height and (D) overall width.
𝐷 = 𝑑 + 𝑊𝑤 (6)
𝐻 = 𝐻𝑤 + 2𝐻𝑦 (7)
2
2.2 The winding design procedure
This section presents steps taken in the design for the low voltage (LV) and High Voltage(HV) windings
of the transformer.
i. Firstly, we determined the phase and line voltages on the primary and secondary side of the
transformer taking note of the given transformer configuration.
iv. Then we selected the conductor for the LV winding in the table given.
ix. Worked out how many conductors can fit in the LV side from the length available
xiii. We then used table 7.4 for paper coved conductors to get ordinary covering and fine covering
xiv. The findings from the table facilitated in finding the length of the HV winding
xv. Hence clearance was determined which is suitable and above 30mm
3
xviii. Hence final clearance was obtained which was above the minimum value 19𝑚𝑚 > 14𝑚𝑚
Hence, using the above calculated values which are the overall dimension of the core and winding we
constructed our circuit model using FEMM software.
4
2.3.1 Magnetic flux density
The magnetic flux density is the amount of magnetic flux in a given area taken perpendicular to the field
direction. In the theoretical calculation a range between 1.1 𝑡𝑜 1.35𝑤𝑏/𝑚2 for flux density was given
in the design specifications and in our design we chose a value of
𝐵 = 1.1𝑤𝑏/𝑚2 (10)
This value is approximately equal to the flux density in the middle limb of the which ranges between 1.181
to 1.272𝑤𝑏/𝑚2 which confirms the expected value for our design and this is depicted in Figure 2. Since
the area of the core is constant the magnetic field is proportional to the flux density according to the
following equation
𝐵 = 𝜙𝐴 (11)
Hence an increase in the flux density causes an increase in the magnetic field, and the reason why the
magnetic flux density is concentrated in the middle limb is due to the fact that the field converges at the
center limb and diverges when it leaves the center limb creating a field imbalance in each limb as a result
the flux density will also vary as shown in the figure below.
Figure 2. The magnetic circuit showing the variation of the magnetic flux density in the core
5
2.3.2 Magnetizing Current
Magnetizing current is a current that flows in the primary winding when the primary voltage is
applied with the secondary unloaded [4]. When we unloaded the secondary we applied no current
(open circuit) to the LV side and introduced a phase shift of 120° in each currents in the limb and
adjusted the current in each limb in order to match with our chosen theoretical flux density of
1.1𝑤𝑏/𝑚2 in the center limb. We also alternated the signs of the current according to the right
hand rule where the currents entering the page are considered to be positive and negative when it
leaves the page, the calculation for each current in the limb is as follows
Since the magnetizing current is approximately equal to the current in HV side at no load then it
follows that
|𝐼𝑚 | = 𝐼𝐻𝑉 (12)
For HV: 1&2
𝐼𝐻𝑉 = ±0.0546𝐴
∴ 𝐼𝑚 = 0.0546𝐴
For HV:3&4
𝐼𝐻𝑉 = ±0.0546∠120°
For HV:5&6
𝐼𝐻𝑉 = ±0.0546∠ − 120°
The flow of current in the winding generates a magnetic field around a coil, thus an increase in the
field increases the magnetic flux density and the relationship between current and the flux density
if given by the following formula which shows that the current and flux density are directly
proportional.
𝐵𝐿
𝐼= (13)
𝑁×𝜇
the graph on the next side shows the variation of flux density across the core with the center of the it being
the highest which confirms where the flux density should be heights and with each core on the sides from
the center being approximately half of the center limb.
6
Figure 3. The graph showing the variation of the magnetic flux density across the core
7
3. Thermal Design (Ayanda Sibiya)
8
Steel, 1% Carbon- Volumetric heat capacity of 3 was used. Steel, 1% Carbon has good thermal properties.
Oil - Used to fill the windows and boundary space of the transformer. Thermal conductivities, 𝐾𝑥= 𝐾𝑦 =
0.12 was used.
Windings (HV and LV)- Thermal conductivity kx and ky of 0.12 were used. Heat Volume generation was
calculated using the losses and block volume from the magnetic circuit.
Winding to oil–This boundary was used for the heat transfer coefficient from winding to oil. The boundary
was labelled Winding to oil and given the following properties:
BC Type: Convection
h (heat transfer) W/m2K = 60
T0 (ambient air temperature) = 293k
The following heat flow distribution diagram that was obtained. The visible intensities of colour per the
density plot the maximum value of the temperature was found to be 293.1K, this value was within the 65°C
(338.5K) threshold set in the design specification sheet.
9
Figure 3: Graph of Temperature Vs Length across transformer
10
Figure 5: Graph of Temperature Vs Length across transformer after cooling
11
3.5 Calculations
For low voltage windings, from the magnetic design total losses are 0.000150322W and the block volume
is 0.00325586𝑚3.Volume heat generation of low voltage windings is given by:
𝑇𝑜𝑡𝑎𝑙 𝑙𝑜𝑠𝑠𝑒𝑠
𝑉𝑜𝑙𝑢𝑚𝑒 ℎ𝑒𝑎𝑡 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑖𝑜𝑛 =
𝐵𝑙𝑜𝑐𝑘 𝑣𝑜𝑙𝑢𝑚𝑒 𝑜𝑓 𝑙𝑣 𝑤𝑖𝑛𝑑𝑖𝑛𝑔𝑠
0.000150322 0.0462𝑊
= 0.00325586
= 𝑚3
For High voltage windings, total losses are 0.00872078 𝑊 and the block volume is 0.00555818𝑚3.
Volume heat generation of high voltage windings is given by:
𝑇𝑎𝑡𝑎𝑙 𝑙𝑜𝑠𝑠𝑒𝑠
𝑉𝑜𝑙𝑢𝑚𝑒 ℎ𝑒𝑎𝑡 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑖𝑜𝑛 =
𝐵𝑙𝑜𝑐𝑘 𝑣𝑜𝑙𝑢𝑚𝑒 𝑜𝑓 ℎ𝑣 𝑤𝑖𝑛𝑑𝑖𝑛𝑔𝑠
0.00872078 1.569𝑊
= =
0.00555818 𝑚3
3.6 Improvements
• In the core use laminated material to decrease Eddy current losses
• Use a suitable material for cooling down the heat generated of a transformer
• Proper insulation is need also in the windings to prevent core losses which also contributes
to the overall heat generated in the transformer
12
4 Insulation design (Simphiwe Dubazana)
The insulation design of a three-phase transformer consists of paper, pressboard and insulating oil.
Insulating oil is one of the most important components within a transformer that acts as both an electrical
insulator and coolant to dissipate heat losses. This oil is seen in 11KV or higher voltage transformer core is
placed. It is not required in low voltage transformers because the heat dissipation in such transformers is
very low. Insulating oil is obtained by fractional distillation and subsequent treatment of crude petroleum
[5]. The insulator design prevents the short circuiting which may occur between the High Voltage and Low
Voltage winding in the transformer. It also decreases the heat transfer between the layers of insulator is
increased to prevent those heat losses during the operation of the transformer. Insulating also have the
important role on protecting short circuiting design by counter acting the axial and radial forces that are
produced from the high current flowing on the windings. At higher voltage and power ratings, shell form
transformers tend to be more prevalent the insulator can be used to prevent these effect [6].
• A magnetic design geometry was exported and imported to the new file which under electrostatic
problem to deal with the effect of insulation.
• To complete the design geometry, a paper and the pressboard with an insulation thickness of
5.21mm was placed between the High voltage and Low voltage windings.
• Under the conductor the Low voltage and High voltage windings were defined with different
voltages.
• The conversion of the line voltage that was given in the design specification to phase voltage before
it was loaded in the transformer winding thickness which is defined under conductor. The
transformer design was a three-phase star-delta and the voltage phase change is 120 degrees apart
from each other.
13
𝑉𝑙𝑖𝑛𝑒
𝑉𝑝ℎ𝑎𝑠𝑒 = 𝑓𝑜𝑟 𝑎 𝑠𝑡𝑎𝑟 𝑐𝑜𝑛𝑛𝑒𝑐𝑡𝑖𝑜𝑛 (15)
√3
HV (high voltage)
LV (low voltage)
Phase 1
For HV 𝑉𝑝ℎ𝑎𝑠𝑒1 = 11000𝑉
400
For LV 𝑉𝑝ℎ𝑎𝑠𝑒1 = = 230.94𝑉
√3
Phase 2
For HV 𝑉𝑝ℎ𝑎𝑠𝑒2 = −5500 + 𝑖9526.28𝑉
For LV 𝑉𝑝ℎ𝑎𝑠𝑒2 = −115.47 + 𝑖200𝑉
Phase 3
For HV 𝑉𝑝ℎ𝑎𝑠𝑒3 = −5500 − 𝑖9526.28𝑉
For LV 𝑉𝑝ℎ𝑎𝑠𝑒3 = −115.49 − 𝑖200𝑉
• The nodes were defined in all the windings of the transformer and material of the transformer, so
the problem will be solved.
• The transformer oil was placed inside the window and outside the transformer core.
• The outer boundary was defined to solve the problem inside the boundary.
• The nodes for the paper and pressboard insulation was also placed.
• A mesh was generated to check if all the nodes were labelled and running using mirror to analyze
the circuit.
The circuit was simulated to obtain the result and check the difference in the intensity field if the paper was
placed between the High voltage and Low voltage windings and if the pressboard was placed. To meet the
electric field strength of 5.5KV/mm as it per design specifications.
The operation of the transformer increases the temperature in the transformer, the paper and the pressboard
are used to reduce and prevent the heat loses and the short circuiting in the transformer. The transformer
oil is used as a coolant and prevent dissipation of heat in the transformer. When the transformer is
14
being cooled using transformer oil there will always be a formation of moisture inside and it is
when the paper and the pressboard is needed to absorb that vapor and reduces failure.
V is the voltage
d is the distance between windings
The figure below that shows the field intensity field in the circuit
15
Figure 7: the graph of the paper as an insulator
The is a noticeable difference between the two graphs. In the first graph the is the slightly decrease in the
field intensity of 2e V/mm because the paper was used as an insulator. In the second graph the pressboard
16
was used as an insulator, the is a noticeable decrease in the field intensity compared to that of the paper.
The pressboard is the most suitable insulator for a transformer to function well as seen on the two graphs.
Although the paper is not expensive as the pressboard, but the pressboard is expensive due to its properties
which are better than for a paper.
4.4 Improvements
Insulation design can be improved by increasing the layers of the insulator in the transformer. This will
help to reduce the heat loss in the Thermal design and prevent furthermore in the short circuit design.
Although oil is important in the transformer, but it help to realize the heats faster in the transformer, so the
will be no pressure of heat in the transformer. This will decrease the field intensity to became smaller
because there will be an increase in the permittivity of the material.
17
5.1.1 Currents in the primary limbs.
Theoretical calculated primary current is 𝐼𝑝𝑟𝑖𝑚𝑎𝑟𝑦 = 0.91 𝐴
The current in primary side is left positive and current in the secondary side is multiplied by a
negative sign because HV currents and LV currents must propagate in the same direction. After
calculating the currents, they were then inserted in the primary and secondary limbs using FEMM.
The reason of doing these calculations is to make a short circuit which results in creating a
mechanical stress.
5.2 RESULTS
𝑭𝒂 (𝒙) = 𝑩𝒓 × 𝑰𝒙 = 𝟎. 𝟎𝟖𝟓 𝑵
The graph of the flux density and the graph of the force is the same this is because force is directly
proportional to the flux density and also directly proportional to the current squared, Flemings left
hand rule is used to determine the direction of the force.
5.2.1 Forces
Short circuit events generate high current conditions in transformer windings. These currents in turn
induce excessive forces in a transformer. Electromagnetic forces are important considerations in the
design, manufacturing and operation of transformers. These forces can be subdivided into axial and radial
forces each with unique considerations and mitigating measures.
The generation of an electromagnetic field inside the transformer is therefore intrinsic to transformer
operation. This electromagnetic field will however lead to the generation of forces inside the transformer
windings stipulated by the laws of magnetism, Faradays law of induction and Lenz's law of
electromagnetic force
The flux at mid winding height is for the most part parallel to the winding height. According to the left
hand rule, the resulting force therefore acts perpendicular to the winding height. For windings on the
inside of the main flux field (situated between primary and secondary windings) the force acts inward,
and for outside windings, outward. Forces acting on the inside windings result in a compressive stress
whereas on the outer winding this force leads to a tensil
19
Figure 10: Flemings Left hand rule
Figure 11: Graph of Bt which shows the components of the flux density
Axial forces are generated parallel with the winding height. Due to the pattern of the magnetic leakage
field, the windings experience opposing forces at the winding ends, leading to compressive forces. Axial
force is generated when the transformer's magnetic field lines are radially orientated. The local force
generation accumulates toward the middle of the windings resulting in a maximum occurring force at
20
mid-winding height. This force is compressive towards the winding center as the circulation direction of
the magnetic field leads to opposing forces at each end of the winding.
Winding displacement from the center line result in excessive axial forces. This is due to the difference in
the ampere-turns (i.e. mmf) distribution along the winding heights resulting in more pronounced bending
of the field lines at the point of missing ampere-turns or where the displacement occurs.
Figure 12: Graph of Bn which shows the components of the flux density
21
6 Conclusion
The implementation of transformer design was done successfully using FEMM software tool, the analysis
of the result played a vital role in understanding the operation of a real transformer which is also governed
by the electromagnetic induction effect observed that when designing a transformer several factors are taken
into account such as the geometry, winding size, insulation material used, depth of core, insulation material
size, thermal stress, mechanical stresses etc.
All these aspects of a transformer mentioned above were critical in considering when designing a
transformer and these measurements are all driven by theoretical design calculations, however the results
obtained in our theoretical calculations are not exactly the same as the one analyzed using FEMM due to
many assumptions done during our calculations and the fact that practical measurements will always have
some slight different to some extent when compared to theoretical measurements and FEMM software is
consider to be one of the best tool in simulating real life electrical or mechanical devices.
22
References
1.Mack, J. E., 2006. Distribution Transformer. In: T. Shoemaker, ed. Lineman's and Cableman's
Handbook. New York: McGraw-Hill, pp. 15-22.
5.H.J.Macbride, 2005. Transformers,Basics, Maintenance and Diagnostics, New York: U.S. Department of
the Interior.
6.John W, K. G., 2012. Hydroelectric Reserch and Technical Services. Interior, Bureau of Reclamation,
II(10), p. 12.
23
Appendix A
Make individual
Deliver work on time contribution to the group
Generate
solution
Execute optimal solution
Effective
communication
between group
members
24
Meeting 1
Date: 08/03/19
Time: 19:30 -23:00
Place: Main Library
• Review on what are transformers and discussed about the basic principles governing it.
• Each member was allocated a section in the design calculation
• Lungelo & Nkosinathi were allocated to do the core design section
• Ayanda & Simphiwe were allocated to do the winding and insulation design section.
Attendee Sheet
By signing this attendee sheet, you affirm that you have participated in the stated meeting and received and
reviewed the materials presented to you. Meeting minutes will be captured, acted upon and then reviewed
as part of the next review meeting.
Group Members
25
Meeting 2
Date: 29/03/19
Time: 19:30-23:30
Place: Main Library
Attendee Sheet
By signing this attendee sheet, you affirm that you have participated in the stated meeting and received and
reviewed the materials presented to you. Meeting minutes will be captured, acted upon and then reviewed
as part of the next review meeting.
Group Members
26
Meeting 3
Date: 06/05/18
Time: 08:30 – 12:30
Place: Main Library
Attendee Sheet
By signing this attendee sheet, you affirm that you have participated in the stated meeting and received and
reviewed the materials presented to you. Meeting minutes will be captured, acted upon and then reviewed
as part of the next review meeting.
Group Members
27
Meeting 4(final)
Date: 04/05/19
Time: 08:30 – 13:00
Place: Main Library
• Review on our last meeting and discuss on improvements based on the presentation
• Finalize our FEMM design for final presentation
• Allocate task to be done on the next presentation
Attendee Sheet
By signing this attendee sheet, you affirm that you have participated in the stated meeting and received and
reviewed the materials presented to you. Meeting minutes will be captured, acted upon and then reviewed
as part of the next review meeting.
Group Members
28