You are on page 1of 1

TITANIUM MIX CONCRETE SDN BHD (1228065-U)

No 33 GF, Jalan 1/2, Taman Sri Jaromas, 42610 Jenjarom, Selangor.


Tel/Fax: 03-3191 5788 Email: titaniummix17@gmail.com

CONCRETE CUBE TEST REPORT

REPORT NO / D.O NO : 1017384 Date : 14/12/2021

PLANT : BANDAR MAHKOTA BANTING

TESTED FOR : LOO SEK CHOY PLUMBING CONSTRUCTION SDN BHD

PROJECT : P4D WATER TANK AT PNB SG MANGGIS

LOCATION OF
STRUCTURE : TRIAL MIX

GRADE : G35N

SLUMP : 90 mm

Cement Ordinary Portland Cement Fine Agg Washed Mining Sand


MATERIAL TYPE
Admix RWD/ADVA323 Coarse Agg 20mm Graded Type

Method Of Test : BS EN 12390-3:2002 "Compressive strength of test specimens" "

Cube Date Date Age Size Weight Density Max Load Compressive
Ref. Cast Tested Days (mm) (Kg) (Kg/m3) (KN) Strength
(N/mm2)

1017384 16/11/2021 14/12/2021 28 150X150X150 8.20 2430 1136 50.5

1017384 16/11/2021 14/12/2021 28 150X150X150 8.20 2430 1059 47.1

1017384 16/11/2021 14/12/2021 28 150X150X150 8.10 2400 965 42.9

Average : 46.8
NOTES:
1. This Report is not valid unless signed and bears our official date stamp.
2. This TEST REPORT cannot be reproduced or published in any form whatsoever or the information contained herein be
used in any form of publication or advertisement without the written permission of TITANIUM MIX CONCRETE SDN BHD

Witnessed by Acknowledged receipt For TITANIUM MIX CONCRETE SDN BHD

OFFICIAL STAMP AND DATE.


Chop & Sign Chop & Sign Authorised Signature

You might also like