SETTING PROTEKSI PLTG BORANG 60 MW

35 MW
35 MW
11.5 kV
G1 11.5 kV G2

Switchgear 1 OUT GT 2 Switchgear 2


OUT GT 1
11.5 kV, 40 kA 11.5 kV, 40 kA

INC AUX INC AUX INC AUX INC AUX


TR-1600 #1 2500 kVA TR-2500 #1 TR-2500 #2 TR-1600 #2

2500 kVA

1600 kVA
1600 kVA

TX-2

TX-2

TX-3
TX-1

BUS TIE

OUT AUX OUT AUX


TR-2500 #1 AUX AUX OUT AUX
TR-1600 #1
LV MDB-1 Switchgear 6.6 kV TR-2500 #2 TR-1600 #2 LV MDB-2
TRAFO-1 TRAFO-2
0.4 kV 0.4 kV
60 MVA 80 MVA

M M
Aux 1 800 kW 800 kW Aux 2
Compressor OUT MAINTRAFO 1 OUT MAINTRAFO 2

BUS 1, 150 kV

BUS 2, 150 kV

Gambar 1. SLD PLTG Borang 60 MW

▪ ALL SETTING PROTEKSI PLTG BORANG

TIME TIME
NAMA MANUFACTURE CT/PT TYPE KURVA RELE SET
DIAL (s) DELAY (s)
INVERS 51 1.21 0.7 -
PHASA
Beckwith Electric (M- - 50 - - -
OUT GT 1 4000/1
3425) - 51G - - -
GROUND
- 50G - - -
INVERS 51 1.21 0.7 -
PHASA
Beckwith Electric (M- - 50 - - -
OUT GT 2 4000/1
3425) - 51G - - -
GROUND
- 50G - - -
DEFINITE 51 1.3 3.5
PHASA
INC AUX TR- DEFINITE 50 4.4 - 3
GE (MIF II) 150/5
2500 #1 DEFINITE 51G 0.25 1 -
GROUND
DEFINITE 50G 0.5 - 0.3
DEFINITE 51 1.3 3.5 -
PHASA
INC AUX TR- DEFINITE 50 4.4 - 3
GE (MIF II) 150/5
2500 #2 DEFINITE 51G 0.25 1 -
GROUND
DEFINITE 50G 0.5 - 0.3
DEFINITE 51 0.8 1 -
INC AUX TR- PHASA
GE (MIF II) 100/5 DEFINITE 50 1.6 - 0.5
1600 #1
GROUND DEFINITE 51G 0.24 0.5 -
SETTING PROTEKSI PLTG BORANG 60 MW
TIME TIME
NAMA MANUFACTURE CT/PT TYPE KURVA RELE SET
DIAL (s) DELAY (s)
DEFINITE 50G 0.5 - 0.3
DEFINITE 51 0.8 1 -
PHASA
INC AUX TR- DEFINITE 50 1.6 - 0.5
GE (MIF II) 100/5
1600 #2 DEFINITE 51G 0.24 0.5 -
GROUND
DEFINITE 50G 0.5 - 0.3
DEFINITE 51 1.2 3 -
PHASA
OUT AUX TR- DEFINITE 50 3.8 - 3
GE (MIF II) 300/5
2500 #1 DEFINITE 51G 0.44 1 -
GROUND
DEFINITE 50G 0.9 - 0.5
DEFINITE 51 1.2 3 -
PHASA
OUT AUX TR DEFINITE 50 3.8 - 3
GE (MIF II) 300/5
2500 #2 DEFINITE 51G 0.44 1 -
GROUND
DEFINITE 50G 0.9 - 0.5
IEC CURVE
51 0.92 1 -
PHASA A
DEFINITE 50 1.85 - 0.5
2500/1
IEC CURVE
51G 0.28 0.5 -
OUT AUX TR- GROUND A
GE (F650)
1600 #1 DEFINITE 50G 0.6 - 0.3
OVER
DEFINITE 59 120 - 10
VOLTAGE
400/110 V
UNDER
DEFNITE 27 50 V - 10
VOLTAGE
IEC CURVE
51 0.92 1 -
PHASA A
DEFINITE 50 1.85 - 0.5
2500/1
IEC CURVE
51G 0.28 0.5 -
OUT AUX TR- GROUND A
GE (F650)
1600 #2 DEFINITE 50G 0.6 - 0.3
OVER
DEFINITE 59 120 - 10
VOLTAGE
400/110 V
UNDER
DEFNITE 27 50 V - 10
VOLTAGE
NORMAL
51 0.5 0.13 -
PHASA INVERS
DEFINITE 50 0.8 - 0.8
ABB (REF 610) 300/5
NORMAL
51G 0.16 0.18 -
OUT MAIN GROUND INVERS
TRAFO 1 DEFINITE 50G 0.33 - 0.8
UVER 51.5
- DEFINITE 81-O - 2
FREQUENSI Hz
GE (SR745)
UNDER 48.5
- DEFINITE 81-U - 2
FREQUENSI Hz
NORMAL
51 0.5 0.13 -
PHASA INVERS
DEFINITE 50 0.8 - 0.8
ABB (REF 610) 300/5
NORMAL
51G 0.16 0.18 -
OUT MAIN GROUND INVERS
TRAFO 2 DEFINITE 50G 0.33 - 0.8
UVER 51.5
- DEFINITE 81-O - 2
FREQUENSI Hz
GE (SR745)
UNDER 48.5
- DEFINITE 81-U - 2
FREQUENSI Hz
BUS TIE ABB (REF 610) 2500/5 PHASA DEFINITE 51 0.5 1 -
SETTING PROTEKSI PLTG BORANG 60 MW
TIME TIME
NAMA MANUFACTURE CT/PT TYPE KURVA RELE SET
DIAL (s) DELAY (s)
DEFINITE 50 0.9 - 0.5
DEFINITE 51G 20 1 -
GROUND
DEFINITE 50G 40 - 0.5

▪ GENERATOR PROTECTION

No Protection Relay Relay Setting


59 N #1 Pickup : 5,8 Volt
1
Neutral Overvolatage Delay : 250 cycles
59 N #2 Pickup : 5,8 Volt
2
Neutral Overvolatage Delay : 500 cycles
59 #1 Pickup : 138 Volt
3
Phase Overvolatage Delay : 200 cycles
59 #2 Pickup : 159 Volt
4
Phase Overvolatage Delay : 50 cycles
27 #1 Pickup : 92 Volt
5
Phase Undervolatage Delay : 150 cycles
81 #2 Pickup : 48 Hz
6
Under Frequency Delay : 250 cycles
81 #4 Pickup : 52 Hz
7
Over Frequency Delay : 250 cycles
50/27 Pickup : 0,4 A
Inadvertent Energizing Volt control : 81 V
8
Pickup delay : 200
d.0 delay : 300
Pickup : -0,004 PU
9 32 #1, Directional Power
Delay : 500 cycles
40 #1 Diameter : 82 ohm
10 Loss Of Field Offset : -11,5 ohm
Delay : 4 cycles
40 #2 Diameter : 82 ohm
11 Loss Of Field Offset : -11,5 ohm
Delay : 25 cycles
24 #1 Pickup : 120 %
12
Volts/Hz Delay : 300 cycles
24 #2 Pickup : 110 %
13
Volts/Hz Delay : 3000 cycles
46 Pickup : 15 %
14
Neg. Sequence Current Delay : 50 cycles
15 51 V Pickup : 1,21 A (In)
SETTING PROTEKSI PLTG BORANG 60 MW

No Protection Relay Relay Setting


Overcurent Curve : INV
Time dial : 0,7
87 Pickup : 0,05 A
16 Differential current Slope : 10 %
Time dial : 1 cycles
25 Phase limit : 10˚
Synhro check Upper V limit : 126,5
17 Lower V limit : 58 V
Delta V : 11,5 V
Delta F : 0,25 Hz

50 BF Pickup : 0,08 A
18
Breaker Failure Delay : 9 cycles

▪ MAINTRAFO PROTECTION

BREAKER FAILURE PROCTECION SETTING


CT Ratio 300/5
CBFP I> 0.1 x In
td
Time Delay Set 200 ms
>
DIFFERENTIAL SETTING
CT Primer 300/5
CT Sekunder 4000/5
Vector Group YnD1
Pickup 0.3 x In
Slope 1 30%
Slope 2 70%
Operating Time 20 ms