RFI-E-069
QRO061
Initiated By:
Martín Zúñiga Bello
RFI-E-069
Walbridge de México
Question:
Originally in the plans of the grounding system, in the area of transformers only one ground wire is
indicated in the low voltage cabinets, which is necessary to install an additional ground wire in the MV
(medium voltage) cabinet for the feeders , because in transformers it has the ground connection screw
and in engineering it marks the wiring of the 3 phases + ground; It is recommended to install an
Signature Attachments: x
Suggestion
Comments: