GW532A Chiller
Controller

Manufacturer Instruction Manual

Please read the in manual carefully before installing the controller!

April 18, 2019


Software Version : X1.GW532A.TY.F01M V100B7
All rights reserved. Any reproduction of the manual will be prosecuted.
X1.GW532A.TY.F01M.Manufacturer Instruction Manual.

Table of contents

1 Instructions.............................................................................................................................................................................1
2 Specifications.........................................................................................................................................................................1
3 Panel Diagram.......................................................................................................................................................................1
4 First Power-on....................................................................................................................................................................... 1
5 Common Screens................................................................................................................................................................. 2
5.1 Main Screen.................................................................................................................................................................. 2
5.2 Alarm Screen.................................................................................................................................................................2
6 Common Operation.............................................................................................................................................................. 2
6.1 Quick Modification of Setting Temperature.................................................................................................................2
6.2 Query/Reset Fault......................................................................................................................................................... 2
7 Function Menu.......................................................................................................................................................................3
8 Parameter Operation............................................................................................................................................................4
9 User Parameters Table........................................................................................................................................................ 4
10 Manufacturer Menu............................................................................................................................................................ 5
10.1 Procedures of Entering Manufacturer Menu.............................................................................................................. 5
10.2 Details of Manufacturer Menu................................................................................................................................... 5
10.3 Manufacturer Debugging............................................................................................................................................5
10.4 Configuration Guide................................................................................................................................................... 6
11 Fault List............................................................................................................................................................................... 7
12 Control................................................................................................................................................................................ 11
12.1 Logic of compressor.......................................................................................................................................... 11
12.2 Logic of pump freeze protection.................................................................................................................... 11
13 Manufacturer Parameters Table.....................................................................................................................................11
14 Electrical Connection Diagram.......................................................................................................................................15
15 Installation Dimensions....................................................................................................................................................15
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 1/15

1 Instructions

Dear Customer:
Thank you for choosing PUNP products!
For your convenience, please read the instructions carefully and follow the steps of the Manual.

2 Specifications
Specification Specification
No. Description No. Description
Parameter Parameter
Rated input
1 220-250VAC 50/60HZ 6 Switch Output 5 relays 250VAC 2A
voltage
Temperature Relay load D01:annunciator
2 -40~100℃ 7
Range type D02-D05: contactor or valve
Measurement
3 0.1℃@25℃ 8 Switch Input 12 passive signal inputs
Accuracy
Working -10℃~60℃,≤85%RH
4 9 Analog Input 1 NTC temperature sensor
Environment non-condensation
Storage -20℃~70℃,≤85%RH
5 10 Current Input 4 ways of current (0.3~35A)
Environment non-condensation

3 Panel Diagram

4 First Power-on
The controller needs to be configured when powered on for the first time. Please refer to 10.4 Configuration
guide for specific operation.
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 2/15

5 Common Screens
Commonly used screens include the main screen and the alarm screen.
5.1 Main Screen 5.2 Alarm Screen
The system will enter the main screen after In case of unit failure, the alarm screen is as follows:
countdown, which displays as follows:

Press + during down count and enter


Press + for 3 seconds on the main screen
can change the language quickly. Language screen, press or to change

current Language, press to quit without

saving, press to save and quit.

6 Common Operation

6.1 Quick Modification of Setting Temperature

If the user parameter [Lock T.set] is set to "No", the setting temperature can be modified directly in the
main screen, with operation details as follows:

Note: the setting temperature can also be modified in the user parameters.

6.2 Query/Reset Fault

In case of fault, the alarm screen will automatically pop up. The operation details of query and reset faults
are as follows:
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 3/15

7 Function Menu

Press the button on the main screen to enter the Function Menu, which includes five items as the
table below:
No. Menu Item Funtion Remark
For number of user parameters and their
User
1 To display user parameters implications, please refer to: 9 User
Settings
Parameters Table.
To display the current operating status Current value is not displayed when current
2 Unit Status
of the unit module is not used.
3 History List Allowing the query of the last 10 faults Press for 2s to clear the fault history.
Comp run To display the cumulative operation
4
time time of the compressor
5 Version To check the current software version
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 4/15

8 Parameter Operation

For the modification operation of parameter value, the user’s modification of setting temperature will be
described as an example.

9 User Parameters Table

The implication of each parameter in the user parameters is listed in the following table:
No. Parameter Factory Setting Range Remark
Name Default
Yes: the set temperature can not be modified
on the main screen when locked.
1 Lock T.set No Yes ~ No
No: the set temperature can be modified on
the main screen.
Setting range is limited by the manufacturer
parameters [T.setpoint max], [T.setpoint
[T.setpoint min]
2 T.setpoint 12.0℃ min].
~[ T.setpoint max]
(When the [TEMP Unit] is set “Fahrenheit”, the
parameter is not displayed.)
Setting range is limited by the manufacturer
[T.setpoint min] parameters [T.setpoint max], [T.setpoint min].
3 T.setpoint 53.6 ℉
~[ T.setpoint max] (When the [TEMP Unit] is set “Celsius”, the
parameter is not displayed.)
4 TEMP Unit Celsius Celsius;Fahrenheit
5 Contrast 32 20~44 Adjust the LCD contrast
Local: the unit can only start and stop locally.
Local + Remote: the start and stop of the unit
Local / Local +
6 On/Off type Local can be controlled both locally and remotely.
Remote / Remote
Remote: the unit can only start and stop
remotely.
7 Backlight On 0 0~255 minute(s) 0: backlight is not turned off.
8 Language Chinese Chinese~English Select the display language.
Select the Comp to run. if select one comp the
1#Comp/2#Comp/Two
9 Comp Select Two Comp other does not work. The parameter is not
Comp
listed for the single comp machine.
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 5/15

10 Manufacturer Menu

Press + in the main screen to enter the Enter Password screen and enter the correct
manufacturer password (default 4561, which is recommended to change). Then enter the Manufacturer Function
Menu, which includes five items.
10.1 Procedures of Entering Manufacturer Menu

10.2 Details of Manufacturer Menu


The details and function of manufacturer menu are shown in the following table:
No. Parameter Item Function Remark s
To set the parameters commonly Refer to 13 Manufacture
1 Manuf. setting
used by the manufacturer Parameters for specific parameters.
To debug the abnormal operation Not available during the unit
2 Manuf. debug
of each electrical part of the unit operation.
Not available during the unit
Commonly used parameters of operation.
3 Config guide
config the unit The screen will pop up when
powered on for the first time.
Refer to 10.5 Manufacture
For initialize all parameters of the
4 Initialize Parameters for the initial values of
machine.
the parameters.
To set the password to enter The default value is 4561, which is
5 Password Set
manufacturer menu. recommended to change.

Note: Press + in the manufacturer menu for 2 seconds can reset the accumulative operation
time of the compressor.

10.3 Manufacturer Debugging

Manufacturer debugging is mainly used to test whether the operation of each electrical part of the unit is
normal, which is not available when the unit is under operation.
Method: to determine whether the unit is normal by testing three-phase power input, seven alarm inputs (10
alarm inputs for two compressors) and 5 relay outputs. For alarm input, it only displays the test result. If the
result is normal the wiring is good and parameter settings are correct; if it alarms, with flashing display of alarm
characters, then make sure whether the external wiring is good and the parameter settings are consistent.
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 6/15

10.4 Configuration Guide

Configure the common parameters of the machine. For the number of parameters of configuration guide
and the significance, please refer to 13 Manufacturer Parameters Table. Access is not available during the unit
operation.
Refer to the Parameter Operation for specific configuration method. The Configuration guide screen will pop
up when powered on for the first time. And if you click “Cancel” operation without configuring at this point, the
Configuration guide screen will still pop up when powered on next time. Once you have entered the
Configuration guide, the Configuration guide screen will not pop up when powered on and you can only enter the
Configuration guide through the Manufacturer Menu.
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 7/15

11 Fault List

Fault Description Test Conditions Troubleshooting Solution


Test when the compressor button
1#Comp.P high High pressure of compressor1
has pressed
If the [LP detect dly] is 0, test when Check if the input is consistent with
the compressor button has pressed; the switch setting.
1#Comp.P low Low pressure of compressor1
If the [LP detect dly] is not 0, then
compressor1 runs the test.
1#Comp Stop compressor1 only Check if the input is consistent with
The compressor1 overload
overload without affect other the switch setting.
The current of compressor1 is equipments to work. [Note1] Check if the rated current of
1#Comp.I high
too high compressor1 is input is reasonable.
Compressor1 runs the test.
The current of compressor1 is Check if the measure tool of the
1#Comp.I low
too low compressor1 current is connect.
The vent temperature of Check if the input is consistent with
1#T.Vent high
compressor1 is too high the switch setting.
Test when the compressor button
2#Comp.P high High pressure of compressor2
has pressed
If the [LP detect dly] is 0, test when Check if the input is consistent with
the compressor button has pressed; the switch setting.
2#Comp.P low Low pressure of compressor2
If the [LP detect dly] is not 0, then
compressor2 runs the test.
2#Comp Stop compressor2 only Check if the input is consistent with
The compressor2 overload
overload without affect other the switch setting.
The current of compressor2 is equipments to work. [Note2] Check if the rated current of
2#Comp.I high
too high compressor2 is input is reasonable.
Compressor2 runs the test.
The current of compressor2 is Check if the measure tool of the
2#Comp.I low
too low compressor2 current is connect.
The vent temperature of Check if the input is consistent with
2#T.Vent high
compressor2 is too high the switch setting.
Stop the compressor and
Check if the Liquid temperature is
The liquid temperature is too delay to stop the cool pump,
Temp.low AL Test after cold pump starts lower than the set temperature of
low and do not stop the cold
Liquid protection.
pump.
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 8/15
Check if the Liquid temperature is
The liquid temperature is Alarm only without affect
T.high warn higher than the set temperature of
higher than the warn value. other equipments to work.
Liquid warn.
If the [Temp.high AL] is set
“Pump keep”,Stop the
compressor and delay to
Check if the Liquid temperature is
The liquid temperature is too stop the cool pump, and do
Temp.high AL higher than the set temperature of
high not stop the cold pump;
Liquid protection.
If the [Temp.high AL] is set
“Pump stop”, Stop the unit in
case of fault.
Check if the antifreeze input is
Anti-freez.AL Antifreeze alarm
consistent with the switch setting.
Stop all the compressor and
The liquid temperature sensor
Probe break Power on to test cool pump, and do not stop
is break Check if the temperature probe is in
the cold pump.
The liquid temperature sensor proper contact.
Probe short
is short
Cool fan overld Check if the fan1 overload input is
The cool pump or fan overload
[Note3] consistent with the switch setting.
The current of cool pump or Stop compressor1 and cool Check if the rated current of cool is
Cool.I high AL Test after Cool pump starts
Fan is too high pump or fan only input is reasonable.
The current of cool pump or Check if the measure tool of the cool
Cool.I low AL
Fan is too low current is connect.
Test after the cool pump starts for Stop compressor1 and cool Check if the cool water flow input is
Cool W.flow AL Lack of cool water flow
[Cool on delay] time pump or fan only consistent with the switch setting.
If the [Lack of water] is set
“Pump keep”, Stop
compressor and cool pump
Test after the cold pump starts for Check if the cold water flow input is
Cold W.flow AL Lack of cold water flow in case of fault.
[Pump on delay] time consistent with the switch setting.
If the [Lack of water] is set
“Pump stop”, Stop the unit in
case of fault.
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 9/15
Cold Pump Check if the cold pump overload
Overld The cold pump overload input is consistent with the switch
[Note3] setting.
The current of cold pump is too Test after cold pump starts Stop the unit Check if the rated current of cold is
Pump.I high AL
high input is reasonable.
The current of cold pump is too Check if the measure tool of the cold
Pump.I low AL
low current is connect.
Check if there is default phase or
The three-phase power input is
Phase AL Power on to test Stop the unit anti-phase in the three-phase power
alarm
input and if the switch is correct.
If the [Low water lv.] is set
“Pump keep”, Stop
compressor and cool pump Check if the water level input is
Water lv. AL The water level is low Power on to test
in case of fault. consistent with the switch setting.
If the [Low water lv.] is set
“Pump stop”, Stop the unit in
case of fault.
The total time of compressor The unit cannot start once stops (the accumulative operation time of
Need Maintain Test after cold pump starts
run over the allow value compressor exceeds the set value).
1#Comp Oil Low Stop the compressor and
delay to stop the cool pump, Check if the comp oil level input is
The comp. oil level is low Compressor1 runs the test.
2#Comp Oil Low and do not stop the cold consistent with the switch setting.
pump.

[Note 1]: In case of "1#Comp.P low " fault, if [LP stop pump] is not zero, the troubleshooting program is: to immediately stop all compressors and cool pump, delay the
[LP stop pump] and stop the cold pump. If [LP stop pump] is zero, then the troubleshooting program is: to only stop compressor1 without affect other equipments to
work.

[Note 2]: In case of "2#Comp.P low " fault, if [LP stop pump] is not zero, the troubleshooting program is: to immediately stop all compressors and cool pump, delay the
[LP stop pump] and stop the cold pump. If [LP stop pump] is zero, then the troubleshooting program is: to only stop compressor2 without affect other equipments to
work.
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 10/15

[Note3]:
[Machine type] the screen real display when Cold Pump overload the screen real display when Cool Pump overload
AIR-WATER Cold Pump Overld Cool Fan Overld
W-W SYS. Cold Pump Overld Cool Pump Overld
AIR-AIR Cold Fan Overld Cool Fan Overld
WATER-AIR Cold Fan Overld Cool Pump Overld
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 11/15

12 Control

12.1 Logic of compressor


Double compressor but select only one / Single compressor:
The heating process, the compressor ON when PV ≥SV + ADD.
The cooling process, the compressor OFF when PV < SV – SUB
Double compressors:
a) If [Unload offset] is not 0
The heating process, one compressor ON when PV> SV and two compressors ON when PV≥ SV
+ ADD.
The cooling process, if two compressors ON currently, one compressor OFF when PV < SV and
two compressors OFF when PV < SV - SUB.If compressor ON currently, the compressor OFF when PV
<SV-SUB.
b) If [Unload offset] is 0
The heating process, one compressor ON when PV> = SV + ADD; after the time of [Capacity ctrl], if PV
≥ SV + ADD remains, two compressors ON.
The cooling process, the compressor OFF when PV <SV.
Note: PV: The liquid temperature SV: set temperature
ADD: load temperature difference SUB: unload temperature difference

12.2 Logic of pump freeze protection


a) When [T.freeze prot] = “forbid”, there is no pump freeze protection.
b) Otherwise under the idle state:
if SV ≤ [T.freeze prot], the pump opens;
if SV ≥ [T.freeze prot] + 2, the pump will close after 10 seconds.

13 Manufacturer Parameters Table


Parameters set by the manufacturer and parameter meanings are listed as follows: ("*" is for parameters of
the configuration guide)
Setting Name of Factory
Setting Range Remark
Item Parameter Default
Forbid: the compressor is allowed to ON only when
press the compressor button;
*One-Key start Forbid Forbid ~ Use
Used: the compressor allows ON when press the
pump button.
Use: the unit starts automatically when powered on;
Forbid: the unit doesn’t start automatically when
Auto start up Forbid Forbid ~ Use powered on;
When the user parameter [On/Off type] is set to
be"Remote", the electrical auto start is invalid.
Keep when mute: press the “alarm output” parameter
Keep when
Keep to take
mute;
Alarm output when action once a fault occurs;
Stop when
mute Stop when mute: press the “alarm output” parameter
mute
Func. to take action in case of no fault after silencing.
Setting N.O: the alarm relay is ON in case of faults;
Alarm type N.O N.O~N.C
N.C: the alarm relay is OFF in case of faults.
Water Water switch; Water switch: DI5 input for water level detection
DI5 function
switch Vent1 temp Vent1 temp: DI5 input for Vent1 temperature detection
Phase switch; Phase switch: DI9 input for phase sequence detection
Cool W.flow Cool W.flow: DI9 input for cool water flow detection
Phase
DI9 function Vent2 temp; Vent2 temp: DI9 input for Vent2 temperature detection
switch
2#Comp Oil 2#Comp Oil level: DI9 input for 2#comp oil level
LVL detection
Pump stop: stop the cold pump in case of low water
Pump Pump stop ~ level fault;
*Low water lv.
stop Pump keep Pump keep: do not stop the cold pump in case of low
water level fault.
*Lack of water Pump Pump stop ~ Pump stop: stop the cold pump in case of cold water
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 12/15

stop Pump keep flow fault;


Pump keep: do not stop the cold pump in case of cold
water flow fault.
*Current Use: there is a current detection module;
Use Forbid ~ Use
detect Forbid: no current detection module
*1#Comp.I 0A: do not detect the current fault.
0.3A 0~35.0A
rating When [Current detect] is set “Forbid”, those parameter
*2#Comp.I is not displayed.
0.3A 0~35.0A
rating (if the rating current of Comp or Pump is lower 1A,
*Pump. I rating 0.3A 0~35.0A when using please winding two or three laps on the
*Cool. I rating 0.3A 0~35.0A sensor)
Onboard: use the controller’s own three-phase power
protection;
Switch input: use an external three-phase power
On_board;
*Phase On_boa protection.
Forbid;
monitor rd (The external three-phase power protection can only
IO_input
be used when [DI9 fuction] is set " Phase switch" .)
Forbid: do not use three-phase power detection
function.
Cool Cool overload;
DI1 input opt Selection of switch DI1 input function
overload Anti-freezing
*Comp
2 1~2 Selection of the number of compressor
number
AIR-WATER; AIR-WATER. fan-cooled water chiller,
AIR-WA W-W SYS.; W-W SYS. :water-cooled water chiller,
*Machine type
TER AIR-AIR; AIR-AIR : fan-cooled fan cooler
WATER-AIR WATER-AIR : water-cooled fan cooler
Use: Allows users to switch between English and
Chinese.
*Lang switch Use Forbid ~ Use
Forbid: Forbid users to switch between English and
Chinese.
Pump stop: stop the cold pump in case of Temp.high
Pump Pump stop ~ fault;
Temp.high AL
keep Pump keep Pump keep: do not stop the cold pump in case of
Temp.high fault.
Remote; Remote:DI2 input for remote switch
DI2 function Remote 1#Comp Oil 1#Comp Oil LVL: DI2 input for 1#comp oil level
LVL detection
Load offset 1.0℃ 0~10.0℃ Temperature deviation of load the compressor
Load offset 1.8℉ 0~18.0℉ Fahrenheit ℉
Unload offset 1.0℃ 0~10.0℃ Temperature deviation of unload the compressor
Unload offset 1.8℉ 0~18.0℉ Fahrenheit ℉
T.setpoint max 30.0℃ -38.0~99.9℃
T.setpoint max 86.0℉ -36.4~211.8℉ To limit the temperature of user set.
T.setpoint min 5.0℃ -38.0~99.9℃
T.setpoint min 41.0℉ -36.4~211.8℉ Fahrenheit ℉
T.bias 0.0℃ -9.9~9.9℃ Compensation for the liquid temperature
Temp. T.bias 0.0℉ -17.8~17.8 Fahrenheit ℉
Setting Fault of “Temp.low AL” warning is reported when the
T.low protect 4.0℃ -40.0~99.9℃
liquid temperature is lower than the set value.
T.low protect 39.2℉ -40.0~211.8℉ Fahrenheit ℉
Fault of “Temp.high warn” warning is reported when
T.high warn 50.0℃ 0~99.9℃
the liquid temperature is higher than the set value.
T.high warn 122.0℉ 32.0~211.8℉ Fahrenheit ℉
Fault of “Temp.high AL” warning is reported when the
T.high alarm 60.0℃ 0~99.9℃ liquid temperature is higher than the set value. And
Stop the compressor and delay to stop the cool pump.
T.high alarm 140.0℉ 32.0~211.8℉ Fahrenheit ℉
T.high reset 5.0℃ 0~99.9℃ If liquid temperature<[T.high alarm]–[T.high reset],
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 13/15

manual reset of “Temp.high AL” fault is allowed;


If liquid temperature<[T.high warn]–[T.high reset], the
“Temp.high warn” fault is automatically reset;
T.high reset 9.0℉ 0~179.8℉ Fahrenheit ℉
T.freeze prot forbid forbid~15.0℃ No such function when set to forbid.
T.freeze prot forbid forbid~59.0℉ No such function when set to forbid(32.0℉).
Pump on delay 10 S 1~255 S Delay after cold pump startup.
Cool on delay 10 S 1~255 S Delay after cool pump startup.
Control the compressor ON/OFF every [Capacity ctrl.]
interval time;
For double-compressor control, if the conditions of
Capacity ctrl. 5S 0~255 S
two compressors ON are satisfied, then one of the
compressors ON and the other after the time of
[Capacity ctrl.].
To avoid frequent ON/OFF the compressor, the
Comp protect 60 S 0~255 S interval between the start of two compressors must be
greater than the set value.
Input stable 2S 0~255 S The time General fault stable.
It is considered to be valid only when the water flow
W.flow stab. 5S 0~255 S
alarm continue for the time.
Compressor low-pressure fault input is allowed only
LP detect dly 60 S 0~255 S
when the compressor has run for the set time.
LP stable 5S 0~255 S Low-pressure fault stable time
0: the parameter has no effect .
Non-0: in case of low pressure fault of the
LP stop pump 0S 0~300 S compressor, immediately stop all compressors and
cool pump, delay the [LP stop pump] and stop the
cold pump.
0: this parameter has no effect.
Time Comp Non-0: the compressor cannot start when the
Setting 0H 0~9999 H
operation accumulative operation time is greater than the set
value.
0: the parameter has no effect ;
Comp shift 0 Min 0~255 H Non-0: a compressor will automatically switch to
another after it has run continuously for that time.
1#Comp.I 2S 1~255 S The current fault of 1#compressor can only be
avoid detected after 1# compressor has started for the set
time.
(When the [Current detect] is set “forbid”, the
parameter is not displayed.)
The current fault of 2#compressor can only be
detected after 2# compressor has started for the set
2#Comp.I
2S 1~255 S time.
avoid
(When the [Current detect] is set “forbid”, the
parameter is not displayed.)
The current fault of cold pump can only be detected
after it has started for the set time.
Pump. I avoid 2S 1~255 S
(When the [Current detect] is set “forbid”, the
parameter is not displayed.)
The current fault of cool pump can only be detected
after it has started for the set time.
Cool. I avoid 2S 1~255 S
(When the [Current detect] is set “forbid”, the
parameter is not displayed.)
Comp Oil dly 5S 1~255 S 1#Comp/2#comp oil low stable time
*Freez Selection of switch input mode
N.O N.O ~ N.C
overload N.O: switch off with no fault;
*Cold W.flow N.C N.O ~ N.C N.C: the switch is closed with no fault.
Input
*W.level When [DI5 fuction] is " Vent1 temp", it is the place for
Setting N.C N.O ~ N.C
switch N.O and N.C settings of vent1 temperature detection.
*Comp Selection of switch input mode
N.O N.O ~ N.C
overload N.O: switch off with no fault;
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 14/15

*Low pressure N.C N.O ~ N.C N.C: the switch is closed with no fault.
*High pressure N.O N.O ~ N.C
When [DI9 fuction] is " Cool W.flow", it is the place for
N.O and N.C settings of cool water flow switch.
*Phase error N.O N.O ~ N.C When [DI9 fuction] is "Vent1 temperature", it is the
place for N.O and N.C settings of vent1 temperature
detection.
When [DI1 input opt] is " Anti-freezing", it is the place
*Cool overload N.C N.O ~ N.C
for N.O and N.C settings of antifreezing switch.
1#Comp/2#comp oil low
Comp Oil
N.C N.O ~ N.C N.O: switch off with no fault;
switch
N.C: the switch is closed with no fault.

[Note]: remote switch, if the remote control is used, the unit will start up when remote switch input is closed and
stop when remote switch input is disconnected.
X1.GW532A.TY.F01M.Manufacturer Instruction Manual. 15/15

14 Electrical Connection Diagram

X1.GW532A.TY.F01M.Electrical Connection Diagram


N(+) ① 1#Comp
DO1:annunciator Connect GW122B 号
DO1 Alarm GW122B
FU COM1 RY1
GW532A L2 ② 2#Comp
L(-) DO2
CUR1 号
RY2 Cool pump(Fan) L1
D02-DO5: L2
CPU
DO3 ① Cool
RY3 Cold pump CUR2
contactor/valve 号
DO4 L1 GW122B
RY4 1#Compressor
DO5 ② Cold
N
2#Compressor 号
RY5
AI1 Two Comp
L
temperature
FU COM2 sensor 1#Comp

R 号
Phase Input DI2 DI1
GW122B
S ② Cold
ICOM DI12 DI11 DI10 DI9 DI8 DI7 DI6 DI5 DI4 DI3 号
T
① Cool

FU GW122B


L N One Comp

DI1:Cool overload/Antifreezing switch DI7:Low pressure of 1#compressor


DI2:Remote switch DI8:High pressure of 1#compressor
DI3:Cold Pump overload DI9:Cool flow switch/Vent2 temprature/Phase switch
DI4:Cold Water flow switch DI10:2#Compressor overload
DI5:Water level switch/Vent1 temperature DI11:Low pressure of 2#compressor
DI6:1#Compressor overload DI12:High pressure of 2#compressor

15 Installation Dimensions