DATA POINT LIST

POINTS PER
QTY OF TOTAL QTY
POINT DESCRIPTION UNIT DESCRIPTION/ REMARKS
UNITS
DI DO AI AO DI DO AI AO
DDC-1 VALVE ROOM PACU 1A&1B
PACU 1A&1B (2 NOS)
Supply Fan start/stop 2 1 - 2 - -
Supply Fan status 2 1 2 - - -
Supply Fan trip 2 1 2 - - -
Supply Fan Air flow 2 1 2 - - -
Supply Fan No Air flow 2 1 - 2 - -
PRE-Filter status 2 1 2 - - -
Final Filter Status 2 1 2 - - -
COMP-(1,2,3&4) Start/Stop 2 4 - 8 - -
COMP-(1,2,3&4) Status 2 4 8 - - -
COMP-(1,2,3&4) Trip 2 4 8 - - -
COMP-(1,2,3&4) High pressure alarm 2 4 8 - - -
COMP-(1,2,3&4) Low pressure alarm 2 4 8 - - -
Condenser Fan Status 2 8 16 - - -
Condenser Fan trip 2 8 16 - - -
Power Fail Status 2 1 2 - - -
Comm. Supply Air Temp. Sensor 1 1 - - 1 -
comm. Return Air Temp. Sensor 1 1 - - 1 -
Room Temp. & R.H 2 2 - - 4 -
EDH COMMAND 2 3 - 6 - -
EDH STATUS 2 1 2 - - -
EDH TRIP 2 1 2 - - -
SA MVD + Auxiliary 2 1 1 2 2 - -
RA MVD + Auxiliary 2 1 1 2 2 - -
Motorized Fire/ Smoke Damper 6 1 1 6 6 - -
DATA POINT LIST

POINTS PER
QTY OF TOTAL QTY
POINT DESCRIPTION UNIT DESCRIPTION/ REMARKS
UNITS
DI DO AI AO DI DO AI AO
DDC-1 VALVE ROOM PACU 1A&1B
SMOKE BURGING FAN ( SPF-01) (1 NOS)
SPF start/stop 1 1 - 1 - -
SPF Fan status 1 1 1 - - -
SPF Fan trip 1 1 1 - - -
SPF Fan Air flow 1 1 1 - - -
SPF Fan No Air flow 1 1 - 1 - -
MVD + Auxiliary 1 1 1 1 1 - -
OTHER SYSTEM
HIGH TEMP ALARM 1 1 - 1 - -
COMMON ALARM 1 1 - 1 - -
DDC RESET 1 1 1 - - -
FIRE SYS. TEST 1 1 1 - - -
FIRE ALARM SIGNAL TO DDC 1 1 1 - - -
BUZZER 1 1 1 - -
TOTAL POINTS 97 34 6 - 137
TOTAL POINTS WITH 20% SPARE 116 41 7 - 164