I/O Modules

140ACO13000 High Density Analog Out I/O Module

Overview The 140ACO13000 is an eight channel analog output module used to control and
monitor current in 4 ... 20 mA, 0 ... 20 mA, and 0 ... 25 mA loops.

Specifications The following table shows the technical specifications for the ACO13000 module.
Specifications
Number of Channels 8
LEDs Active, indicates bus communication present
F, indicates a fault on a channel
1 ... 8 (Green) - Module outputs active
1 ... 8 (Red) - Broken wire on indicated channels
Required Addressing 8 Words Out
Module Ranges and Resolution 0 ... 25 mA, 0 ... 25,000 counts
0 ... 20 mA, 0 ... 20,000 counts
4 ... 20 mA, 0 ...16,000 counts
4 ... 20 mA, 0 ...4,095 counts
Loop Voltage 6 ... 30 Vdc maximum
Internal Voltage Drop 6 Vdc min, 30 Vdc max @ 25 mA
Accuracy Error @ 25 ° C +/- 0.2% of full scale
Linearity +/-12 µA, 4 ... 20 mA, 0 ... 4,095 counts
+/-4 µA, 0 ... 25 mA, 0 ... 25,000 counts
+/-4 µA, 0 ... 20 mA, 0 ... 20,000 counts
+/-4 µA, 4 ... 20 mA, 0 ... 16,000 counts
Accuracy Drift w/Temperature Typical: 0.004% of full scale / °C.
Maximum: 0.007% of full scale / °C
Isolation
Channel to Channel none
Field to Bus 1780 Vac for 1 minute
Update Time 5 ms for all 8 channels
Settling Time Full Scale 1.6 ms to 5% of the final value
Step Change 3.2 ms to 0.1% of the final value
Fault Detection Broken wire in 4 ... 20 mA mode.
Bus Current Required 550 mA
Power Dissipation 5.0 W
External Power Supply See Loop Voltage above

840 USE 100 00 September 2002 509


I/O Modules

Specifications
Fusing
Internal None
External None
Voltmeter Monitor
Scaling VOUT (Volts) = ILOOP (mA) x 0.10
Accuracy @ 25° C +/- 0.2% of full scale
Output Impedance 300 Ω
Maximum Cable Length 1 meter
Programming Software Modsoft Ver 2.6 or Concept 2.2

510 840 USE 100 00 September 2002


I/O Modules

Wiring Diagram The folllowing figure shows the 140ACO130 Wiring Diagram.
VM

RETURN 2 1 MONITOR 1

Field Device OUTPUT 1 SINK 4 3 N/C

RETURN 6 5 MONITOR 2

Field Device OUTPUT 2 SINK 8 7 N/C

N/C 10 9 N/C

RETURN 12 11 MONITOR 3

OUTPUT 3 SINK 14 13 N/C


Field Device
RETURN MONITOR 4
16 15

OUTPUT 4 SINK 18 17 N/C


Field Device
N/C 20 19 N/C

RETURN 22 21 MONITOR 5

Field Device OUTPUT 5 SINK 24 23 N/C

RETURN 26 25 MONITOR 6

OUTPUT 6 SINK 28 27 N/C


Field Device
N/C 30 29 N/C

RETURN 32 31 MONITOR 7

OUTPUT 7 SINK 34 33 N/C


Field Device
RETURN 36 35 MONITOR 8

OUTPUT 8 SINK 38 37 N/C


Field Device
+ VM
N/C 40 39 N/C
24 Vdc
loop
– supply

840 USE 100 00 September 2002 511


I/O Modules

Notes on Wiring 1. At power up, channel outputs are all at zero current (0 mA).
Diagram 2. VM is an optional voltmeter that can be connected to read voltage that is
proportional to the current. Wiring to this terminal is limited to 1 meter maximum.
3. Either shielded or unshielded cables may be used. In noisy environments, twisted
shielded cable is recommended. Shielded cable should have a shield tied to earth
ground near the signal source end.
4. Unused outputs may cause the activation of the F (fault) LED. To avoid this
occurrence the unused channels should be configured in the 0 ... 25 mA range.
5. All terminals labeled ‘RETURN" are common inside the module.
6. N/C = Not connected

512 840 USE 100 00 September 2002