You are on page 1of 2

So ware Version: 3.8.3.

FCU SUMMARY REPORT

SOFTWARE VERSION: 3.8.3.0 Report Date: 5/16/2023

Project Name: Customer:


Address : Selec on by:

Cooling Coil Data Hea ng Coil Data

Fan Cooling Capacity Air Side Water Side Air Side Water Side
Air Flow ESP
Speed Hea ng
Water
Unit Inlet Temp. Pressure Capacity Entering Leaving Inlet Water Pressure
Model Total Sensible Entering Temp Leaving Temp* Flow
Naming Temp. Rise Drop Temp Temp* Temp. Flow Rate Drop
Rate
DB WB DB WB DB DB
H/M/L m3/hr Pa kW kW °C °C L/s kPa kW °C L/s kPa
°C °C °C °C °C °C
Room 1
FWF02C FWF02C HIGH 646 - 1.80 1.31 24.00 18.61 18.04 15.79 7.00 7.00 0.06 7.3 - - - - - -
[2]
Room 1
FWF04C FWF04C HIGH 680 - 3.30 2.20 24.00 18.61 14.48 13.55 7.00 7.00 0.11 11.5 - - - - - -
[3]
Room 1
FWF05C FWF05C HIGH 748 - 3.57 2.43 24.00 18.61 14.43 13.63 7.00 7.00 0.12 11.6 - - - - - -
[4]
Room 1
FWK06E FWK06E HIGH 1274 - 4.66 3.27 24.00 18.61 16.44 14.86 7.00 7.00 0.16 7.4 - - - - - -
[5]

The cer fica on of the so ware has to be verified in www.euroventcer fica on.com
So ware Version: 3.8.3.0
Room 1
FWK08E FWK08E HIGH 1461 - 5.21 3.69 24.00 18.61 16.55 14.96 7.00 7.00 0.18 13.2 - - - - - -
[6]
Room 1
FWK09E FWK09E HIGH 1512 - 6.79 4.52 24.00 18.61 15.19 13.95 7.00 7.00 0.23 9.3 - - - - - -
[7]
Room 1
FWK11E FWK11E HIGH 1699 - 8.10 5.59 24.00 18.61 14.31 13.64 7.00 7.00 0.28 15.2 - - - - - -
[8]
Room 1
FWK13E FWK13E HIGH 1937 - 10.33 6.51 24.00 18.61 14.09 13.00 7.00 7.00 0.35 21.2 - - - - - -
[9]
*For reference only

Disclaimer: The results are based on simula on and may not be accurate or reflect the actual condi on. While all reasonable a empts have been made to ensure accuracy, currency and reliability of the
content, all informa on is provided "as is". There is no guarantee as to the completeness, accuracy, meliness or the results obtained from the use of this informa on. Daikin Malaysia Sdn. Bhd. cannot be
held responsible for the correctness, completeness or quality of the informa on provided by this so ware. Therefore, liability claims regarding any damages caused by the use of any informa on provided,
including informa on which is incomplete or incorrect, will be discarded.

The cer fica on of the so ware has to be verified in www.euroventcer fica on.com