Professional Documents
Culture Documents
ABSTRACT rates, and chilled water storage tanks will store many more
ton-h (MJ) of cooling. This fundamental approach provides
This article recommends practical methods for achieving
significant, enduring improvements in the performance of
high, i.e., 15°F (8.3"C) or greatel; chilled water temperature
variable-flow hydronic cooling systems.
differentials (ATs) in new and existing variableflow hydronic
cooling systems. Once high chilled water ATs are realized,
ANALOGY: ELECTRICAL DISTRIBUTION SYSTEMS
more Btu's (Jh)of cooling will be accomplished per gallon
(liter)of chilled water distributed (Figure 1). Pressure losses A useful analogy for understanding the causes and effects
and pumping energy will decline considerably in existing of lowhelow design chilled water temperature differentials
(ATs) in variable flow hydronic cooling systems is power
--```,,,``,,`,`,``,,,,,``,,,,`,`-`-`,,`,,`,`,,`---
hydronic cooling systems, and smaller pumps and piping may
be installed in new hydronic cooling systems. Also, water chill- factor correction in alternating current electrical distribution
ers will no longer be limited by maximum evaporator flow systems (Table 1). In effect, a low power factor is equivalent
to a lowhelow design chilled water AT. Furthermore, operat-
ing an alternating current electrical distribution system with a
i SLOPE = 8.33/1.W
TABLE 1
ElectricaVCoolingAnalogy
'1 /
/
/-I
I
I
I
II
I Root Cause
Solution
I Large, underloaded
induction motors
~ ~ _____~
TABLE 2
Cooling Coil Characteristics
--```,,,``,,`,`,``,,,,,``,,,,`,`-`-`,,`,,`,`,,`---
60 47.8 60.8"F (16.0"C) 18.8"F (10.4"C) 125.3
50 37.8 62.1"F (16.7"C) 20.1"F ( 11.2"C) 134.0
40 27.9 63.5"F (17.5"C) 21.5"F (11.9"C) 143.3
--```,,,``,,`,`,``,,,,,``,,,,`,`-`-`,,`,,`,`,,`---
2 0 7 F AT
conditions.
7 i . r ~uma
4. Specify control valve cages, trim, plugs, and seals capable 327 gpm
RECOMMENDED PRACTICE
of withstanding the erosion and cavitation present when
throttling flow at the highest AP that the chilled water distri-
bution pump can apply at low flow conditions. Figure 2 Cascade cooling.
4 r CHW
~
CWUND nui
<M w m . EXCWGUI
CONVENTIONAL PRACTICE
CHWR C H W
CONVENTIONAL PRACTICE
RECOMMENDED PRACTICE
COST-OF-OWNERSHIP
Cost-of-ownership considerations include capital expen-
ditures and annual operating expenditures.
A hydronic cooling system with a 15°F (8.3"C) chilled
water AT will require smaller pumps, piping, heat exchangers,
and cool storage tanks than an equivalent-capacity system
with a 10°F (5.6"C) AT. However, the high AT system will
spend more for ( i ) cooling/dehumidifying coils having addi- 1 J
&3T
tional rowslenlarged face areas and (2) equal-percentage RECOMMENDED PRACTICE
control valves having globe-style bodies with robust actua-
tors, cages, trim, lugs, and seats, than the low AT system. Figure 5 Run-around coils.
When combined, these factors will tend to yield lower capital
expenditures for systems with higher chilled water ATs in
large applications having fewer/larger air-handling units, Annual operating expenditures are clearly lower for
more distribution pump stations, greater lengths of distribu- hydronic cooling systems having higher chilled water ATs due
tion piping, and large cool storage tanks. Good candidates to lower flow rates and pressure losses year-round. Also,
include university campuses, airports, and the like where a providing cooling/dehumidifying coils with enlarged face
large central water-chilling plant serves multiple buildings. areas precludes increased air-side pressure losses (and
--```,,,``,,`,`,``,,,,,``,,,,`,`-`-`,,`,,`,`,,`---
664
Copyright American Society of Heating, Refrigerating and Air-Conditioning Engine ASHRAE Transactions: Symposia
Provided by IHS Markit under license with ASHRAE Licensee=Parsons - Locations 5 - 44/9989682108, User=Badr, Youssef
No reproduction or networking permitted without license from IHS Not for Resale, 11/29/2017 04:28:20 MST
increased fan energy usage) normally associated with addi- BIBLIOGRAPHY
tional rows. Larger hydronic cooling systems (such as those Avery, G. 1998. Controlling chillers in variable flow sys-
described in the above paragraph) stand to realize the greatest tems. ASHRAE Journal 40(2): 42-45.
savings in annual operating expenditures.
Fiorino, D. 1999. Achieving high chilled water delta Ts.
ASHRAE Journal 41(11) 24-30.
REFERENCES
Hansen, E.G. 1985. Hydronic system design and operation.
Kirshner, W. 1995. Troubleshooting chilled water distribu- New York: McGraw-Hill.
tion problems at NASA Johnson Space Center. Heating/ Hansen, E.G. 1998. Letter to the editor, Re: Low delta T.
PipingIAir Conditioning 67(2): 51-59. ASHRAE Journal 40( 11): 19.
Brown, W. 2000. Letter to the editor, Re: Achieving High Kirshner, W. 1998. Low delta t central plant syndrome.
chilled water delta Ts. ASHRAE Journal 42(2): 12. ASHRAE Journal 40( 1): 37-32.
--```,,,``,,`,`,``,,,,,``,,,,`,`-`-`,,`,,`,`,,`---