Compressor Staging/
ICM 102
Startup Delay Timer DELAY ON MAKE
• Knob adjustable from .03-10 minutes HMPS00C
• Works with anticipator thermostats
MODE OF OPERATION INSTALLATION
When power is applied to the input, the 1. Disconnect power.
time delays begins. After the time delay is 2. Connect terminals in series with the
complete, the load energizes and remains starting device as shown in the wiring
energized as long as power is applied. The diagram below.
control is reset by removing power during 3. For 24 VAC circuits, apply control as
or after the time delay period. The ICM102 packaged. For 120/240 VAC circuits, cut
provides thermostat interruption protection, the jumper wire.
even in the presence of a trickle current. 4. Select the desired time delay.
5. Reapply power, check operation.
SPECIFICATIONS 6. Trickle current bypass resistor
Input T1 to T3 < 1K ohm.
• Voltage: 18-240 VAC
• Frequency: 50-60 Hz TIMING DIAGRAM
Output Input
• Output Ratings: Voltage
0V
– Maximum: 1.5 amps Transfer Time
– Minimum: 40 mA
Load
– Inrush: 15 amps Load
Voltage
Time Delay
Energized
0V
Time Delay Time
C
Y
Contactor
T’STAT