Professional Documents
Culture Documents
Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG ("Siemens"). They are
non-binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.
Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
Siemens AG 2006 All rights reserved
foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.
Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.
Security information
Siemens provides products and solutions with Industrial Security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the Internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: https://www.siemens.com/industrialsecurity.
Table of contents
Legal information ......................................................................................................... 2
1 Introduction ........................................................................................................ 4
2 Function .............................................................................................................. 5
2.1 Description of the Functionality for Clockwise Motor Rotation ............. 5
2.1.1 The Preferred Circuitry Configuration is Implemented ......................... 5
2.1.2 The Preferred Circuitry Configuration is not Implemented ................... 6
2.2 Changing the Direction of Rotation from Clockwise to
Counterclockwise ................................................................................. 7
2.3 Device Rating for Standard Start-up .................................................... 7
2.4 Favorable and Unfavorable Circuitry Configurations ........................... 8
3 Assembly and Wiring ...................................................................................... 10
3.1 Main Circuit Overview ........................................................................ 10
1.1 Control Circuit Overview..................................................................... 10
4 Siemens – The Solution for Complete Contactor Assemblies for
Star-delta Starting (Wye-delta Starting) up to 90 kW for one Direction
of Rotation ........................................................................................................ 11
5 Annex ................................................................................................................ 13
5.1 Contact Partner .................................................................................. 13
5.2 Bibliography ........................................................................................ 13
Siemens AG 2006 All rights reserved
1 Introduction
Star-delta (wye-delta) starting continues to be used for switching on 3-phase
induction motors. When this type of connection method is used, the starting current
is reduced to 1/3 of the current required for direct switching.
When switching from a star (wye) circuit to a delta circuit, transients can occur in
the motor, which, further intensified by an unfavorable constellation of line
frequency and inductor field, lead to the development of larger current peaks than
is the case if the stopped motor is directly switched into a delta connection. In an
unfavorable case, the following problems could occur:
• Short-circuit devices could trip,
• The delta contactor could become welded or be subject to high contact erosion,
• The motor could be subject to extreme dynamic overloading.
2 Function
Two different types of motor connections are often listed in star-delta (wye-delta)
starter circuit diagrams: One for clockwise and one for counterclockwise motor
rotation. When installing the motor, care should be taken to ensure that the
transient current peaks are as small as possible. Correct wiring of the motor
terminal board is essential.
The vector diagram illustrated below shows the voltages that develop in a motor
with clockwise rotation when the motor is switched from a star (wye) to a delta
connection. In this case, the motor terminals are correctly connected according to
the preferred circuitry configuration, meaning that phase L1 is connected to the
motor terminals U1 and V2, L2 is connected to V1 and W2, and L3 is connected to
W1 and U2:
L1 L2 L3
L1 L2 L3
Siemens AG 2006 All rights reserved
U1 V1 W1
U1 V1 W1
U2 V2 W2 U2 V2 W2
L1
U L1´− N
L3‘ L1‘
∆U U L1− L 3
U L1´− N
U L1− L 3 N
L3 L2
L2‘
Fig. 2: Vector diagram for switching from a star (wye) connection to a delta connection for
clockwise motor rotation when the motor phases are correctly connected
During the idle changeover delay, the rotor lags behind the phase sequence. The
magnetic field induces a damped residual voltage, which is listed here in the
voltage vector diagram for phase L1: U L1' − N . When switching over to a delta
connection (Fig. 1 and Fig. 2), the stator winding carrying this residual voltage is
supplied with the line voltage U L1− L 3 . Thanks to the favorable vector position of the
residual voltage U L1' − N and the line voltage U L1− L 3 , which have approximately the
same values, the differential voltage ∆U is relatively small. Thus, the current peaks
resulting from this voltage also remain small.
The motor also rotates clockwise when the motor terminals are connected as
follows: Phase L1 is connected to motor terminals U1 and W2, L2 is connected to
V1 and U2, and L3 is connected to W1 and V2.
L1 L2 L3
U1 V1 W1
U2 V2 W2
Siemens AG 2006 All rights reserved
Fig. 3: Incorrect connection of the motor phases also resulting in clockwise motor rotation
Both the lagging residual voltage and the damped residual voltage are active in the
stator. When the motor is switched to a delta connection, the phase winding with
the vector U L1' − N is supplied with the line phase U L1− L 2 . However, each of these
voltages has a different vectorial direction. The differential voltage ∆U is high, thus
causing a correspondingly high transient current peak. Switching from a star (wye)
connection to a delta connection therefore results in the following vector diagram:
The rotor lags during the
idle pause
Phase sequence
L1
U L1´− N
L1‘
L3‘
U L1− L 2
U L1´− N U L1− L 2
N ∆U
L3 L2
L2‘
Fig. 4: Vector diagram for connecting the motor phases according to Fig. 3,
resulting in a large transient current peak
L1 L2 L3 L1 L2 L3
U1 V1 W1 U1 V1 W1
U2 V2 W2 U2 V2 W2
Fig. 5: Correct connection of the motor phases for counterclockwise rotation of the motor
Siemens AG 2006 All rights reserved
Refer to Section 3 for information regarding the wiring of the main current and the
control current. The circuit diagrams for contact assemblies for star-delta (wye-
delta) starting with clockwise and counterclockwise motor rotation are illustrated in
the preferred circuitry configuration.
unfavorable favorable
U1: L3 U2: L1 U1: L3 U2: L2
V1: L1 V2: L2 V1: L1 V2: L3
W1: L2 W2: L3 W1: L2 W2: L1
Comment: When two phases in the circuit are exchanged to change the direction of rotation,
the connection is automatically switched from the more favorable connection to the less
favorable one and vice versa.
L1 L2 L3
Line
CCW
Line
CW
Delta
CCW
Delta
CW Y
V1
L2-U1 / U2-L1 M V2 L2-V1 / V2-L1
L3-W1 / W2-L2 L3-W1 / W2-L2
U1
3~ U2
Fig. 6: Main circuit of the contactor assembly for star-delta (wye-delta) starting
L1/L+
Delta CCW Y
Delta CW
Fig. 7: Control circuit of the contactor assembly for star-delta (wye-delta) starting
Contactor assemblies
Size
AC-3/400 V tested
11 25 S00-S00-S00 3RA2417-8XF31-1…
11 25 S0-S0-S0 3RA2423-8XF32-1…
22 50 S0-S0-S0 3RA2426-8XF32-1…
37 80 S2-S2-S0 3RA2435-8XF32-1…
45 86 S2-S2-S0 3RA2436-8XF32-1…
Contactor assemblies
11 25 S00-S00-S00 3RA2417-8XF31-2…
11 25 S0-S0-S0 3RA2423-8XF32-2…
22 50 S0-S0-S0 3RA2426-8XF32-2…
For further information, for example, regarding other voltages and/or accessories,
please refer to the IC 10 catalog.
Siemens AG 2006 All rights reserved
5 Annex
5.1 Contact Partner
Technical Support for Electrical Products
Support requests: www.siemens.com/support-request
Telephone: +49 (911)-895-7222
5.2 Bibliography
[1] “Schalten, Schützen, Verteilen in Niederspannungsnetzen”, Fachbuch
Siemens [Switching, Protection and Distribution in Low-Voltage
Networks” (Siemens reference book)]