You are on page 1of 6

I–BETH39GB_C page 1/6 OIL TREATMENT

TYPE MAS 2000 TEC ARRAS MAXEI


TECHNICAL DESCRIPTION
OF THE ON-LINE OIL TREATMENT PLANTS OF THE TRANSFORMERS

TYPE MAS 2000 TEC


PREAMBLE MAXEI Industries Electri- tests performed in our Quality
ques oil treatment plants and Control platform, ARRAS
The efficient and reliable use are particularly recommen- MAXEI treatment plants
SUMMARY: of dielectric fluids in trans- ded to maintain, dry and meant to treat live / operating
formers, circuit breakers and fill your transformers and transformers ensure a reliable
other types of electrical circuit- breakers.
Operating principle 2 equipments depends upon By removing solid impuri-
and safe treatment of the
some of their basic character- ties, dissolved moisture and transformer.
Main characteristics 2 istics, which in service may gases from insulating and Available with various auto-
be affected, resulting in re- cooling oils, they indeed mation levels, the MAS 4000
duced operating efficiency of enable to restore the oil TEC and MAS 2000 TEC
Plant components 2
the electrical equipments. dielectric properties, and plants can operate not only
In order to act as an insulant, thus to extend the useful on live / operating trans-
Plant description 3 a coolant and an extinguish- life of your electrical equip- formers, but also on non-
ing medium, dielectric fluids ment. energized transformers ei-
Operating diagram 4 must have some basic proper- Used and reknowned all over ther for their filling-up or
ties, and especially a high the world for their perfor-
for their traditional mainte-
dielectric strength. mance, reliability and ease
Optional features 5
Now, in service, the dielectric of operation, our standard
fluids basic properties may be plants have been enriched
affected by oxidation, con- with the latest technological
densation and other contami- achievements in order to
nants such as dissolved gases develop a complete range of
and solid impurities. plants meant to treat live /
Working on the principles operating transformers.
of filtration, dehydration, As their operation principle
and vacuum degasification, has been approved further to MAS 2000 TEC on a skid

Treatment of live / operating transformers with MAS 2000 TEC


ARRAS MAXEI MAS 2000 TEC plant ARRAS MAXEI MAS 2000 TEC plant treatment.
has been especially designed to carry out has been designed to treat dielectric oil An oil at 20 ppm will go out at 3
the operations of filtration, dehydration with a 50 ppm moisture content and a ppm* after 1 pass. For a treatment of
and absorption of dissolved gases on a dissolved gas content of approx. 10% the active parts of transformer, these
transformer that is under current or operat- by volume before being treated. data can vary in function of the state
ing. Then, the transformer is totally avail- Once the optimal treatment conditions of the transformer.
able during the treatment operations that have been reached, the clean treated oil
are necessary for its efficient and safe op- goes out after 1 pass at a maximum tem- Co mp aris o n b etwenn vap o r and liq uid
p has es o f mo is t ure and d ielectric o il
eration. Furthermore, the transformer does perature of 70°C with a moisture con- 1 000
EAU
not need to be stopped at all during con- tent below 5 ppm* and a dissolved gas Lliq uid wat er
HUILE
nection with the plant if the security dis- content of approximately 0.1% by vol-
1 00

Liq uid o il
tance between the transformer’s connec- ume*. 1 0

Vap o r wat er
tions and the terminals can be respected. This restores the oil dielectric strength 1

Vap o r o il
to a value in excess of 75 kV after 0,1

0,01

Type of transformer to be treated Up to 220 kV


Max. oil quantity 20 000 litres T °C
I–BETH39GB_C page 2/6 OIL TREATMENT TYPE MAS 2000 TEC
ARRAS MAXEI

Operating principle
The pre-filtered dielectric fluid enters the
plant through an inlet strainer, and then
passes through an inlet oil pump and into
Options an oil heater, where it is heated by im-
mersion heaters.
Road trailer
Cart After a first filtration 6 µ absolute
through cartridge filter, the dielectric
fluid is sprayed into a vacuum chamber
on a basket of degazing rings.
Finally, after elimination of the air bub-
bles, the clean treated fluid flows through
the outlet oil pump.

Main characteristics
Nominal flow* during treatment in l/h 2,000

Options Heating power in kW 31

Plant with metallic cover Total power in kW 38

Plant with tarpaulin Filtration** by cartridge in absolute µm 6


Limit vacuum closed suction in mbars 0,5
Vacuum during treatment in mbars 0,5 to 5
* : Approximate value.
** : Consumable cartridge with filtration expressed in absolute µm at 99.9 %.
Our plants are all equipped with tropicalized electrical material
Power supply 400 Volts 3 phases 50 Hz
Auxiliary operation in 220 Volts by transformer.

Plant components.
- 1 Inlet oil motor-pump.
Options - 1 Direct electrical heater.
Telecontrol - 1 Cartridge filter 6µ absolute.
- 1 Dehydration tank.
System of on-line measuring of - 1 Outlet oil vacuum motor-pump.
moisture content - 1 Trap system of free gases.
Cartridge filter 1µ absolute - 1 Single-staged vacuum motor-pump.
- 1 Set measuring, controlling, alarming and regulating apparatus
Digital recording of the treat- - 1 Control panel with display and PLC
ment parameters - 1 Set pipes, valves and accessories for the connection of the plant to the transformer.
Continuous control of the oil - 1 Set of 6 hoses with flanges (5 hoses ∅25 , length : 10 m and 1 hose ∅25 , length : 2 m ).
level in the transformer. - 1 Set of automatic valves to isolate the transformer
- 1 Section iron plate with retention tray and maintenance wheels.
I–BETH39GB_C page 3/6 OIL TREATMENT TYPE MAS 2000 TEC
ARRAS MAXEI

Plant description
Inlet pump
Continuous control of the temperature of the plant at oil inlet,
Maximum flow of pump in l/h 4,000
before degazing chamber and at oil outlet.
Pump type Centrifugal
Remote control of the overheating through security thermostat.
Discharge rate in mCE 30

Motor power in kW 2.2 Permanent control of the overpressures in the network thanks to
Rotation speed in rpm 1,500
pressostat, security valve and by-pass.
Pump building Cast iron/steel
Flows display at inlet, before degazing (regulation and mini-
Connection diameter in mm 25 mum flow) and outlet of the plant .

Oil heating Continuous control of the oil levels and condensats in the plant.
Total heating power in kW 31
Automatic regulation of foaming effects.
Number of thermo dippers 4

Power of an element in kW 7.8 Bi-filtration through strainer (0,8 mm), filtration before de-
gazing (1 filter 6µm absolute).
Filtration 6 µm absolute
Number de cartridges per filter 3 Remote control of filters clogging with pressostat.
Number of filter 1
Vacuum control with Pirani gauge and manometer.
Filter building Cast iron/steel

Clogging control Pressostat


Removal of free gases and air bubbles at outlet of the plant.

Detection and automatic draining of free gases at plant outlet.

Vacuum pump Running of the plant thanks to an operating system.


3
Flow in m /h 100
Self-operating in compressed air by compressor.
Limit vacuum in mbar 0.5

Motor power in kW 2.2 Vacuum accumulator for draining of transformers’ connections.


Rotation speed in rpm 1,500
Secure connections to the transformer.
Oil capacity in litres 3

Vacuum measurement Pirani

Outlet pump
Maximum flow of pump in l/h 2,500

Pump type Centrifugal

Discharge rate in mCE 30

Motor power in kW 1.5 Automated and rationalized starting sequences.


Rotation speed in rpm 1,500
Filling of the plant.
Pump building Cast iron/bronze
Piping put under vacuum.
Connection diameter in mm 25
Filling of the piping.
Treatment in closed circuit.
Treatment on transformer.
Draining of the piping.
Draining of the plant.
Vacuum in the accumulator for the pipes draining.
I–BETH39GB_C page 4/6 OIL TREATMENT TYPE MAS 2000 TEC
ARRAS MAXEI

Control panel
ARRAS MAXEI oil treatment plant type MAS 2000 TEC is equipped with a watertight
panel of industrial type in painted cast iron, with PLC, contactors, relays, terminal boards,
and every cables necessary for the plant operation.
On the door of the control panel stand the operating desk, the switches and the warning
lights of the different components.

Painting
ARRAS MAXEI oil treatment plant type MAS 2000 TEC is painted in white (RAL9002).

Approximate dimensions
Length in Width in Height in Weight in
mm mm mm kg
Plant on platform with tarpaulin 2950 1900 2298 2600

Plant on skid with tarpaulin 2950 1900 2280 2600

Plant on low speed trailer with 2950 1900 2650 3000


tarpaulin
Plant on low speed trailer with 2950 1900 2640 3200
metallic cover
Plant on road trailer with tarpaulin 2950 1900 2930 3500

Plant on road trailer with metallic 2950 1900 2920 3500


cover
High transformer valve
High symetrical connection Auxiliairy inlet for MAS filling thanks to tanks
Teflon insulating ring or inlet for traditionnal treatment
Driven opening valve
6 µm absolute filtration

G3
Optional : on-line water content measuring
V23
B3 (JN3)
Mano 4

V2

CdC V28 Clap


T°1 TS PS1 ID PIR

VP3 CAR3 F1 VP6


B5 (JN5)
VP12
P1
RAO13
G2 BP V4 V5 V10 Mano 1 V11
V3 V8 NHCS
V25 V13
B6 (JT6,CI6)
B8 (JN8) CH Reg IC Mano 2
TE V12 V14'
M1 SS1
VP7
RAO25
PV ACCU

V14

RASCH
SCD
B7 (JN7) VP9
T1 T2
V20
DM

SCAH DEGAZ

VP2

VP4

RAO1 PT1
SCAB

M3D
V1

G1

B4 (JN4)
B2 (JN2)
M2
VP1
PS2 T°2
Oil level in MAS NHG
B1 (JT1,CI1) retention tray
VP11 F2 CAR1
CAR2
I–BETH39GB_C page 5/6

P2
V18
Low symetrical connection
V19' V17
Low transformer valve V16 V15

G4
Oil level in V19
Alarm switch transformer
Buchholz warning
MAS 2000 TEC (optional)
switch : NO
: NO Auxiliairy outlet for MAS draining in tanks
1 µm absolute filtration (optional)
or standard treatment outlet
ARRAS MAXEI
OIL TREATMENT
TYPE MAS 2000 TEC

All characteristics may be modified without any prior notice.


I–BETH39GB_C page 6/6 OIL TREATMENT TYPE MAS 2000 TEC
ARRAS MAXEI

Optional features
The process controls AUTOMATIC DRAINING OF THE VALVE
This option enables an optimal protection of the vacuum net of the plant.
VOLTMETER / AMMETER
This option will enable you to visualize the power supply of the plant, as well as the strength developed in order to protect the net
and equipment.
REMOTE CONTROL
The remote control enables to be informed of the plant operation through an internal phone line, a TELECOM phone line, or through
the GSM network.
RECORDER
This option enables to record the physical parameters of the degassing process like temperature and vacuum level.
CONTINUOUS MOISTURE CONTENT MEASURING
This option has been designed to carry out on-line moisture content measurement, that means continuously during the oil treatment.
Then you reduce the errors linked to the sampling method and the risks due to hot oil handling.
REGENERATION
This option enables to regenerate the oil and to decrease its acidity thanks to absorbent and colloidal properties product.

Digital recorder

Telecontrol GSM

The presentations 1) LOW SPEED TRAILER


The oil treatment can be installed on a low speed trailer with full tyres (max. speed : 20 km/hr).
2) ROAD TRAILER
The oil treatment plant can be installed on a road trailer. The trailer is equipped with rear lights in accordance with the EU regula-
tions of road code. The whole installation is commissioned by the French government vehicle testing service to be allowed to circu-
late in France and in the European countries.
3) TARPAULIN PROTECTION
The plant can be equipped with a protection type tarpaulin, which protects it from bad weather.
The tarpaulin can be opened on the four sides thanks to its panels to enable the access to all the components of the plant.
Options
4) METALLIC COVER PROTECTION
Regeneration The plant can be equipped with a metallic cover type protection, which protects it from bad weather. It is made of aluminium and the
frame is made of iron steel. The side panels open horizontally, close per key and are maintained thanks to gas jacks. The panels en-
able the access to the components of the plant.

Road trailer with metallic cover Low speed trailer with tarpaulin Skid with tarpaulin

You might also like