Taj Uruk M 76 6405
Taj Uruk M 76 6405
Contractor:
Design Subcontractor:
Document title:
Fire Pump Set Calculations as per NFPA
B. Theoretical Calculations of Water Spray Cooling System for LDO Storage Tank:
D. Theoretical Calculations of Foam System using Foam Monitors For Dyke Wall
Risk Area 1 :
Risk Area 2 :
Risk Area 3 :
Water Storage Tank Capacity for the duration of 30 Minutes = 165000 Liters
Risk Area 4 :
Water Storage Tank Capacity for the duration of 120 Minutes = 319440 Liters
Largest Risk Area is Dyke Wall using Foam Pourer = 9475.20 Lpm
= 13345.2 Lpm
Maximum Theoretical Pressure Required is for Foam Monitor & Fire Hydrant = 7 Bar
The Fire Water Storage Tank capacity shall be capable of feeding largest risk area
in addition to flow of two hydrants
Largest Risk Area is LDO Storage Tank with Foam & Water Spray System = 505960.5
Liters
Hence the Fire Water Tank Capacity = 505960.5 Liters + 453600 Liters
= 959560.6 Liters (959.56 M3)
Also this is a theoretical calculation actual hydraulic calculations have been done
to achieve the accurate pump capacity.
Summary:
Fire Pump Set Capacity (Theoretical) 13345.2 Lpm (800.7m3/hr).
Maximum Theoretical Pressure Required 7 Bar
3% AFFF Foam Concentrate Tank with reserve (8790 Liters x 2)
capacity For the operation of Largest area = 17580 Liters
which is foam pourers for dyke wall for a
duration 30 minutes as per (NFPA11, Table
5.7.3.2 Class I hydrocarbon)
Water Storage Tank Capacity X1.1 1055516 Liters (1055 M3)