Professional Documents
Culture Documents
RS1069 - Improved Methods For Condensate Cooling Calculations in TASC
RS1069 - Improved Methods For Condensate Cooling Calculations in TASC
J M McNaught
HTFS/NEL
East Kilbride, Glasgow
ABSTRACT
This report describes methods developed to improve the prediction of condensate cooling in TASC 5.00. The
improvements apply to cooling over the condensing range and to cooling below the bubble point. Particular
attention is focused on horizontal shellside condensation, where the condensate tends to separate from the vapour.
The Silver method is adapted so that the surface area requirement for cooling of the condensate over the condensing
range can be estimated. The implications of the new methods are illustrated with reference to example cases.
29
where αf is the combined heat transfer coefficient for An alternative way of expressing equation (7) is
the coolant, tube wall and fouling, αc is the
condensate heat transfer coefficient, αg is the ∆A = ∆ Q U ′(T − t ) (8)
coefficient for the gas phase flowing alone, and Z is where
given by 1 F 1 − FC
= C + (9)
Z = x g C pg
dT
(2) U ′ UC UL
dh
and
FC = (∆Q − ∆QL ) ∆Q (10)
There is no direct account taken anywhere in the
method of the heat transfer coefficient that applies to
The local overall heat transfer coefficient UC is given
the required cooling of the liquid phase along the
by
heat release curve. In effect it is being assumed that
1 1 1 ZC
the controlling resistances are the gas phase and the = + + (11)
UC α f αc α g
condensate, and that the accumulated condensate
remains in good contact with the tube wall.
where ZC is defined by
These assumptions are generally thought to be
dT
reasonable for configurations such as vertical Z C = x g C pg (12)
dh − dhL
tubeside condensation. However the assumptions are
probably not reasonable for configurations in which UL is given by
the condensate tends to separate from the vapour, for
1 1 1
example horizontal shellside condensation. This = + (13)
UL α f αL
situation is considered in Section 3 below.
3. SEPARATED FLOW OF VAPOUR where αL is the liquid heat transfer coefficient for the
AND CONDENSATE condensate cooling region.
FNAT =
(1 + B ) 1 + Bx g ,in
ln
1
−
( )
The subscript C refers to the condensing (+gas (14)
B x g ,in − x g ,out
2 1 + Bx g ,out B
cooling) region, and the subscript L refers to the
liquid cooling region.
where
0.556
ρ
0.111
A mean heat transfer coefficient U can be defined by ηg
B= l
η
−1 (15)
ρg
l
∆A = ∆AC + ∆AL = ∆ Q U (T − t ) (6)
30 RS1069
Z 1 α L = min( α C ,α L ) (19)
+ (1 − FC )
1 1 1
= + FC C + (16)
U′ α f
α g αc αL
5. HEAT TRANSFER COEFFICIENT
FOR LIQUID COOLING
There are many approximations and simplifications
inherent in this equation, the principal approximation The methods for the coefficient αL for liquid cooling
being that the temperature differences for the in condensers are described below for the various
condensing and subcooling regions are equal. configurations.
However the equation has the advantage that it is 5.1 Vertical Tubeside Condensation
correct for the two extremes of condensation with no
condensate cooling and liquid cooling with little 5.1.1 Cooling over the condensing range
condensation.
The heat transfer coefficient for liquid cooling in
vertical tubeside condensation is evaluated as
Working equations for FC and ZC are:
follows:
(
FC = 1 − 1 − x g C pl) dT
dh
(17) 1. Calculate the void fraction εg in the channel.
and 2. Calculate the mass flux in the channel for the
dT liquid phase flowing alone
x g C pg
dh 3. Multiply the liquid-alone mass flux by 1/(1 - εg)
ZC = (18)
(
1 − 1 − x g C pl ) dT
dh
4. Calculate the heat transfer coefficient αCC using
the mass flux evaluated at step 3 above
5. Calculate the heat transfer coefficient αFF
4. COMBINED LIQUID COOLING AND assuming gravity-controlled film flow
CONDENSATION
When the vapour and liquid flow in contact with the It is possible for the user to specify that the falling
same surface, it is reasonable to retain the current film coefficient is used throughout. In this case the
assumption that liquid cooling is not the controlling coefficient αL is simply set to αFF.
resistance. However the current implementation of
Silver’s method has the problem that it does not If a falling film coefficient is not specifically
extrapolate correctly to the case where there is very requested by the user, then the two-phase flow
little heat transfer due to condensation, and the liquid pattern map in HTFS Handbook Sheet TM1 is used
cooling dominates. to decide whether or not the flow pattern is annular
(shear-driven or falling film). The larger of αCC and
It is difficult to set up tractable equations that αFF is used if the predicted flow pattern is annular.
describe simultaneous gas cooling, condensation and (Note that in a shear-driven annular flow αCC could
condensate cooling to the same surface. It may be be taken to represent a shear-controlled annular film
adequate to formulate an equation that gives the coefficient). If the predicted flow pattern is plug or
correct results in the limits of zero- and all-liquid bubbly, the coefficient αCC is used. Interpolation
cooling, and gives sensible interpolation between the between the two coefficients is used if the flow
limits. pattern is oscillary.
Equation (16) fulfils this role. However it would not It seems that in common condensation applications
be expected that the coefficient αL used in equation the liquid superficial velocity is relatively low, with
(16) would exceed the local condensate heat transfer the result that the predicted flow pattern from Sheet
coefficient. Therefore the following limit should be TM1 is almost always annular.
applied before equation (16) is evaluated:
31 RS1069
5.1.2 Cooling below the bubble point The approach taken is to apply the separated flow
equation (11), with the heat transfer coefficient αL set
For condensate cooling below the bubble point, it is
to the coefficient αCC obtained as in Section 5.1.
also possible in TASC 5.00 for the user to specify a
falling-film calculation. The default calculation, 5.3 Horizontal Shellside Condensation
introduced in TASC 4.10, attempts to allow for the
In horizontal shellside condensation it will be
fact that some of the condensate cooling will actually
assumed that all the liquid cooling occurs in
take place in parallel with condensation. The method
separated flow. Therefore the methods of Section 3
is as follows:
above apply.
4. Calculate a revised liquid flowrate M& lR from 5.4 Vertical Shellside Condensation
32 RS1069
This variable is summed over the exchanger(s), A warning is generated to the effect that only 32% of
added to the corresponding value for cooling below the subcooling duty is likely, and that the calculated
the bubble point, and its integrated value compared number of tubes that are naturally submerged is 10,
with FNAT. A warning is printed if the integrated but the number of tubes that must be submerged to
value is greater than FNAT. achieve the subcooling duty is 33.
Also, the user can utilise a new input item in TASC There is no facility to re-submit the data with
5.00 to specify a fixed fraction of the tubes that are revisions to the input data to remove the warning
submerged. message.
A comparison of the TASC 4.11 and TASC 5.00T This extreme example shows that because the liquid
predictions for a case with subcooling below the velocity decreases as the liquid level is increased, the
bubble point is shown below actual surface area required for subcooling is very
large. It shows that the subcooling would be much
TASC 4.11 more effectively accomplished in a separate
Mean shellside heat transfer coefficient: 5799 exchanger specifically designed for the purpose.
W/m2K
Area ratio: 1.37
33 RS1069
7.2 Condensate Cooling Over the Condensing fraction of tube submergence is specified in the
Range input
34 RS1069