Professional Documents
Culture Documents
LESSON 2 - Wires and Cable Layout
LESSON 2 - Wires and Cable Layout
Cabling or wire pulling, also known as fishing, is the process in which wires and cables are inserted inside the conduit. According to PEC, only
40% of the area of the conduit must be occupied by the conductors to provide space for ambient temperature.
The table below from the NEC shows the maximum number of allowed conductors to be placed inside an Electrical Metallic Tubing:
SPLICING OF WIRES AND CABLES
Splicing or joining by interweaving conductors inside the raceway is prohibited because wire pulling becomes difficult to conduct. Instead,
splicing must be performed in a splice box except for direct-buried conductors or cables, which can be spliced or tapped without using splice
boxes.
There must be at least 100 mm distance between all conductors inside the building and the conductors of any electric light, power, or signaling
circuit.
If the opening to an outlet, junction, or switch point is smaller than 200 mm in any dimension, each conductor must be long enough to extend at
least 75 mm outside the opening.
INSULATED FITTINGS
Raceways containing 22 mm2 or larger ungrounded conductors that enter a cabinet, box enclosure, or raceway must have the conductors
protected by a substantial fitting with a smoothly rounded insulating surface unless the conductors and the fitting or raceway are separated
from each other through a securely fastened substantial insulating material.