You are on page 1of 5

REMARKS:

Revision Description Date Approved


DRAWN BY: MNOOR DATE:
DESIGNED BY: MEL DATE:
CHECKED BY: SUHAIMI DATE:

REVIEWED BY: ANIDA DATE:


OWNER'S/CLIENT :

TENAGA
NASIONAL BERHAD

OWNER'S ENGINEER:

TENAGA
NASIONAL BERHAD

CONTRACTOR:

SUPPLIER :

PROGRESSIVE
IMPACT TECHNOLOGY. SDN. BL HD. (240206-U)

PROJECT TITLE:

CONTRACT No.:
TENDER No.:
SUBSTATION

DRAWING TITLE

DRAWING MULTIFUNCTION METER

+ /A1

For For Revised Updated


PRELIMINARY REVIEW APPROVAL "AS-MANUFACTURED" "AS-BUILT" DRAWING NO.: REV.: THIS SHEET: 01
(After 'FAT') (After 'SAT')
0 NEXT SHEET: 02
DATE SHEET NO. REVISION NO. DESCRIPTION OF CHANGE

PROGRESSIVE
IMPACT TECHNOLOGY. SDN. BHD. (240206-U)
NO TITLE DRAWING NO. SHEET NO. REVISION NO. DATE

1 COVER SHEET 01 0 27.07.21


2 REVISION HISTORY 02 0 27.07.21
3 TABLE OF CONTENTS 03 0 27.07.21
4 MULTIFUNCTION METER DRAWING - MULTIFUNCTION METER LIST 05 0 27.07.21
5 MULTIFUNCTION METER DRAWING - MULTIFUNCTION METER SPECIFICATION 06 0 27.07.21

PROGRESSIVE
IMPACT TECHNOLOGY. SDN. BHD. (240206-U)
MEASURED CLASS AUX MEASURED INPUT
MAKE MODEL CT AND VT RATION
PARAMETER INDEX SUPPLY RANGE RANGE

CURRENT (A) MC740 0 - 1440A


0.2 CURRENT
VOLTAGE (V) ISKRA MC740 AND VOLTAGE 0-150kV 0 - 1.0A CT : 1200/1A

MW (MW) MC740
0.5 MW
AND MVAR
110VDC
-300 0 +300 MW 0 - 150V √3 / /
VT:3x132000V 110V 110V
√3 √3
MVar (MVar) MC740 -300 0 +300 MVar
CURRENT (A) MC740 0 - 1440A
0.2 CURRENT
VOLTAGE (V) ISKRA MC740 AND VOLTAGE 0-150kV 0 - 1.0A CT : 1200/1A

MW (MW) MC740
0.5 MW
AND MVAR
110VDC
-300 0 +300 MW 0 - 150V √3 / /
VT:3x132000V 110V 110V
√3 √3
MVar (MVar) MC740 -300 0 +300 MVar
CURRENT (A) MC740 0 - 480A
0.2 CURRENT
VOLTAGE (V) ISKRA MC740 AND VOLTAGE 0-150kV 0 - 1.0A CT : 400/1A

MW (MW) MC740
0.5 MW
AND MVAR
110VDC
0 TO 100 MW 0 - 150V √3 / /
VT:3x132000V 110V 110V
√3 √3
MVar (MVar) MC740 0 TO 100 MVar
CURRENT (A) MC740 0.2 CURRENT 0 - 3600A 0 - 1.0A
CT : 1600/1A
AND VOLTAGE
VOLTAGE (V)
FREQUENCY (HZ)
ISKRA MC740
MC740
0.5 MW
AND MVAR
110VDC
0-150kV
44-55HZ MW
0 - 150A
0 - 150V
√3 / /
VT:3x132000V 110V 110V
√3 √3

CURRENT (A) MC740 0 - 1440A


0.2 CURRENT
VOLTAGE (V) ISKRA MC740 AND VOLTAGE 0-150kV 0 - 1.0A CT : 400/1A

MW (MW) MC740
0.5 MW
AND MVAR
110VDC
-300 0 +300 MW 0 - 150V √3 / /
VT:3x132000V 110V 110V
√3 √3
MVar (MVar) MC740 -300 0 +300 MVar

PROGRESSIVE
IMPACT TECHNOLOGY. SDN. BHD. (240206-U)
MULTIFUNCTION METER MC 740

MC 740
Multifunction Meter Iskra
TRANSDUCER SPECIFICATION
GENERAL INFO
UNIVERSAL POWER SUPPLY 20 V−300 VDC or 48 V − 276 VAC
ACCURACY CLASS Class S according to EN61000-4-30
OEM ISKRA
TRANSDUCER TYPE/MODEL MC740-SUENNBC
COUNTRY OF MANUFACTURER SLOVENIA
FUNCTION MULTIFUNCTION METER
MEASUREMENT MORE THAN 140 QUANTITIES
(U, I, P, Q, S, PF, PA, f, φ,
THD, MD, ENERGY, ENERGY COST BY TARIFFS, ETC.).
COMMUNICATION PORT SERIAL, ETHERNET AND USB
SOFTWARE CONFIGURE MIQEN

BASIC SPECIFICATION
FREQUENCY WIDE RANGE 16-400hz
ACCURACY CLASS VOLTAGE AND CURRENT ACCURACY = 0.2
POWER ACCURACY = 0.5
VOLTAGE RANGE 1000 Vrms
CURRENT RANGE 12.5A

TERMINAL CONNECTION
STANDARD MEASUREMENT INPUT
NORMINAL FREQUENCY RANGE 50 Hz, 60 Hz
CURRENT NOMINAL VALUE 1 A, 5 A
CURRENT MAX. MEASURED VALUE 12.5 A sin.
(I1- I3 ONLY)
TRANSDUCER SPECIFICATION 0.01 Ω per phase
CURRENT CONSUMPTION
PIN NO. DESCRIPTION VOLTAGE NORMINAL VALUE 500 VLN , 866 VLL
1/3 CURRENT 1 (IL1) VOLTAGE MAX. MEASURED VALUE (CONT.) 600VLN; 1000VLL
4/6 CURRENT 2 (IL2) VOLTAGE CONSUMPTION 4.2MΩ PER PHASE
7/9 CURRENT 3 (IL3)
2 VOLTAGE 1 (UL1)
5 VOLTAGE 2 (UL2)
8 VOLTAGE 3 (UL3) STANDARD MEASUREMENT INPUT ACCURANCY ± OF READING
11 VOLTAGE NEUTRAL (UN) VOLTAGE L-N,L-L ± 0.2%
13 POWER SUPPLY + / AC (L) CURRENT ± 0.2%
14 POWER SUPPLY – / AC (N) ACTIVE POWER (IN = 5 A) ± 0.5%
12 GROUNDING ACTIVE POWER (IN = 1 A) ± 0.5%
ACTIVE ENERGY Cl. 0.5S
USB-
TYPE B
REACTIVE ENERGY Cl.1
FREQUENCY (F) ± 0.01 Hz
POWER FACTOR (PF) ± 0.5%
RJ45
THD (U) ± 0.3%
THD (I) ± 0.3%
REAL TIME CLOCK (RTC) < ± 1s/day

PROGRESSIVE