User Manual
www.flsmidth.com/automation
csc@flsmidth.com
Disclaimer:
The information in this document is subject to change without notice and should not be construed
as a commitment by FLSmidth A/S. FLSmidth assumes no responsibility for any errors that may
appear in this document.
In no event shall FLSmidth be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall FLSmidth be liable
for incidental or consequential damages arising from use of any software or hardware described in
this document.
Options specified and described in the FLSmidth documentation as part of the general description -
but initially neither ordered by the customer nor confirmed by the seller - will not commit the
supplier to any further and future supply and/or installation.
The software described in this document is furnished under a license and may be used, copied, or
disclosed only in accordance with the terms of such license.
1. Introduction 4
1.1 Purpose 4
1.2 Intended audience 4
1.3 How to use this manual 4
2. General Description 5
2.1 Alternate 5
2.2 Compressor Sequence 6
3. Dynamic Symbol 7
4. Alternate Faceplate 8
4.1 Tab: Status 8
4.2 Tab: Input & Output 10
4.3 Tab: Info 11
5. Related Manual 12
5.1 Related Manuals 12
1.1 Purpose
This manual explains the functions of the ECS/ACESYS V8 Alternate Faceplate
functions for ECS/ControlCenter V8.
2.1 Alternate
The sequencer is intended to auto start and load of up to 10 compressors.
Basically the sequencer will start/stop compressors (auto start) and load/unload
the compressors based on an output from a PID in the range 0-100%. This PID
output is converted to a number of compressors to be loaded
The operator selects the compressors that will be available to the sequencer by
tacking them in the faceplate. Increasing/decreasing the number of active
compressors is conducted following a priority. The priority can be selected to
follow a manual priority entered by the operator, or an automatic priority
based on the actual running hours for the compressor motor. Summering of
operation hours is carried out by the compressor sequence block, when the load
request is set for the specific compressor.
In automatic priority the compressor with the lowest hour count will become the
highest priority.
A priority change will also take place; if a compressor is lost by the result of a
fault or if a compressor is selected or deselected
Only compressors that are auto started and unit OK will participate in the priority.
To protect the MCC/MDB against overload the sequencer will only allow one
compressor to start at the time. A delay can be set from the faceplate. The delay
is always used both when loading and unloading.
When stopping a compressor the compressor will be unloaded, but the auto start
request will remain high a time selected from the faceplate. This delay is to avoid
rapid start/stop of the compressor.
The sequencer works together with the normal group control. The compressors
must be selected in the faceplate of the sequencer and then started by the group.
If a full stop is wanted the group can be stopped in the normal way. But besides
this it is also possible to start and stop the compressors by selecting / deselecting
them in the sequencer faceplate, after an “operator select / deselect” the
operator is prompted and has to confirm the action. (This ensures a 2 step
command before start/stop).
Compressor status
Selected operation form
Operating hours
Actual pressure
Pressure set point
1 2 3 4
9
8
1 2