Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


909 Supply, Installation, Testing & Commissioning of 24 Port POE+ Access Switches with switching Nos 5
capacity of 128 Gbps, forwarding performance 95 Mpps, having 24 x 10/100/1000BASE-T PoE-
plus(RJ45) with minimum PoE budget of 370W and 4x 10G SFP+ uplink ports . Should support
min 2GB internal DRAM, 2GB internal Flash memory,32K MAC address, 1K IPv6 Multicast
Routes, Should have static Routes from day 1.One year support. Approved Make : Cisco/
Impulse / Juniper / Extreme/ Arista
910 Supply, Installation, Testing & Commissioning of 4TB HD Approved Makes: WD, Seagate / Nos 5
Toshiba.
911 Supply, Installation, Testing and Commissioning of Full HD 65" LED Professional Display Panel. Nos. 5
Approved Makes: Panasonic, Sony, Samsung.
912 Supply, Installation, Testing and Commissioning of Workstation PC: Intel(R) Core(TM) i7-3770 Nos. 1
Processor (8M Cache, up to 3.90 GHz); Memory: 4GB, NON-ECC, 1600MHZ; RAM: 4GB
(1x4GB) Non-ECC DDR3 1600MHz SDRAM Memory; Keyboard: 12 function keys; Chassis:
Tower/Workstation; DVD: 8X Slimline DVD+/-RW, Data Only; 20" TFT Monitor; Dual Graphics
Card; Network interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000;
Hard disk: 250GB, 7200 RPM 3.5" SATA 6Gb/s Hard Drive; Operating system: Windows 7
Professional 64 Bit. Approved Makes: HP, Dell, IBM.
913 SH: IX: UPS SYSTEM Each 3
Supply, Installation, Testing & Commissioning of 80 KVA UPS in paralleling mode at 0.99 input
power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, Isolation
transformer as per specification given in the document with following broad features. THD(i) shall
be less than 3% in the entire loading range.
UPS shall carry design output at 40 deg.
Shall have soft start and hold of for incoming supply.
Invertor capability to supply 150% load for 5 sec.
Three Phase Input and Three Phase Output. (Input - 340V - 470V, Three Phase, 4 wire. / Output -
400-415 Volt, Three Phase, 4 Wire.)
Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt
cells.
Battery shall be external type with rack and suitable for 30 minute backup on 100% load.
UPS shall be compatible for 4 nos unit in parallel operation. (Synchronize). Parallel operation kit
shall be supplied with UPS.
Suitable size of cable from UPS to battery bank.
UPS described as above
914 Supply, installation, testing & commissioning of 20 KVA UPS at 0.99 input power factor with Each 1
SNMP card, compatible for BMS connectivity on backnet/MODBUS, inbuilt isolation transformer
as per specification given in the document with following broad features.
THD(i) shall be less than 3% in the entire loading range.
UPS shall carry design output at 40 deg.
Shall have soft start and hold of for incoming supply.
Invertor capability to supply 150% load for 5 sec.
Three Phase Input and Three Phase Output. ( Input - 340V - 470V, Three Phase, 4 wire. / Output
- 400-415 Volt, Three Phase, 4 Wire.)
Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt
cells.
Battery shall be external type with rack and suitable for 90 minute backup on 100% load.
Suitable size of cable from UPS to battery bank.
UPS described as above
915 Supply installation , testing & Commissioning of following rating of invertor with battery and Each 1
trolley as complete as required. Invertor shall be suitable for 90 minute backup on full load as
per specification.
1000 VA, 220 Volt