Professional Documents
Culture Documents
MANUAL
Multiple Installation Controller
T519-998-9130
Operation Manual Code No.
(E130-002-0940)
Date of preparation: May 2012
Important Safety Information
Before using the Multiple Installation Controller(*) (Pressure Controller MP1-200/MI Terminal MT1-200),
ensure that this operation manual is read and fully understood; furthermore, the instructions given herein
should be strictly observed during operation.
The Multiple Installation Controller(*) contains high voltage sections that could cause electric shock.
Failure to use the controller in the appropriate manner can, therefore, result in death, injury, the outbreak
of fire, and other serious accidents.
In order to ensure that tasks undertaken during operation and maintenance of the Multiple Installation
Controller(*) can be completed safely, it is critical that all dangerous and hazardous parts of this
equipment be confirmed in advance. Here at MIURA, it is practically impossible to anticipate all
potentially dangerous situations, and therefore, this operation manual deal only with known hazards. A
higher level of safety can be achieved by carefully observing the warnings and instructions set forth
herein.
Safety- and damage-related warnings are classified into the following three levels, and notification of
these warnings is provided within this operation manual and using warning labels(*) on the Multiple
Installation Controller(*) itself.
Indicates a situation which might cause serious injury or death to the user, if
the product is mishandled.
Indicates a situation which might cause minor injury to the user or the
occurrence of physical damage only, if the product is mishandled.
If any part used in the product fails, contact our sales office to replace it with its genuine part. Using parts
of different models might reduce safety.
It should be noted that unauthorized alteration of the Multiple Installation Controller (*) or repair
procedures other than those described herein can pose a serious safety risk. Never make any
modifications or repairs without MIURA’s permission.
i
Introduction
Introduction
This document describes the methods of handling a Multiple Installation Controller(*) to ensure its proper
use.
Not only those who use the Multiple Installation Controller (*) for the first time but also those who know the
handling methods should read this document carefully and understand the proper handling methods
before use of the Multiple Installation Controller (*).
Furthermore, we also recommend that this Operation Manual be stored in a specially designated location
so that it can be referred to at any time to confirm the correct usage.
[Explanation of Notation]
The meanings of the symbols used in this manual are as shown below.
Indicates a caution.
ii
Definition of Terms
Definition of Terms
The following are the meanings of terms used in this operation manual. (Indicated by (*) in the text).
Terms Details
Multiple installation (MI) To automatically operate the quantity of boilers among several installed
control boilers that corresponds to the required amount of steam.
Boiler number Serial numbers for boilers under multiple installation control.
iii
Table of Contents
Table of Contents
Important Safety Information ....................................................................... i
Introduction ................................................................................................. ii
Definition of Terms ..................................................................................... iii
iv
Table of Contents
v
Table of Contents
vi
SECTION 1 SAFETY
SECTION 1 SAFETY
1. Safety Regulations
Handling of the Multiple Installation Controller(*) is comprised of operations associated with running of
the equipment and operations regarding maintenance.
The Multiple Installation Controller(*) should be operated by persons who were given explanations of the
operation with this operation manual.
3. Protective Equipment
Wear protective items such as a helmet and safety footwear as required for the task.
1
SECTION 1 SAFETY
2
SECTION 1 SAFETY
6. Safety Precautions
6.1 Safety Precautions for Installation
The following safety precautions apply to installation.
WARNING
Pressure Controller MP1-200
Ensure that a dedicated circuit breaker (with overcurrent protection) is installed
on the main power supply line.
Wiring
MI Terminal MT1-200
Ensure that the main power supply line is wired from the boiler power supply line.
For installation of the power supply of the main power supply line, connect wires
with the specified diameter and ensure that they are grounded.
Ground
アース端子 terminal
3
SECTION 1 SAFETY
WARNING
Do not perform this procedure with wet hands.
Failure to observe this precaution can result in high-voltage electric shock and
Wet Hands
injury or death.
Prohibited
6.3 Safety Precautions for Relocation or Resale (excerpt from page 51- of the text)
WARNING
Ensure that the boiler is installed only in the specified condition and connected to
the specified peripheral equipment.
Failure to observe this precaution may result in injury.
4
SECTION 2 OVERVIEW
SECTION 2 OVERVIEW
1. Product Overview
1.1 Features and Functions
This unit automatically determines the optimum number of boilers to operate in consideration of the
load and operates the required number of boilers in descending order of priority(*). The major features
are as follows.
This unit efficiently operates 15 boilers at maximum depending on the pressure status detected
by the pressure sensor installed on the steam header.
The boiler can reduce unnecessary start and stop by setting the quantity of low fire standby units
depending on loading condition.
When something goes wrong with one of the boilers, this unit performs MI control(*) on the rest of
the normal boilers. This enables the unit to perform a stable MI control(*) at a boiler abnormality.
The automatic rotation(*) function determines combustion priorities(*) for the boilers according to
the cumulative combustion time of the boiler, which enables automatic equalization of boiler
combustion time.
The blowdown time can be notified with the indication lamp by setting the blowdown timing. After
performing blowdown, the boiler can be operated temporarily on a priority basis to prevent the
corrosion of the boiler pressure vessel.
The boiler can be turned on and off once a day by timer function. Setting can be performed
separately for each boiler under automatic operation(*).
By installing an optional pressure sensor onto the MI Terminal MT1-200 of each boiler, the
pressure can be controlled at almost the same level as automatic operation(*) even when the
boiler is under manual operation(*). The unit can respond to a sudden load change by keeping
the boilers at a constant pressure during standby.
The MI controllers(*) are connected only by two-core twisted pair cables(*) and the quantity of
boilers to be controlled can be changed by setting. This facilitates additional installation of
boilers after introduction of MI controllers(*).
5
SECTION 2 OVERVIEW
1.2 Configuration
As shown in the following figure, the unit is composed of a steam header that collects steam from the
boilers, a pressure sensor that monitors steam pressure of the steam header, a Pressure Controller
MP1-200, steam boilers controlled under MI control(*) and MT1-200 units that control the boilers.
The Pressure Controller MP1-200 performs monitoring on steam pressure of the steam header to
determine the most efficient combustion condition depending on the status of load change.
The MI Terminal MT1-200 receives information from the Pressure Controller MP1-200 to determine
the priorities(*), thus performing combustion control on the boilers.
6
SECTION 2 OVERVIEW
1.3 Specifications
1.3.1 Common Specifications
7
SECTION 2 OVERVIEW
Monitor output:
Terminal
Output name Signal type
number
Sensor fail 9-10
Communication status 10-11
Boiler operation 12-13
Alarm 13-14 Normally open dry contact
Emergency stop 15-16 Contact rating: 250 VAC / 1 A (resistance load)
Boiler trouble 16-17
Pressure alarm L 18-19
Pressure alarm H 19-20
8
SECTION 2 OVERVIEW
9
SECTION 2 OVERVIEW
When operations such as configuration are performed with the front panel opened, do not touch
undesignated portions such as the terminal blocks or parts on the circuit board. It can cause an
electric shock or failure of the equipment.
The main unit front panel and the base plate must be locked. To remove the front panel, hold it with
both hands and pull it. See the figure below for internal construction.
10
SECTION 2 OVERVIEW
NOTE
You are not able to use TIMER FUNCTION if the local code does not allow you to use it.
11
SECTION 2 OVERVIEW
2.2.2 Internal Structure
Do not carry out internal setting with the top cover of the main unit open. A touch on the internal
terminal blocks or parts on the circuit board results in an electric shock or mechanical problem.
An error in setting leads to malfunction. Do not open the top cover except for special cases
such as installation check.
12
SECTION 3 OPERATION
SECTION 3 OPERATION
1. Operating the Pressure Controller MP1-200
1.1 Normal Operation
a) Display control
When the “DISPLAY CHANGE” switch is pressed, items on the display change as shown below.
The left end of LED indicates the type of the display item.
13
SECTION 3 OPERATION
NOTE
The boilers under manual operation(*) will not stop.
If the MI Terminal MT1-200 is installed with the optional pressure sensor, all stop
operation cannot stop the boiler under automatic operation(*) from performing
combustion until the standby pressure is reached.
NOTE
Any boilers which have been stopped by the MI Terminal MT1-200 will not perform
combustion.
Any boiler whose boiler steam pressure exceeds the steam pressure setting (high)
or whose combustion SW or operation switch is turned off will not perform
combustion.
All combustion is impossible during all stop or emergency stop input.
14
SECTION 3 OPERATION
15
SECTION 3 OPERATION
This section specifies the operation method for setting the switches within the main unit and
the pressure sensor adjusting value.
Failure to observe the setting procedures may cause control problems. Ask MIURA
representatives for setting and operation or perform the operation upon consulting.
2) SW1-4
Set output conditions for communication status
external output.
OFF: The output contact closes in the event of
a communication error in any of the
connected MT1-200 units.
ON: The output contact closes during normal communication with any of the connected
MT1-200 units.
3) SW1-5, 6
Set a connected pressure sensor type.
SW1 Maximum steam pressure
5 6 MPa {kgf/cm2}
OFF OFF 0.98 {10.0}
ON OFF 1.96 {20.0}
OFF ON No setting is allowed
ON ON 2.94 {30.0}
4) SW1-8
Set a steam pressure unit. See the “4. Display Unit Change Function” for details.
P.46
16
SECTION 3 OPERATION
5) SW1-1, 3, 7 (Switches other than those above)
Fix the SW1-1 to ON and other switches to OFF.
P. 36
17
SECTION 3 OPERATION
e) Zero adjustment, zero adjustment 2, gain adjustment Pressure sensor adjustment
When the local use environment causes a deviation in the steam pressure display from the
actual value, there is a need to perform settings for both zero adjustment and gain adjustment.
There is no need to adjust zero adjustment 2.
Contact MIURA maintenance personnel for this operation.
18
SECTION 3 OPERATION
Priority(*) (Example: 1)
Header steam pressure (Example: 0.85MPa)
SELECT
SELECT
SELECT
SELECT
SELECT
Under-judgment alarm
SELECT
* This is indicated only during alarm judgment.
NOTE
Pressure (header steam pressure, boiler steam pressure) is displayed in “MPa”, “kgf/cm2”, or
“psi”. The position of the decimal point varies depending on the pressure unit.
P.46
19
SECTION 3 OPERATION
b) Automatic/manual change
Press the “AUTO” switch to change the boiler operation from either automatic operation(*) under
MI control(*) or manual operation(*) by means of the boiler's steam pressure setting.
The “AUTO” LED turns on in automatic operation(*) mode.
P.28
Combustion under timer control ..... The “TIMER” LED turns ON.
Boiler stops under timer control ..... The “TIMER” LED blinks.
Timer control OFF .......................... The “TIMER” LED turns OFF.
NOTE
You are not able to use TIMER FUNCTION if the local code does not allow you to use it.
20
SECTION 3 OPERATION
1) Press the “SELECT” switch as many times as needed to display the desired setting information.
2) Press the “UP” and “DOWN” switches simultaneously.
(The area that allows setting starts blinking.)
3) Press the “UP” or “DOWN” switch to set the desired value.
4) Press the “SELECT” switch as many times as needed to display the digit to be changed.
Repeat 3).
When all the digits are set, the setting is finished with nothing blinking on the display.
The following four items can be set or changed;
Priority(*): ................................... See below.
Current time (hour, minute) ....... P.22
Day of the week ........................ P.22
Cumulative combustion time ..... P.23
Other displayed items are inalterable.
1) Press the “SELECT” switch as many times as needed to display the priority(*) and header steam
pressure.
2) Press the “UP” and “DOWN” switches simultaneously, and then the digit for the priority(*) starts
blinking.
3) Press the “UP” or “DOWN” switch to set the desired priority(*).
4) Press the “SELECT” switch to finish the setting.
21
SECTION 3 OPERATION
22
SECTION 3 OPERATION
NOTE
In the system where old and new boilers coexist, you can adjust the cumulative combustion
time to make the following operation implementable: Give higher priorities (*) to new boilers all
the time. Divide old boilers and new boilers into separate groups for automatic rotation(*).
Example: When two new boilers (No.(*) 1 and 2) and two old boilers (No.(*) 3 and 4)
coexist.
For example, set the cumulative combustion time for the boiler No. (*)1 and 2
to 0 and the boiler No. (*)3 and 4 to 1000.
Due to a shorter cumulative combustion time of the new boilers than that of
the old boilers, the new boilers (No.(*) 1 and 2) are given the first and second
priorities(*) respectively after automatic rotation(*). The old boilers are given
the third and fourth priorities(*).
There is no difference in the cumulative combustion time between the boiler
No. (*) 1 and 2, and between No.(*) 3 and 4, respectively. The rotation (*) is
performed to equalize the cumulative combustion time of boiler No.(*) 1 and 2,
and boiler No.(*) 3 and 4 respectively.
This condition will be held until the cumulative combustion time of the new
boilers exceeds that of old boilers. To hold this condition, set the cumulative
combustion time again.
23
SECTION 3 OPERATION
Setting can be performed as in same way as normal setting in the following procedures.
1) Press the “SELECT” switch as many times as needed to display the desired setting information.
2) Press the “UP” and “DOWN” switches simultaneously.
(The area that allows setting starts blinking.)
3) Press the “UP” or “DOWN” switch to set the desired value.
4) Press the “SELECT” switch as many times as needed to display the digit to be changed.
Repeat 3). When all the digits are set, the setting is finished with nothing blinking on the display.
NOTE
The information in the shaded box can be displayed and set only when an optional
pressure sensor is installed on the MI Terminal MT1-200.
24
SECTION 3 OPERATION
a) Steam pressure setting (high) (Option: Only when pressure sensor is installed)
This setting provides combustion stop pressure under manual operation(*). Under manual
operation(*), the boiler combustion stops when the boiler steam pressure rises to the set
pressure.
P.19
P.19
25
SECTION 3 OPERATION
c) Steam pressure setting (low) (Option: Only when pressure sensor is installed)
This setting provides high fire stop pressure under manual operation(*). Under manual operation(*),
the boiler shifts from high fire to low fire when the boiler steam pressure rises to the set pressure
during high fire.
Set the same unit as that of header steam pressure.
P.19
P.19
26
SECTION 3 OPERATION
P.19
P.19
27
SECTION 3 OPERATION
Tue
Thu
Sat
Fri
NOTE
You are not able to use TIMER FUNCTION if the local code does not allow you to use it.
28
SECTION 3 OPERATION
The relation between the setting value and operation ON/OFF is as follows.
3) When the ON time is the same as the OFF time (Turned ON all day long.)
OFF time
0:00 ON time 24:00
Operation
Previous Operation
day status
Previous Stop
day status
29
SECTION 3 OPERATION
Setting example
4) To turn on the boiler at a fixed time (8:00 in example), and stop by a customer.
ON time ...................... 8:00
OFF time .................... 13:00 (Set a time when the boiler should be stopped)
The timer operation causes the boiler to start firing at 8:00. Be sure to press “TIMER” between
8:00 and 13:00 to stop timer operation. (Disabling the timer operation allows the boiler to
perform combustion after 13:00.)
To stop boilers, press the “TIMER” switch to activate the timer operation.
5) To turn on the boiler by a customer and stop at a fixed time (17:00 in example)
ON time ...................... 13:00 (Set a time when the boiler should be in operation)
OFF time .................... 17:00
To start boilers, press the “TIMER” switch before 13:00 to stop the timer operation. (Stopping
the timer operation allows the boiler to start combustion.)
Press the “TIMER” switch between 13:00 and 17:00 to activate the timer.
(The boiler combustion continues as the time is after the ON time.)
The timer function causes the boiler to stop at 17:00.
30
SECTION 3 OPERATION
31
SECTION 3 OPERATION
j) Rotation(*) flag
Set the rotation(*) timing identification within the ranges of 0 to 9 and
A to F. P.38
The correspondences between the setting numbers and the
functions are as shown below.
0 : Automatic rotation(*) is not allowed.
1~7 : Set a rotation(*) interval by days.
The valid setting can be made only with the MI Terminal MT1-200 installed on the
boiler No. (*)1.
8 : Automatic rotation(*) is performed at a complete blowdown. All the boilers start
automatic rotation(*) at the press of the “B.BLOW” switch of the boiler in which the set
value is set to 8.
9 : If this value is set to a boiler, the priority(*) is fixed with the boiler. The priority(*) does not
change at automatic rotation(*) timing for other boilers.
Those boilers are given a new priority(*) other than the fixed boiler priority(*).
A to F : Set a rotation(*) at 1 to 12-hour intervals.
The valid setting can be made only with the MI Terminal MT1-200 installed on the
boiler No. (*)1.
The valid setting can be made only when an optional pressure sensor is installed.
after blowdown.
Set the time within the range of 0 to 9800 (about 2 hours and 43
minutes) in second units.
The priority combustion does not function after complete
blowdown if the time is set to 0.
33
SECTION 3 OPERATION
NOTE
Steam pressure (header steam pressure, boiler steam pressure, steam pressure setting (high),
differential setting (high), steam pressure setting (low), differential setting (low), holding-pressure
setting, differential setting (holding)) can be displayed in the units of MPa, kgf/cm2, or psi.
P.19
34
SECTION 3 OPERATION
b) Operation timing
Boilers are fired up or go on standby by the MI control(*) at one second intervals. To control power
supply, boilers are started at the minimum interval of three seconds (simultaneously start
prevention function).
35
SECTION 3 OPERATION
P.17
2) The boilers are started in the order of priority(*) (from the first priority(*)).
Header pressure
1 Low fire High fire High fire High fire High fire High fire High fire High fire
2 Low fire High fire High fire High fire High fire High fire
1 Low fire Low fire Low fire Low fire High fire High fire High fire High fire
2 Low fire Low fire Low fire Low fire High fire High fire High fire
3 Low fire Low fire Low fire Low fire High fire High fire
4 Low fire Low fire Low fire Low fire High fire
2) If more boilers than the set quantity of stand-by boilers continue low fire for over 15 minutes,
operation is stopped from the lowest priority(*) boiler in sequence, and the boilers with high
priority(*) are shifted to high fire.
Header pressure
1 High fire High fire High fire High fire Low fire Low fire Low fire Low fire
2 High fire High fire High fire Low fire Low fire Low fire Low fire
3 High fire High fire Low fire Low fire Low fire Low fire
4 High fire Low fire Low fire Low fire Low fire
36
SECTION 3 OPERATION
P.21
37
SECTION 3 OPERATION
The following shows operation when an alphabetical character from A to F is set to the rotation(*) flag.
Rotation(*) flag
Rotation(*)
setting
Every 1 Rotation(*) is performed on the hour.
hour
38
SECTION 3 OPERATION
NOTE
If the automatic rotation(*) function is utilized at intervals from 1 to 12 hours, it is necessary
to check the version of each MI Terminal MT1-200 and the Pressure Controller MP1-200.
Contact MIURA maintenance personnel for details.
39
SECTION 3 OPERATION
P.32
• The notification time for complete blowdown and soot blow can be set and notify
individually.
• To reset the value, press the “B.BLOW” or “S.BLOW” switches after the blowdown timing
is notified.
• This setting can be made within the range of 0 to 999 in hour units (high fire converted
combustion time). This function is not activated if the value is set to 0.
40
SECTION 3 OPERATION
20
19
18
17
16
15 7-8: All stop
14
Stop all the boilers
13 under MI control(*).
12
11
10
6-7: All combustion
9 Fire up all the
boilers under MI
control(*).
8
7
6 4-5: Alarm check
When the contact of the
5 alarm output (No. 14) is
4 closed, the output is
brought to stop.
3
2
1 2-3: Emergency stop
FG R S Stop the combustion
process of all the
communicating boilers.
1: S-phase output
Used to illuminate
the indication lamp.
P.16
b) Alarm confirmation input (Terminal block No.4 and No.5 input)
This control signal input has no impact on the MI control(*) function. When the Pressure Controller
MP1-200 provides an alarm output (terminal block No.14) due to abnormality in the boiler, this
input stops the alarm output.
41
SECTION 3 OPERATION
14: Alarm
8
The contact closes when any
7 contact of 15, 17, 18, and 20
6
above is closed.
5
12: Boiler operation
4
The contact closes when any
3 boiler's operation switch is
2 ON.
1
11: Communication status
FG R S The contact outputs the
communication status. The
operation varies depending
on the settings of the internal
“SWITCH 1”.
9: Sensor failure
The contact closes when a
pressure sensor failure is
detected.
42
SECTION 3 OPERATION
The pressure controller, model MP1-200, has several “dry” contacts available. On site wiring of
these outputs must be done by the customer or electrical contractor to fully utilize the available
features. All of the outputs require power from an outside source. The contacts are operated by a
relay mounted on the MP1-200. The relay contacts are rated for 250VAC, 1A. Output loads are
requested to be non-inductive. MIURA does not recommend installing an induction load, such as a
solenoid valve or transformer. If an induction load is to be connected, use an external relay
operated by the contact to avoid inductive kick on the MP1 circuit board.
P.16
When the SW1-4 is OFF
The contact closes if an MI Terminal MT1-200 has a communication error.
When the SW1-4 is ON
The contact closes if there is no problem in communication with all the MT1-200 units.
43
SECTION 3 OPERATION
e) Emergency stop output (Terminal block No.15)
This contact closes when an input is provided to the emergency stop input terminal (No.2 and 3).
The input logic of emergency stop can be changed with the “SWITCH 1”.
P.16
P.15
P.15
44
SECTION 3 OPERATION
P.25
b) Pressure holding
By setting a holding pressure to the MI Terminal MT1-200, the boilers can perform combustion up
to a certain pressure even though the boilers are under standby state during automatic
operation(*). (The pressure to hold the pressure constant is referred to as holding pressure.)
This function is effective in case of sudden fluctuations in load since the boilers under standby
can always keep pressure above a certain level.
P.27
45
SECTION 3 OPERATION
46
SECTION 4 BREAKDOWN AND COUNTERMEASURES
P. 13
b) If nothing above applies, defects in the pressure sensor and wiring or clogged piping are
possible causes.
Contact MIURA sales office.
P. 20
b) Check if the “AUTO” LED of the MI Terminal MT1-200 is blinking.
If the “AUTO” LED is blinking, the unit is in manual operation(*) mode due to the
communication error with the Pressure Controller MP1-200.
Check whether the power supply of the Pressure Controller MP1-200 is turned off or not. If
the power supply is turned on, there may be something wrong with the communication wiring.
Contact MIURA sales office.
P. 13, 15
47
SECTION 4 BREAKDOWN AND COUNTERMEASURES
b) Check if the setting of the boiler pressure is lower than the control pressure.
Set the pressure of the boiler pressure 0.1 MPa {1.0 kgf/cm2} higher than the control
pressure.
P. 20, 28
c) Check if the “LUMP OPERATION” or “EMERGENCY STOP” LED of the Pressure Controller
MP1-200 control panel is turned on.
The boiler does not start combustion when control signals are input to the all stop or
emergency stop terminal for external control. Turn off the switches provided outside to
cancel the boiler stop input.
If an earthquake detector is connected to the unit, the detector may be in the detecting
process.
Check the cause and then perform resetting.
P. 9, 41
P. 32, 33
48
SECTION 4 BREAKDOWN AND COUNTERMEASURES
P. 32
b) Check if the rotation(*) flag of the boiler, of which priority(*) does not change, is set to 9.
Priority(*) is fixed for the boiler of which rotation(*) flag is set to 9. Check for proper setting.
P. 32
d) Check if the cumulative combustion time is larger (or smaller) than that of other boilers.
Under the automatic rotation(*), the MI Terminal MT1-200 determines the priorities(*) of the
boilers in ascending order of the cumulative combustion time. Check the cumulative
combustion time.
P. 19
49
SECTION 4 BREAKDOWN AND COUNTERMEASURES
c) At backup control
In the following cases, the priorities(*) do not change.
• If any abnormality prevents the controller from controlling a boiler, the controller
does not count the boiler in the number of controlled boilers and allows the other
boilers with successive priorities(*) to fire up in order.
• The controller fires up the other boilers with lower priorities(*) temporarily during
pre-purge (especially when priority(*) is changed) to ensure stable operation.
When there is warning displayed on MI Terminal of MT1-200, Please see the chart below for how to
handle issues.
Pressing on the Select switch will reset the display windows.
Display Countermeasure
There is trouble in the machine. Please contact the maintenance
company.
MP1 is not functioning and the boiler operation has been switched to
manual operation.
50
SECTION 5 STORAGE
SECTION 5 STORAGE
1. Transfer or Resale
Ensure that the boiler is installed only in the specified condition and connected to the
specified peripheral equipment.
Failure to observe this precaution may result in injury.
When moving, reselling, or reusing the equipment, the location of installation and the facilities must
be confirmed to cause no trouble to normal operation of the equipment; contact a MIURA sales
office or your local dealer.
Inappropriate installation or unsuitable peripheral equipment may cause personal injuries. When
reselling our products, pass the operation manual and product-related documentation together on to
the next user.
51
SECTION 6 WARRANTY
SECTION 6 WARRANTY
1. Note Regarding Warranty
Miura Manufacturing America Co., Ltd., and Miura Boiler Co., Ltd., at its discretion, will repair or
replace at no charge (excluding shipping and labor charges) any Miura component, if found to be
defective in workmanship or material within twelve months from the date of commissioning or eighteen
months from the date of shipment from the factory, whichever occurs first.
All claims for the above warranty are to be presented in writing to a Miura factory or a Miura office for
review within 10 days of discovery of any defects.
The above limited warranty is given by Miura to the original purchaser only and is not assignable or
transferable to subsequent purchasers or lessees.
52
SECTION 7 APPENDIX
SECTION 7 APPENDIX
1. Purchasing Individual Operation Manuals
If you need the operation manual of the Pressure Controller MP1-200/MI Terminal MT1-200, contact
a MIURA sales office.
Have your operation manual code number on the cover ready when calling.
53
SECTION 7 APPENDIX
MEMO
54
MEMO