You are on page 1of 63

OPERATION

MANUAL
Multiple Installation Controller

Pressure Controller MP1-200


MI Terminal MT1-200

INFORMATION IN THIS MANUAL MAY BE


CHANGED WITHOUT NOTICE.

Ensure that this operation manual is fully


read and observed by all persons working
with the product.
Store this operation manual in a location
where it may be easily accessed by said
persons.

T519-998-9130
Operation Manual Code No.
(E130-002-0940)
Date of preparation: May 2012
Important Safety Information

Important Safety Information

Before using the Multiple Installation Controller(*) (Pressure Controller MP1-200/MI Terminal MT1-200),
ensure that this operation manual is read and fully understood; furthermore, the instructions given herein
should be strictly observed during operation.

The Multiple Installation Controller(*) contains high voltage sections that could cause electric shock.
Failure to use the controller in the appropriate manner can, therefore, result in death, injury, the outbreak
of fire, and other serious accidents.

In order to ensure that tasks undertaken during operation and maintenance of the Multiple Installation
Controller(*) can be completed safely, it is critical that all dangerous and hazardous parts of this
equipment be confirmed in advance. Here at MIURA, it is practically impossible to anticipate all
potentially dangerous situations, and therefore, this operation manual deal only with known hazards. A
higher level of safety can be achieved by carefully observing the warnings and instructions set forth
herein.
Safety- and damage-related warnings are classified into the following three levels, and notification of
these warnings is provided within this operation manual and using warning labels(*) on the Multiple
Installation Controller(*) itself.

Indicates an imminently dangerous situation which leads to serious injury or


death to the user, if the product is mishandled.

Indicates a situation which might cause serious injury or death to the user, if
the product is mishandled.

Indicates a situation which might cause minor injury to the user or the
occurrence of physical damage only, if the product is mishandled.

If any part used in the product fails, contact our sales office to replace it with its genuine part. Using parts
of different models might reduce safety.
It should be noted that unauthorized alteration of the Multiple Installation Controller (*) or repair
procedures other than those described herein can pose a serious safety risk. Never make any
modifications or repairs without MIURA’s permission.

i
Introduction

Introduction

This document describes the methods of handling a Multiple Installation Controller(*) to ensure its proper
use.
Not only those who use the Multiple Installation Controller (*) for the first time but also those who know the
handling methods should read this document carefully and understand the proper handling methods
before use of the Multiple Installation Controller (*).
Furthermore, we also recommend that this Operation Manual be stored in a specially designated location
so that it can be referred to at any time to confirm the correct usage.

[Explanation of Notation]
The meanings of the symbols used in this manual are as shown below.

Indicates a prohibited action (what you must not do).

Indicates a possibility of electric shock when the product is


handled with wet hands.

Indicates an action to be taken according to an instruction (what


to be executed).

Indicates an action connecting a grounding wire.


Ground
Connection

Indicates a caution.

Indicates a possibility of injury due to high temperatures under


specific conditions.

Describes the precautions to prevent failures of the boiler, points


NOTE
to perform effective operation, and useful information to know.

Indicates the page of related information.

ii
Definition of Terms

Definition of Terms

The following are the meanings of terms used in this operation manual. (Indicated by (*) in the text).

Terms Details

Warning label A sticker that urges caution in operation.

A status in which boilers are operated according to directions from the


Automatic operation
MI controllers.

A status in which boilers are operated independently of directions from


Manual operation
the MI controllers.

Multiple installation (MI) To automatically operate the quantity of boilers among several installed
control boilers that corresponds to the required amount of steam.

A pair of electric wires of two intertwined electric wires.


Twisted pair cable
Resistant to exterior electrical hazard and used for communication.

Boiler number Serial numbers for boilers under multiple installation control.

Boilers with higher priorities are more frequently fired up to provide


Priority
uniform combustion load and to prevent the corrosion of the boilers.

It changes the priorities of the boilers under multiple installation control


Rotation
to be fired up in order to make the combustion load uniform.

iii
Table of Contents

Table of Contents
Important Safety Information ....................................................................... i
Introduction ................................................................................................. ii
Definition of Terms ..................................................................................... iii

SECTION 1 SAFETY ..................................................................... 1


1. Safety Regulations ............................................................................... 1
2. Safety-related Knowledge and Expertise ............................................. 1
3. Protective Equipment ........................................................................... 1
4. Prohibition of Unapproved Modification ............................................... 1
5. Warning Labels on the Product Main Unit ............................................ 2
6. Safety Precautions ............................................................................... 3
6.1 Safety Precautions for Installation .................................................................. 3
6.2 Safety Precautions for Use of the Equipment ................................................. 4
6.3 Safety Precautions for Relocation or Resale (excerpt from page 51- of the text)
4

SECTION 2 OVERVIEW ................................................................ 5


1. Product Overview ................................................................................. 5
1.1 Features and Functions .................................................................................. 5
1.2 Configuration .................................................................................................. 6
1.3 Specifications.................................................................................................. 7
1.3.1 Common Specifications .......................................................................... 7
1.3.2 Pressure Controller MP1-200 ................................................................. 8
2. Component Names and Functions....................................................... 9
2.1 Pressure Controller MP1-200 ......................................................................... 9
2.1.1 Control Panel ......................................................................................... 9
2.1.2 Internal Structure .................................................................................. 10
2.2 MI Terminal MT1-200 .................................................................................... 11
2.2.1 Control Panel ....................................................................................... 11
2.2.2 Internal Structure .................................................................................. 12

iv
Table of Contents

SECTION 3 OPERATION ............................................................ 13


1. Operating the Pressure Controller MP1-200 ...................................... 13
1.1 Normal Operation ......................................................................................... 13
1.2 Operation with External Control Signal (External connection is required
separately) .................................................................................................... 14
1.2.1 Stopping All the Boilers ........................................................................ 14
1.2.2 Firing Up All the Boilers ........................................................................ 14
1.2.3 Suspending Alarm Output .................................................................... 14
1.3 Setting Operation (Control Pressure, Alarm Pressure) ................................. 15
1.4 Other Setting Operation (Switch, Pressure Sensor Adjustment) .................. 16
2. Operating the MI Terminal MT1-200 ................................................... 19
2.1 Normal Operation ......................................................................................... 19
2.2 Normal Setting Operation ............................................................................. 21
2.2.1 Setting Priority ...................................................................................... 21
2.2.2 Setting the Current Time ...................................................................... 22
2.2.3 Setting the Day of the Week................................................................. 22
2.2.4 Setting Cumulative Combustion Time .................................................. 23
2.3 Basic Data Display and Setting Operation.................................................... 24
2.4 List of Setting Display ................................................................................... 34
3. Details of Control and Function .......................................................... 35
3.1 MI Control Function ...................................................................................... 35
3.2 Determination of Priority ............................................................................... 37
3.3 Backup Control ............................................................................................. 37
3.4 Automatic Rotation Function ........................................................................ 37
3.5 Blowdown Timing Notification Function ........................................................ 40
3.6 External Signal Control of the Pressure Controller MP1-200 ........................ 41
3.6.1 External Control Input (Terminal Block No.1 to No.8) ........................... 41
3.6.2 Output for External Monitor (Terminal Block No.9 to No.20) ................ 42
3.7 Boiler Pressure Control Function (Option) .................................................... 45
4. Display Unit Change Function ............................................................ 46
4.1 Changing the Display Unit of the MI Terminal MT1-200 ............................... 46

v
Table of Contents

SECTION 4 BREAKDOWN AND COUNTERMEASURES .......... 47


1. When Pressure Indication of the Pressure Controller MP1-200 Is Incorrect
........................................................................................................... 47
2. When the Boilers Cannot Be Automatically Operated (the Boilers Are
Controlled by Their Pressure Settings) .............................................. 47
3. When the Boilers Stop Before the Specified Pressure Is Obtained ... 47
4. When the Boilers Do Not Start Combustion ....................................... 48
5. When the “B.BLOW” or “S.BLOW” LED Does Not Turn on at All or Turns on
Frequently .......................................................................................... 48
6. When Automatic Rotation Is Not Performed or Automatic Rotation Does
Not Change The Priorities .................................................................. 49
7. When the Boilers Do Not Fire According to the Priorities ................... 49
8. Warning displayed on MI Terminal of MT1-200 ................................... 50

SECTION 5 STORAGE ................................................................ 51


1. Transfer or Resale ............................................................................. 51

SECTION 6 WARRANTY ............................................................. 52


1. Note Regarding Warranty .................................................................. 52
2. Inquiries Regarding the Product or Operation Manual ....................... 52

SECTION 7 APPENDIX ............................................................... 53


1. Purchasing Individual Operation Manuals .......................................... 53

vi
SECTION 1 SAFETY

SECTION 1 SAFETY
1. Safety Regulations
Handling of the Multiple Installation Controller(*) is comprised of operations associated with running of
the equipment and operations regarding maintenance.
The Multiple Installation Controller(*) should be operated by persons who were given explanations of the
operation with this operation manual.

2. Safety-related Knowledge and Expertise


Usage of the Multiple Installation Controller(*) requires knowledge and experience of the operation and
maintenance of mechanical equipment. Understand the operation manual before attempting to use the
controller.

3. Protective Equipment
Wear protective items such as a helmet and safety footwear as required for the task.

4. Prohibition of Unapproved Modification


It should be noted that unauthorized alteration of the Multiple Installation Controller(*) or repair
procedures other than those described herein can pose a serious safety risk. We strongly advise against
improvised customization and repair.

1
SECTION 1 SAFETY

5. Warning Labels on the Product Main Unit


A warning label(*) is affixed where caution is required for operation.
Replace peeling or torn warning labels(*).
If warning labels(*) are peeling off or damaged, replace with new ones.

 Pressure Controller MP1-200

2
SECTION 1 SAFETY

6. Safety Precautions
6.1 Safety Precautions for Installation
The following safety precautions apply to installation.

WARNING
 Pressure Controller MP1-200
Ensure that a dedicated circuit breaker (with overcurrent protection) is installed
on the main power supply line.

Circuit breaker Breaker Circuit breaker


(with overcurrent protection) capacity (with overcurrent protection)

Wiring

 MI Terminal MT1-200
Ensure that the main power supply line is wired from the boiler power supply line.

For installation of the power supply of the main power supply line, connect wires
with the specified diameter and ensure that they are grounded.

Ground
アース端子 terminal

3
SECTION 1 SAFETY

6.2 Safety Precautions for Use of the Equipment


The following safety precautions apply to the use of the equipment.

WARNING
Do not perform this procedure with wet hands.
Failure to observe this precaution can result in high-voltage electric shock and

Wet Hands
injury or death.
Prohibited

Do not place combustible materials in the unit.


Failure to observe this precaution can result in a fire and death.

6.3 Safety Precautions for Relocation or Resale (excerpt from page 51- of the text)

WARNING
Ensure that the boiler is installed only in the specified condition and connected to
the specified peripheral equipment.
Failure to observe this precaution may result in injury.

4
SECTION 2 OVERVIEW

SECTION 2 OVERVIEW
1. Product Overview
1.1 Features and Functions
This unit automatically determines the optimum number of boilers to operate in consideration of the
load and operates the required number of boilers in descending order of priority(*). The major features
are as follows.

 This unit efficiently operates 15 boilers at maximum depending on the pressure status detected
by the pressure sensor installed on the steam header.

 The boiler can reduce unnecessary start and stop by setting the quantity of low fire standby units
depending on loading condition.

 When something goes wrong with one of the boilers, this unit performs MI control(*) on the rest of
the normal boilers. This enables the unit to perform a stable MI control(*) at a boiler abnormality.

 The automatic rotation(*) function determines combustion priorities(*) for the boilers according to
the cumulative combustion time of the boiler, which enables automatic equalization of boiler
combustion time.

 The blowdown time can be notified with the indication lamp by setting the blowdown timing. After
performing blowdown, the boiler can be operated temporarily on a priority basis to prevent the
corrosion of the boiler pressure vessel.

 The boiler can be turned on and off once a day by timer function. Setting can be performed
separately for each boiler under automatic operation(*).

 By installing an optional pressure sensor onto the MI Terminal MT1-200 of each boiler, the
pressure can be controlled at almost the same level as automatic operation(*) even when the
boiler is under manual operation(*). The unit can respond to a sudden load change by keeping
the boilers at a constant pressure during standby.

 The MI controllers(*) are connected only by two-core twisted pair cables(*) and the quantity of
boilers to be controlled can be changed by setting. This facilitates additional installation of
boilers after introduction of MI controllers(*).

5
SECTION 2 OVERVIEW

1.2 Configuration
As shown in the following figure, the unit is composed of a steam header that collects steam from the
boilers, a pressure sensor that monitors steam pressure of the steam header, a Pressure Controller
MP1-200, steam boilers controlled under MI control(*) and MT1-200 units that control the boilers.
The Pressure Controller MP1-200 performs monitoring on steam pressure of the steam header to
determine the most efficient combustion condition depending on the status of load change.
The MI Terminal MT1-200 receives information from the Pressure Controller MP1-200 to determine
the priorities(*), thus performing combustion control on the boilers.

6
SECTION 2 OVERVIEW

1.3 Specifications
1.3.1 Common Specifications

Applicable boiler : Three position step burner HIGH-LOW-OFF


Quantity of boiler under control : 15 units at the maximum
Control pressure : Working
Employed Control Range
Pressure Range
Sensor MPa
MPa
(Type) {PSI}
{PSI}
0.098 - 0.93 0.050 - 0.39
YSK-AC10M-333
{14 - 136} {8 - 56}
0.195 - 1.86 0.098 - 0.78
YSK-AC20M-334
{28 – 270} {14 – 114}
Control communication : Mutual information transmission by two-core (pair)
twisted pair cable(*).
Total interconnection length : Maximum 300 m (wiring for MI control(*) communication
line)
Control method : Combustion unit distribution system by steam header
pressure
Low fire unit ensuring type starting system (for the units
specified)
Low fire priority stop system
Functions : Automatic rotation(*) function
Complete blowdown immediate prioritized combustion
functions
Abnormal boiler backup functions
Pre-purge backup function
Pressure holding function of each boiler (optional)

7
SECTION 2 OVERVIEW

1.3.2 Pressure Controller MP1-200

External control input:


Terminal
Input name Signal type
number
Emergency stop 2-3
Contact input
Alarm check 4-5
Input voltage: Follows the power supply voltage.
All combustion 6-7
Input current: 6 mA (at 200 VAC)
All stop 7-8

Monitor output:
Terminal
Output name Signal type
number
Sensor fail 9-10
Communication status 10-11
Boiler operation 12-13
Alarm 13-14 Normally open dry contact
Emergency stop 15-16 Contact rating: 250 VAC / 1 A (resistance load)
Boiler trouble 16-17
Pressure alarm L 18-19
Pressure alarm H 19-20

8
SECTION 2 OVERVIEW

2. Component Names and Functions


2.1 Pressure Controller MP1-200
2.1.1 Control Panel

9
SECTION 2 OVERVIEW

2.1.2 Internal Structure

When operations such as configuration are performed with the front panel opened, do not touch
undesignated portions such as the terminal blocks or parts on the circuit board. It can cause an
electric shock or failure of the equipment.

The main unit front panel and the base plate must be locked. To remove the front panel, hold it with
both hands and pull it. See the figure below for internal construction.

10
SECTION 2 OVERVIEW

2.2 MI Terminal MT1-200


2.2.1 Control Panel

NOTE
You are not able to use TIMER FUNCTION if the local code does not allow you to use it.

11
SECTION 2 OVERVIEW
2.2.2 Internal Structure

Do not carry out internal setting with the top cover of the main unit open. A touch on the internal
terminal blocks or parts on the circuit board results in an electric shock or mechanical problem.
An error in setting leads to malfunction. Do not open the top cover except for special cases
such as installation check.

12
SECTION 3 OPERATION

SECTION 3 OPERATION
1. Operating the Pressure Controller MP1-200
1.1 Normal Operation
a) Display control
When the “DISPLAY CHANGE” switch is pressed, items on the display change as shown below.
The left end of LED indicates the type of the display item.

13
SECTION 3 OPERATION

1.2 Operation with External Control Signal (External connection is required


separately)
1.2.1 Stopping All the Boilers
All the boilers can be stopped by entering control signals to the all stop input terminal.
With external all stop operation, the “Lump operation” LED turns on and then the boilers under
automatic operation(*) stop combustion in order.

NOTE
 The boilers under manual operation(*) will not stop.
 If the MI Terminal MT1-200 is installed with the optional pressure sensor, all stop
operation cannot stop the boiler under automatic operation(*) from performing
combustion until the standby pressure is reached.

1.2.2 Firing Up All the Boilers


All the boilers can be fired up by entering control signals to the all combustion input terminal. With
external all combustion operation, the “Lump operation” LED turns on and then the boilers under
automatic operation(*) start combustion in order.

NOTE
 Any boilers which have been stopped by the MI Terminal MT1-200 will not perform
combustion.
 Any boiler whose boiler steam pressure exceeds the steam pressure setting (high)
or whose combustion SW or operation switch is turned off will not perform
combustion.
 All combustion is impossible during all stop or emergency stop input.

1.2.3 Suspending Alarm Output


The Pressure Controller MP1-200 has alarm outputs to connect a buzzer or other purposes. The
output contact closes in case of abnormality. To stop this output, press the “DISPLAY CHANGE”
switch or perform alarm check operation from outside to the alarm check input terminal (internal
terminal block No. 4 and No. 5).

14
SECTION 3 OPERATION

1.3 Setting Operation (Control Pressure, Alarm Pressure)


This section offers explanation on setting methods related to header steam pressure.
Perform setting by operating the internal potentiometers with the front panel of the main unit open.

a) Setting of control pressure


Press the “DISPLAY CHANGE” switch to display the “Control
pressure setting”.
Turn the internal potentiometer VR1 to set the maximum steam
pressure value.

b) Setting of control range


Press the “DISPLAY CHANGE” switch to display the “Control range
setting”.
Turn the internal potentiometer VR4 to set a control steam pressure
range.

c) Setting of pressure alarm L


Press the “DISPLAY CHANGE” switch to display the “Pressure
alarm L setting”.
Turn the internal potentiometer VR3 to set a pressure at which low
steam pressure alarm is set off.

d) Setting of pressure alarm H


Press the “DISPLAY CHANGE” switch to display the “Pressure
alarm H setting”.
Turn the internal potentiometer VR2 to set a pressure at which high
steam pressure alarm is set off.

15
SECTION 3 OPERATION

1.4 Other Setting Operation (Switch, Pressure Sensor Adjustment)

This section specifies the operation method for setting the switches within the main unit and
the pressure sensor adjusting value.
Failure to observe the setting procedures may cause control problems. Ask MIURA
representatives for setting and operation or perform the operation upon consulting.

a) Setting of “SWITCH 1” (SW1)  Setting of basic function


1) SW1-2
Specify a contact (normally open) type of the
emergency stop input.
OFF: Normally closed contact
ON: Normally open contact

2) SW1-4
Set output conditions for communication status
external output.
OFF: The output contact closes in the event of
a communication error in any of the
connected MT1-200 units.
ON: The output contact closes during normal communication with any of the connected
MT1-200 units.

3) SW1-5, 6
Set a connected pressure sensor type.
SW1 Maximum steam pressure
5 6 MPa {kgf/cm2}
OFF OFF 0.98 {10.0}
ON OFF 1.96 {20.0}
OFF ON No setting is allowed
ON ON 2.94 {30.0}
4) SW1-8
Set a steam pressure unit. See the “4. Display Unit Change Function” for details.
P.46

16
SECTION 3 OPERATION
5) SW1-1, 3, 7 (Switches other than those above)
Fix the SW1-1 to ON and other switches to OFF.

b) Setting of “SWITCH 2” (SW2)  Setting the quantity


of boilers under control
Set the quantity of boilers to be controlled.
Alphabetical characters A to F correspond to 10 to 15
units. Boilers connected more than quantity specified
here will not be under MI control(*).

c) Setting of “SWITCH 3” (SW3)  Setting the quantity


of stand-by boilers
Set the quantity of boilers that should be held at
low-fire conditions. Alphabetical characters A to F
correspond to 10 to 15 units. Follow the same
procedure as for setting the quantity of boilers under
control above. Out of the quantity specified here, the
largest possible number of boilers are started to hold
low fire.
Start operation depends on the set value.

P. 36

d) Setting of “SWITCH 4” (SW4)  Setting of delay time


Set the time to delay the actual boiler stop even after
the first-priority(*) boiler reaches the pressure to stop.
Note that if the pressure increases in the delay time
to the level where the pressure switch of the boiler is
activated, the order of the subsequent ignitions may
be incorrect or the response may be delayed. See the
following for the relation between switch settings and
delay time.
SW4 set value 0 1 2 3 4 5 6 7
Delay time (second) 0 1 2 4 6 8 10 14

SW4 set value 8 9 A B C D E F


Delay time (second) 18 22 26 30 35 40 45 55

17
SECTION 3 OPERATION

e) Zero adjustment, zero adjustment 2, gain adjustment  Pressure sensor adjustment
When the local use environment causes a deviation in the steam pressure display from the
actual value, there is a need to perform settings for both zero adjustment and gain adjustment.
There is no need to adjust zero adjustment 2.
Contact MIURA maintenance personnel for this operation.

18
SECTION 3 OPERATION

2. Operating the MI Terminal MT1-200


2.1 Normal Operation
a) Display control
When the “SELECT” switch is pressed, items on the display change as shown below.

Priority(*) (Example: 1)
Header steam pressure (Example: 0.85MPa)
SELECT

Boiler steam pressure (Example: 0.87MPa)


(Option)

SELECT *This is indicated only when an optional pressure sensor is installed.

Current time (Example: 12:38)

SELECT

Day of the week (Example: 0=Sunday)

SELECT

Next ON/OFF time (Example: Unit is ON at 13:00)


display: ON time
SELECT F display: OFF time

Cumulative combustion time (Example: 1,800 hours)

SELECT

Input signal error

SELECT

Under-judgment alarm

SELECT
* This is indicated only during alarm judgment.

NOTE
Pressure (header steam pressure, boiler steam pressure) is displayed in “MPa”, “kgf/cm2”, or
“psi”. The position of the decimal point varies depending on the pressure unit.

The pressure display unit is changeable as well.

P.46

19
SECTION 3 OPERATION

b) Automatic/manual change
Press the “AUTO” switch to change the boiler operation from either automatic operation(*) under
MI control(*) or manual operation(*) by means of the boiler's steam pressure setting.
The “AUTO” LED turns on in automatic operation(*) mode.

c) Timer control ON/OFF change


Press the “TIMER” switch to turn ON or OFF the timer control that is set separately. The timer
control can be performed only when the MI Terminal MT1-200 is in automatic mode. The “TIMER”
LED changes depending on the timer control status.

P.28

 Combustion under timer control ..... The “TIMER” LED turns ON.
 Boiler stops under timer control ..... The “TIMER” LED blinks.
 Timer control OFF .......................... The “TIMER” LED turns OFF.

NOTE
You are not able to use TIMER FUNCTION if the local code does not allow you to use it.

d) Resetting complete blowdown notification


Press the “B.BLOW” switch to reset the notification for complete blowdown timing (The “B.
BLOW” LED blinks) specified separately. Resetting the complete blowdown notification causes
the “B.BLOW” LED to turn off.

e) Resetting the soot blow notification


Press the “S.BLOW” switch to reset the notification for soot blow timing (The “S.BLOW” LED
blinks) specified separately. Resetting the soot blow notification causes the “S.BLOW” LED to
turn off. (This function is not used on North American made boiler models.)

20
SECTION 3 OPERATION

2.2 Normal Setting Operation


This section specifies operation method for setting (normal setting) that can be displayed by pressing
the “SELECT” switch.

Perform common setting operation in the following procedures.

1) Press the “SELECT” switch as many times as needed to display the desired setting information.
2) Press the “UP” and “DOWN” switches simultaneously.
(The area that allows setting starts blinking.)
3) Press the “UP” or “DOWN” switch to set the desired value.
4) Press the “SELECT” switch as many times as needed to display the digit to be changed.
Repeat 3).

When all the digits are set, the setting is finished with nothing blinking on the display.
The following four items can be set or changed;
 Priority(*): ................................... See below.
 Current time (hour, minute) ....... P.22
 Day of the week ........................ P.22
 Cumulative combustion time ..... P.23
Other displayed items are inalterable.

2.2.1 Setting Priority


This information determines the priorities based on which the boilers are fired up.

1) Press the “SELECT” switch as many times as needed to display the priority(*) and header steam
pressure.
2) Press the “UP” and “DOWN” switches simultaneously, and then the digit for the priority(*) starts
blinking.
3) Press the “UP” or “DOWN” switch to set the desired priority(*).
4) Press the “SELECT” switch to finish the setting.

21
SECTION 3 OPERATION

2.2.2 Setting the Current Time


The timer function is activated according to the current time that is set here. When the setting is
done to MI Terminal MT1-200 for boiler No.(*) 1, no setting is necessary with other MT1-200 units
(Settings are automatically done to other MT1-200 units).
1) Press the “SELECT” switch as many times as
needed to display the current time
(hour/minute).
2) Press the “UP” and “DOWN” switches
simultaneously, and then the digit for hour of
the current time starts blinking.
3) Press the “UP” or “DOWN” switch to set a
value.
4) Press the “SELECT” switch to finish setting
hour, and then the digit for minute starts
blinking.
5) Press the “UP” or “DOWN” switch to set a
values.
6) Press the “SELECT” switch to finish the setting.

2.2.3 Setting the Day of the Week


The timer function is activated according to the day of the week that is set here. When the setting is
done to MI Terminal MT1-200 for boiler No.(*) 1, no setting is necessary with other MT1-200 units
(Settings are automatically done to other MT1-200 units).
1) Press the “SELECT” switch as many times as
needed to display the day of the week. (The
day of the week is displayed in a number. The
correspondences between days of the week
and numbers are listed as below. )
2) Press the “UP” and “DOWN” switches
simultaneously, and then the digit for the day of
the week starts blinking.
3) Press the “UP” or “DOWN” switch to set a value.
4) Press the “SELECT” switch to finish the setting.

Correspondences between days of the week and numbers


Day of the week Sun Mon Tue Wed Thu Fri Sat
Display 0 1 2 3 4 5 6

22
SECTION 3 OPERATION

2.2.4 Setting Cumulative Combustion Time


Boilers are prioritized for the automatic rotation(*) function according to this setting. Under the
automatic rotation(*), the priorities(*) of the boilers are determined in ascending order of the
cumulative time that is set here.

1) Press the “SELECT” switch as many times as


needed to display the cumulative combustion
time.
2) Press the “UP” and “DOWN” switches
simultaneously, then the first 3 digits start
blinking.
3) Press the “UP” or “DOWN” switch to set a value.
4) Press the “SELECT” switch, then the lower two
digits start blinking.
5) Press the “UP” or “DOWN” switch to set a lower
digits.
6) Press the “SELECT” switch to finish the setting.

NOTE
In the system where old and new boilers coexist, you can adjust the cumulative combustion
time to make the following operation implementable: Give higher priorities (*) to new boilers all
the time. Divide old boilers and new boilers into separate groups for automatic rotation(*).
Example: When two new boilers (No.(*) 1 and 2) and two old boilers (No.(*) 3 and 4)
coexist.
For example, set the cumulative combustion time for the boiler No. (*)1 and 2
to 0 and the boiler No. (*)3 and 4 to 1000.
Due to a shorter cumulative combustion time of the new boilers than that of
the old boilers, the new boilers (No.(*) 1 and 2) are given the first and second
priorities(*) respectively after automatic rotation(*). The old boilers are given
the third and fourth priorities(*).
There is no difference in the cumulative combustion time between the boiler
No. (*) 1 and 2, and between No.(*) 3 and 4, respectively. The rotation (*) is
performed to equalize the cumulative combustion time of boiler No.(*) 1 and 2,
and boiler No.(*) 3 and 4 respectively.
This condition will be held until the cumulative combustion time of the new
boilers exceeds that of old boilers. To hold this condition, set the cumulative
combustion time again.

23
SECTION 3 OPERATION

2.3 Basic Data Display and Setting Operation


This section describes how to perform setting operation on the basic data display mode.
Press the “SELECT” and “B.BLOW” switches simultaneously to display the basic data display mode.
To go back to the normal display mode, press the “SELECT” and “S.BLOW” switches simultaneously.

Setting can be performed as in same way as normal setting in the following procedures.
1) Press the “SELECT” switch as many times as needed to display the desired setting information.
2) Press the “UP” and “DOWN” switches simultaneously.
(The area that allows setting starts blinking.)
3) Press the “UP” or “DOWN” switch to set the desired value.
4) Press the “SELECT” switch as many times as needed to display the digit to be changed.
Repeat 3). When all the digits are set, the setting is finished with nothing blinking on the display.

The following thirteen items can be set or changed;


 Steam pressure setting (high) ................................................. Refer to P.25.
 Differential setting (high) ......................................................... Refer to P.25.
 Steam pressure setting (low) .................................................. Refer to P.26.
 Differential setting (low)........................................................... Refer to P.26.
 Holding-pressure setting ......................................................... Refer to P.27.
 Differential setting (holding) .................................................... Refer to P.27.
 Timer (Sun. through Sat.)........................................................ Refer to P.28.
 Post-fire time ........................................................................... Refer to P.31.
(*) (*)
 Rotation time (only for the boiler No. 1) .............................. Refer to P.31.
(*)
 Rotation flag ......................................................................... Refer to P.32.
 Priority combustion time after complete blowdown ................. Refer to P.32.
 Notification time for complete blowdown timing ...................... Refer to P.32.
 Notification time for soot blow timing....................................... Refer to P.33.

NOTE
The information in the shaded box can be displayed and set only when an optional
pressure sensor is installed on the MI Terminal MT1-200.

24
SECTION 3 OPERATION

a) Steam pressure setting (high) (Option: Only when pressure sensor is installed)
This setting provides combustion stop pressure under manual operation(*). Under manual
operation(*), the boiler combustion stops when the boiler steam pressure rises to the set
pressure.

P.19

1) Press the “SELECT” switch as many times as


needed to display steam pressure setting
(high).
2) Press the “UP” and “DOWN” switches
simultaneously, then the set value starts
blinking.
3) Press the “UP” or “DOWN” switch to set the
desired pressure.
4) Press the “SELECT” switch to finish the setting.

b) Differential setting (high) (Option: Only when pressure sensor is installed)


After boiler combustion is stopped at the pressure specified in the previous section, combustion
starts again when the boiler steam pressure decreases by the specified differential set in this
section.
Set the same unit as that of header steam pressure.

P.19

1) Press the “SELECT” switch as many times as


needed to display differential setting (high).
2) Press the “UP” and “DOWN” switches
simultaneously, and then the set value starts
blinking.
3) Press the “UP” or “DOWN” switch to set the
desired pressure.
4) Press the “SELECT” switch to finish the setting.

25
SECTION 3 OPERATION

c) Steam pressure setting (low) (Option: Only when pressure sensor is installed)
This setting provides high fire stop pressure under manual operation(*). Under manual operation(*),
the boiler shifts from high fire to low fire when the boiler steam pressure rises to the set pressure
during high fire.
Set the same unit as that of header steam pressure.

P.19

1) Press the “SELECT” switch as many times as


needed to display steam pressure setting
(low).
2) Press the “UP” and “DOWN” switches
simultaneously, then the set value starts
blinking.
3) Press the “UP” or “DOWN” switch to set the
desired pressure.
4) Press the “SELECT” switch to finish the setting.

d) Differential setting (low) (Option: Only when pressure sensor is installed)


After the shift from high fire to low fire at the pressure specified in the previous section, the boiler
starts high fire again when the boiler steam pressure decreases by the specified differential set in
this section.
Set the same unit as that of header steam pressure.

P.19

1) Press the “SELECT” switch as many times as


needed to display differential setting (low).
2) Press the “UP” and “DOWN” switches
simultaneously, then the set value starts
blinking.
3) Press the “UP” or “DOWN” switch to set the
desired pressure.
4) Press the “SELECT” switch to finish the
setting.

26
SECTION 3 OPERATION

e) Holding-pressure setting (Option: Only when pressure sensor is installed)


This setting provides standby pressure under automatic operation(*). The boiler fires up until the
boiler steam pressure reaches the pressure set in this section regardless of the header steam
pressure. Set the pressure lower than (the value obtained by subtracting the control range from
the control pressure) specified at the Pressure Controller MP1-200.The boiler is on standby
above a constant pressure, enabling stable response at a sudden load change.
Set the same unit as that of header steam pressure.

P.19

1) Press the “SELECT” switch as many times as


needed to display the holding-pressure
setting.
2) Press the “UP” and “DOWN” switches
simultaneously, and then the set value starts
blinking.
3) Press the “UP” or “DOWN” switch to set the
desired pressure.
4) Press the “SELECT” switch to finish the setting.

f) Differential setting (holding) (Option: Only when pressure sensor is installed)


After boiler combustion is stopped at the pressure specified in the previous section, combustion
starts again when the boiler steam pressure decreases by the specified differential set in this
section.
Set the same unit as that of header steam pressure.

P.19

1) Press the “SELECT” switch as many times


as needed to display differential setting
(holding).
2) Press the “UP” and “DOWN” switches
simultaneously, then the set value starts
blinking.
3) Press the “UP” or “DOWN” switch to set the
desired pressure.
4) Press the “SELECT” switch to finish the setting.

27
SECTION 3 OPERATION

g) Timer (Sun. through Sat.)


Set a boiler ON time and OFF time for each day from Sunday to Saturday. Timer settings for
each day are displayed in the following order. The information enclosed in the box describes the
indications of a ON time and OFF time on the display.
 Sunday Boiler ON time
Boiler OFF time
 Monday Boiler ON time
Boiler OFF time
:
 Saturday Boiler ON time
Boiler OFF time
Wed
Mon
Sun

Tue

Thu

Sat
Fri

NOTE
You are not able to use TIMER FUNCTION if the local code does not allow you to use it.

28
SECTION 3 OPERATION

The relation between the setting value and operation ON/OFF is as follows.

1) When the ON time is earlier than the OFF time:

0:00 ON time OFF time 24:00

Previous Operation Stop


day status

2) When the ON time is later than the OFF time:

0:00 OFF time ON time 24:00

Previous Stop Operation


day status

3) When the ON time is the same as the OFF time (Turned ON all day long.)

OFF time
0:00 ON time 24:00

Operation

4) When only ON time is set (OFF time = 24:00)

0:00 ON time 24:00

Previous Operation
day status

5) When only OFF time is set (ON time = 24:00)


0:00 OFF time 24:00

Previous Stop
day status

29
SECTION 3 OPERATION

Setting example

1) To stop the boiler all the day


ON time ...................... 24:00
OFF time .................... 0:00

2) To fire up the boiler all the day


ON time ...................... 0:00
OFF time .................... 24:00

3) To fire up the boiler from 8:00 to 17:00


ON time ...................... 8:00
OFF time .................... 17:00

4) To turn on the boiler at a fixed time (8:00 in example), and stop by a customer.
ON time ...................... 8:00
OFF time .................... 13:00 (Set a time when the boiler should be stopped)

The timer operation causes the boiler to start firing at 8:00. Be sure to press “TIMER” between
8:00 and 13:00 to stop timer operation. (Disabling the timer operation allows the boiler to
perform combustion after 13:00.)
To stop boilers, press the “TIMER” switch to activate the timer operation.

5) To turn on the boiler by a customer and stop at a fixed time (17:00 in example)
ON time ...................... 13:00 (Set a time when the boiler should be in operation)
OFF time .................... 17:00

To start boilers, press the “TIMER” switch before 13:00 to stop the timer operation. (Stopping
the timer operation allows the boiler to start combustion.)
Press the “TIMER” switch between 13:00 and 17:00 to activate the timer.
(The boiler combustion continues as the time is after the ON time.)
The timer function causes the boiler to stop at 17:00.

30
SECTION 3 OPERATION

Setting can be performed in the following procedures.


The following shows how to set the ON time on Sunday. Setting can be performed for other days of
the week and OFF time in the same procedures.

1) Press the “SELECT” switch as many times as


needed to display the ON time indication on
Sunday (“0” is displayed).
2) Press the “UP” and “DOWN” switches
simultaneously, then the digit for hour of timer
starts blinking.
3) Press the “UP” or “DOWN” switch to set the
desired time.
4) Press the “SELECT” switch to finish setting
hour, and then the digit for minute starts
blinking.
5) Press the “UP” or “DOWN” switch to set the desired minute.
6) Press the “SELECT” to finish the setting for ON
time on Sunday.

h) Post-fire time (second)


If the boiler is to be stopped during automatic operation(*) before
the specified period of low fire is satisfied, this function continues
low fire until the end of the specified period, and then stops
combustion.
Use this function to prevent fluctuation of the main gas pressure by performing low-fire
combustion for given time before stopping the gas-fired boiler.
For oil-fired boilers, set the time to 0.

i) Rotation(*) time (only for boiler No. (*)1)


P.37
At rotation(*), combustion boilers change.
To set a fixed time for automatic rotation(*), select a proper time in
which all the boilers are stopped or all the boilers are under
combustion.

31
SECTION 3 OPERATION

j) Rotation(*) flag
Set the rotation(*) timing identification within the ranges of 0 to 9 and
A to F. P.38
The correspondences between the setting numbers and the
functions are as shown below.
0 : Automatic rotation(*) is not allowed.
1~7 : Set a rotation(*) interval by days.
The valid setting can be made only with the MI Terminal MT1-200 installed on the
boiler No. (*)1.
8 : Automatic rotation(*) is performed at a complete blowdown. All the boilers start
automatic rotation(*) at the press of the “B.BLOW” switch of the boiler in which the set
value is set to 8.
9 : If this value is set to a boiler, the priority(*) is fixed with the boiler. The priority(*) does not
change at automatic rotation(*) timing for other boilers.
Those boilers are given a new priority(*) other than the fixed boiler priority(*).
A to F : Set a rotation(*) at 1 to 12-hour intervals.
The valid setting can be made only with the MI Terminal MT1-200 installed on the
boiler No. (*)1.
The valid setting can be made only when an optional pressure sensor is installed.

k) Priority combustion time after complete blowdown (second)


When the “B.BLOW” switch is pressed, the priority(*) is brought forward temporarily until the
cumulative combustion time reaches the set value or the surface blowdown valve starts to
operate.
This function accelerates the concentration of the boiler water P.38

after blowdown.
Set the time within the range of 0 to 9800 (about 2 hours and 43
minutes) in second units.
The priority combustion does not function after complete
blowdown if the time is set to 0.

l) Notification time for complete blowdown timing (hour)


When the cumulative combustion time reaches the value specified here, the “B.BLOW” LED
starts blinking.
Press the “B.BLOW” switch to restart timing.
Set the time within the range of 0 to 999 in hour units.
If the time is set to 0, the complete blowdown notification does
not function.
32
SECTION 3 OPERATION

m) Notification time for soot blow timing (hour)


When the cumulative combustion time reaches the value specified here, the “S.BLOW” LED
starts blinking.
Press the “S.BLOW” switch to restart timing.
Set the time within the range of 0 to 999 in hour units.
If the time is set to 0, the soot blow notification does not function.

33
SECTION 3 OPERATION

2.4 List of Setting Display

NOTE
Steam pressure (header steam pressure, boiler steam pressure, steam pressure setting (high),
differential setting (high), steam pressure setting (low), differential setting (low), holding-pressure
setting, differential setting (holding)) can be displayed in the units of MPa, kgf/cm2, or psi.
P.19

34
SECTION 3 OPERATION

3. Details of Control and Function


3.1 MI Control Function
This MI controller(*) fires up the required quantity of boilers in accordance with the steam pressure
detected by the pressure sensor connected to the Pressure Controller MP1-200.

a) Conditions for MI control(*)


1) Boilers in the following statuses are not controlled by MI control(*).
• Boilers with combustion switch OFF
• Boilers in error statuses
• Boilers under manual operation(*)
• Boilers which are stopped by the timer function of MI Terminal MT1-200
• Boilers of which the power of the Pressure Controller MP1-200 or the MI Terminal
MT1-200 is OFF or MI communication is not performed
• Boilers of which boiler number(*) of the MI Terminal MT1-200 is larger than the boiler
quantity set at the Pressure Controller MP1-200
• Boilers of which boiler number(*) of the MI Terminal MT1-200 is duplicated with that of
other MI Terminal MT1-200
• Boilers which are off by the pressure switch of the boiler

2) MI control(*) is not performed under the following additional conditions.


• External control signaling is input to the Pressure Controller MP1-200.
• The pressure sensor has failed.
In this case, actual control depends on the failure status. If the Pressure Controller
MP1-200 can detect a failure, each boiler is switched to manual operation(*) and then
controlled by the boiler steam pressure setting (or MI Terminal MT1-200 pressure
sensor). If a failure cannot be detected, the unit carries out MI control(*) corresponding to
the displayed pressure.

b) Operation timing
Boilers are fired up or go on standby by the MI control(*) at one second intervals. To control power
supply, boilers are started at the minimum interval of three seconds (simultaneously start
prevention function).

35
SECTION 3 OPERATION

c) Operation at boiler start


1) In accordance with the increase in load and resulting decrease in header steam pressure, this
MI controller(*) increases the quantity of boilers to fire. The unit starts the boilers while securing
the quantity of low fire boiler that was set in advance at the setting of the quantity of stand-by
boilers (set with the Pressure Controller MP1-200).

P.17
2) The boilers are started in the order of priority(*) (from the first priority(*)).

Header pressure

1 Low fire High fire High fire High fire High fire High fire High fire High fire

2 Low fire High fire High fire High fire High fire High fire

3 Low fire High fire High fire High fire

4 Low fire High fire

1 Low fire Low fire Low fire Low fire High fire High fire High fire High fire

2 Low fire Low fire Low fire Low fire High fire High fire High fire

3 Low fire Low fire Low fire Low fire High fire High fire

4 Low fire Low fire Low fire Low fire High fire

d) Operation at boiler stop


1) The unit decreases the quantity of boilers to fire in accordance with the increase in header
steam pressure resulting from decrease in load. The shift from high fire to low fire is performed
on a priority basis regardless of the setting of the quantity of stand-by boilers. Therefore, the
quantity of boilers fired up at low fire may exceed the set quantity of stand-by boilers.

2) If more boilers than the set quantity of stand-by boilers continue low fire for over 15 minutes,
operation is stopped from the lowest priority(*) boiler in sequence, and the boilers with high
priority(*) are shifted to high fire.

Header pressure

1 High fire High fire High fire High fire Low fire Low fire Low fire Low fire

2 High fire High fire High fire Low fire Low fire Low fire Low fire

3 High fire High fire Low fire Low fire Low fire Low fire

4 High fire Low fire Low fire Low fire Low fire

36
SECTION 3 OPERATION

3.2 Determination of Priority


The boiler with shorter cumulative combustion time is given a higher priority(*). Although setting can be
made with each MI Terminal MT1-200, make setting so as not to make priorities(*) duplicate.

P.21

3.3 Backup Control


The MI controller(*) carries out backup control in the following cases.

a) Backup control when a boiler is out of control


If any of the boilers is out of control due to a failure or a combustion switch OFF, the controller
distributes load to the controllable boilers and give a priority(*) to the boilers and starts
combustion.
b) Backup control during pre-purge
When a newly activated boiler is performing pre-purge, other low fire boilers temporarily shift to
high fire. This minimizes the delay of load response.
If the priority(*) sequence of boilers is changed, the existing boilers continue combustion until the
new boiler starts combustion.
c) A pressure sensor is installed on the MI Terminal MT1-200
If an optional pressure sensor is installed on the MI Terminal MT1-200, other boilers perform
backup operation until the new boilers obtain a sufficient pressure after combustion begins.

3.4 Automatic Rotation Function


This MI controller(*) has an automatic rotation(*) function that determines the priority(*) automatically at
a preset timing in ascending order of length of the cumulative combustion time.

a) Automatic rotation(*) at one- to seven-day intervals [Rotation(*) flag=1 to 7]


By setting a value from 1 to 7 to the rotation(*) flag with the MI Terminal MT1-200 for the boiler
No.(*)1, rotation(*) of boilers is performed automatically every 1 to 7 days.
Automatic rotation(*) is performed at a rotation(*) time specified with the MI Terminal MT1-200 of
the boiler No.(*)1.

37
SECTION 3 OPERATION

b) Automatic rotation(*) after complete blowdown [Rotation(*) flag=8]


This function is activated when the rotation(*) flag is set to 8 with each MI Terminal MT1-200. Pressing
the “B.BLOW” switch on any MI Terminal MT1-200 under such setting resets the complete blowdown
notification timer. The rotation(*) is performed at the same time.
If setting of any priority combustion time after complete blowdown is made, the priority(*) is changed
temporarily.
c) Fixing the priority(*) of particular boiler [Rotation(*) flag=9]
This function is activated when the rotation(*) flag is set to 9 with each MI Terminal MT1-200. Under
this setting, the priority(*) set with the MI Terminal MT1-200 remains unchanged at automatic rotation(*)
timing.
Precluding the priority(*) that is fixed with this setting, the other MT1-200 units under automatic
rotation(*) determine the priority(*).
d) Automatic rotation(*) at intervals of 1 to 12 hours [Rotation(*) flag = A to F]
(Option: Only when pressure sensor is installed)
If an optional pressure sensor is installed, the automatic rotation(*) can be performed at intervals of 1
to 12 hours by setting the rotation(*) flag to an alphabetical character rom A to F with the MI Terminal
MT1-200 of the boiler No.(*)1.
If the rotation(*) flag is set from A to F without installing an optional pressure sensor, the automatic
rotation(*) is performed every day at a specified time.

The following shows operation when an alphabetical character from A to F is set to the rotation(*) flag.
Rotation(*) flag
Rotation(*)
setting
Every 1 Rotation(*) is performed on the hour.

hour

Every 2 Rotation(*) is performed every two hours from 00:00.

hours (0 o'clock, 2 o'clock, 4 o'clock ..., 20 o'clock, 22 o'clock)

Rotation(*) is performed every four hours from 00:00.


Every 4
(0 o'clock, 4 o'clock, 8 o'clock, 12 o'clock, 16 o'clock, 20
hours
o'clock)

Every 6 Rotation(*) is performed every six hours from 00:00.

hours (0 o'clock, 6 o'clock, 12 o'clock, 18 o'clock)

Every 8 Rotation(*) is performed every eight hours from 00:00.

hours (0 o'clock, 8 o'clock, 16 o'clock)

Every 12 Rotation(*) is performed every twelve hours from 00:00.

hours (0 o'clock, 12 o'clock)

38
SECTION 3 OPERATION

NOTE
If the automatic rotation(*) function is utilized at intervals from 1 to 12 hours, it is necessary
to check the version of each MI Terminal MT1-200 and the Pressure Controller MP1-200.
Contact MIURA maintenance personnel for details.

e) Inactivation of automatic rotation(*)


Automatic rotation(*) is not performed under the following case.
• The rotation(*) flag is set to 0 or 9 with the MI Terminal MT1-200 of the boiler No.(*)1.

f) Setting example of automatic rotation(*)


The following is an example where MI control(*) is performed on four units of boilers.
Boiler Rotation(*) High fire converted Priority(*) before Priority(*) after
(*) (*)
No. flag combustion time Rotation Rotation(*)
1 2 900 1 4
2 - 800 2 2
3 9 700 3 → 3
4 - 600 4 1
• In this example, automatic rotation(*) is performed every two days at a specified time (in
accordance with the rotation(*) flag setting for the boiler No.(*)1).
• At the rotation(*) time, a higher priority order is given to the boilers in which the cumulative
combustion time is shorter.
• For the boiler of which rotation(*) flag is set to 9 (boiler No.(*)3), the priority(*) is fixed.

39
SECTION 3 OPERATION

3.5 Blowdown Timing Notification Function


This function is activated when the time for blowdown timing notification is set to other than 0 with
each MI Terminal MT1-200.
When the high fire converted combustion time reaches a specified time after resetting the notification
time for blowdown timing, the “B.BLOW” LED on the MI Terminal MT1-200 blinks to notify the
blowdown timing.

P.32

• The notification time for complete blowdown and soot blow can be set and notify
individually.
• To reset the value, press the “B.BLOW” or “S.BLOW” switches after the blowdown timing
is notified.
• This setting can be made within the range of 0 to 999 in hour units (high fire converted
combustion time). This function is not activated if the value is set to 0.

40
SECTION 3 OPERATION

3.6 External Signal Control of the Pressure Controller MP1-200


3.6.1 External Control Input (Terminal Block No.1 to No.8)
The terminal blocks No.1 to 8 are terminal blocks for external control input.
To carry out terminal input, provide an external contact as needed. Use a rated contact that can be
operable at 200 VAC / 6 mA.

20
19
18

17
16
15 7-8: All stop
14
Stop all the boilers
13 under MI control(*).
12
11
10
6-7: All combustion
9 Fire up all the
boilers under MI
control(*).
8
7
6 4-5: Alarm check
When the contact of the
5 alarm output (No. 14) is
4 closed, the output is
brought to stop.
3
2
1 2-3: Emergency stop
FG R S Stop the combustion
process of all the
communicating boilers.

1: S-phase output
Used to illuminate
the indication lamp.

a) Emergency stop input (Terminal block No.2 and No.3 input)


If emergency stop input is implemented, the “EMERGENCY STOP” LED on the control panel
turns on and all the boilers in successful communication stop operation, regardless of their
pressure or operation mode (manual/automatic). The contact of the alarm output (terminal block
No.14) also closes.
The input logic can be changed with the internal “SWITCH 1”.

P.16
b) Alarm confirmation input (Terminal block No.4 and No.5 input)
This control signal input has no impact on the MI control(*) function. When the Pressure Controller
MP1-200 provides an alarm output (terminal block No.14) due to abnormality in the boiler, this
input stops the alarm output.
41
SECTION 3 OPERATION

c) All stop input (Terminal block No.7 and No.8 input)


This input stops all the firing boilers under MI control(*) by providing an all stop input.
All the automatically operated(*) boilers connected to the MI Terminal MT1-200 with passage of
electric current are targets.

d) All combustion input (Terminal block No.6 and No.7 input)


An all combustion input causes all the boilers under MI control(*) to start combustion in order.
All the automatically operated(*) boilers connected to the MI Terminal MT1-200 with passage of
electric current are targets. This input is nonfunctional if “Emergency stop Input” and “All Stop
Input” are input. (The boilers are stopped in accordance with the status of each input condition.)

3.6.2 Output for External Monitor (Terminal Block No.9 to No.20)


The terminal blocks No.9 through 20 are non-voltage contact output terminals ( normally open ) for
the external monitor.
Connect a load of 250 VAC, 1 A or less.
20: Pressure alarm H
The contact closes when
header steam pressure
20 exceeds alarm H setting.
19
18: Pressure alarm L
18
The contact closes when
17 header steam pressure is
16 lowered below alarm L
setting.
15

14 17: Boiler trouble


13
The contact closes when any
boiler under MI control(*) has
12
an error.
11
15: Emergency stop
10
The contact closes when the
9
emergency stop is input.

14: Alarm
8
The contact closes when any
7 contact of 15, 17, 18, and 20
6
above is closed.

5
12: Boiler operation
4
The contact closes when any
3 boiler's operation switch is
2 ON.
1
11: Communication status
FG R S The contact outputs the
communication status. The
operation varies depending
on the settings of the internal
“SWITCH 1”.

9: Sensor failure
The contact closes when a
pressure sensor failure is
detected.

42
SECTION 3 OPERATION

The pressure controller, model MP1-200, has several “dry” contacts available. On site wiring of
these outputs must be done by the customer or electrical contractor to fully utilize the available
features. All of the outputs require power from an outside source. The contacts are operated by a
relay mounted on the MP1-200. The relay contacts are rated for 250VAC, 1A. Output loads are
requested to be non-inductive. MIURA does not recommend installing an induction load, such as a
solenoid valve or transformer. If an induction load is to be connected, use an external relay
operated by the contact to avoid inductive kick on the MP1 circuit board.

a) Sensor fail output (Terminal block No.9)


This contact closes when an error is detected with the pressure sensor installed on the steam
header. When this contact closes, a sensor failure or disconnection in wire to the sensor is
attributed to the possible cause.

b) Communication status output (Terminal block No.11)


The communication status is output through the contact. Operation varies depending on the
setting of the “SWITCH 1” installed inside.

P.16
When the SW1-4 is OFF
The contact closes if an MI Terminal MT1-200 has a communication error.
When the SW1-4 is ON
The contact closes if there is no problem in communication with all the MT1-200 units.

c) Boiler operation output (Terminal block No.12)


The contact closes when the operation switch of any of the boilers is ON.
When all the boiler's operation switches are OFF, the contact opens after five seconds.
The operation switch of any boiler with a communication error is considered to be in the OFF
state.

d) Alarm output (Terminal block No.14)


This contact closes when any contact of pressure alarm H (No.20), pressure alarm L (No.18),
boiler trouble (No.17), and emergency stop (No.15) is closed.
This contact opens under the following cases.
• All these contacts open.
• The alarm confirmation input (No.4 and No.5 input) is ON.
• The “DISPLAY CHANGE” switch on the control panel is pressed.

43
SECTION 3 OPERATION
e) Emergency stop output (Terminal block No.15)
This contact closes when an input is provided to the emergency stop input terminal (No.2 and 3).
The input logic of emergency stop can be changed with the “SWITCH 1”.

P.16

f) Boiler trouble output (Terminal block No.17)


This contact closes if any of the boilers communicating with the MI Terminal MT1-200 sets off a
buzzer.

g) Pressure alarm L output (Terminal block No.18)


This contact closes and the “LOW-PRESSURE” LED on the control panel turns ON when the
steam header's steam pressure is lowered below the specified “Pressure Alarm L Setting”.
The output is reset automatically when the header steam pressure exceeds the set value of
“Pressure Alarm L Setting”.
No output is provided when all the boilers are brought to a stop by means of the timer function of
the MI Terminal MT1-200.

P.15

h) Pressure alarm H output (Terminal block No.20)


This contact closes and the “HIGH-PRESSURE” LED on the control panel turns ON when the
steam header's steam pressure exceeds the specified “Pressure Alarm H Setting”.
The output is reset automatically when the header steam pressure drops below the set value of
“Pressure Alarm H Setting”.

P.15

44
SECTION 3 OPERATION

3.7 Boiler Pressure Control Function (Option)


The controller allows this function to operate when an optional pressure sensor is installed on the MI
Terminal MT1-200 of each boiler.

a) Boiler pressure control under manual operation(*)


The controller controls the boiler combustion in accordance with the control pressure separately
set when the MI Terminal MT1-200 is under the manual operation(*) mode.
When the boiler is set to the manual operation(*) mode, operation is changed automatically so
that it operates at a control pressure set with the MT1-200.

P.25

b) Pressure holding
By setting a holding pressure to the MI Terminal MT1-200, the boilers can perform combustion up
to a certain pressure even though the boilers are under standby state during automatic
operation(*). (The pressure to hold the pressure constant is referred to as holding pressure.)
This function is effective in case of sudden fluctuations in load since the boilers under standby
can always keep pressure above a certain level.

P.27

45
SECTION 3 OPERATION

4. Display Unit Change Function

4.1 Changing the Display Unit of the MI Terminal MT1-200


The pressure display unit of the MI Terminal MT1-200 is changeable (MPa, kgf/cm2, psi).
To make changes to the pressure display unit, contact MIURA maintenance personnel.

46
SECTION 4 BREAKDOWN AND COUNTERMEASURES

SECTION 4 BREAKDOWN AND COUNTERMEASURES


1. When Pressure Indication of the Pressure Controller MP1-200 Is
Incorrect
a) Check if the left end LED is OFF or “P” is displayed.
Any other indications do not provide the pressure information.
Press the “DISPLAY CHANGE” switch to show the pressure.

P. 13
b) If nothing above applies, defects in the pressure sensor and wiring or clogged piping are
possible causes.
Contact MIURA sales office.

2. When the Boilers Cannot Be Automatically Operated (the Boilers


Are Controlled by Their Pressure Settings)
a) Check if the “AUTO” LED of the MI Terminal MT1-200 is OFF.
If it is OFF, the unit is in manual operation(*) mode. Press the “AUTO” switch to select the
automatic operation(*) mode.

P. 20
b) Check if the “AUTO” LED of the MI Terminal MT1-200 is blinking.
If the “AUTO” LED is blinking, the unit is in manual operation(*) mode due to the
communication error with the Pressure Controller MP1-200.
Check whether the power supply of the Pressure Controller MP1-200 is turned off or not. If
the power supply is turned on, there may be something wrong with the communication wiring.
Contact MIURA sales office.

3. When the Boilers Stop Before the Specified Pressure Is Obtained


a) Check if the control pressure of the Pressure Controller MP1-200 is set properly.
Press the “DISPLAY CHANGE” switch to display control pressure and then check the set
value.
If the setting is not done properly, set the control pressure in accordance with “Chapter 3 1.3
Setting operation (control pressure, alarm pressure)”.

P. 13, 15

47
SECTION 4 BREAKDOWN AND COUNTERMEASURES

b) Check if the setting of the boiler pressure is lower than the control pressure.
Set the pressure of the boiler pressure 0.1 MPa {1.0 kgf/cm2} higher than the control
pressure.

4. When the Boilers Do Not Start Combustion


a) Check if the boiler's operation switch or combustion switch are turned on.
The boiler does not start combustion unless the boiler's operation switch and combustion
switch are turned on. Turn on the boiler's operation switch and combustion switch in
accordance with the boiler's operation manual to make the boiler ready for combustion.

b) Check if the “TIMER” LED of the MI Terminal MT1-200 is blinking.


When the “TIMER” LED is blinking, the boilers are stopped with the timer function.
Press the “TIMER” switch to cancel the timer function or change the timer setting.

P. 20, 28

c) Check if the “LUMP OPERATION” or “EMERGENCY STOP” LED of the Pressure Controller
MP1-200 control panel is turned on.
The boiler does not start combustion when control signals are input to the all stop or
emergency stop terminal for external control. Turn off the switches provided outside to
cancel the boiler stop input.
If an earthquake detector is connected to the unit, the detector may be in the detecting
process.
Check the cause and then perform resetting.

P. 9, 41

5. When the “B.BLOW” or “S.BLOW” LED Does Not Turn on at All or


Turns on Frequently
a) Check if the complete blowdown/soot blow time of the MI Terminal MT1-200 is set properly.
If the complete blowdown/soot blow notification timing is set to 0, no notification will be set
off.
The notification timing is set by hours. Check for proper setting.

P. 32, 33

48
SECTION 4 BREAKDOWN AND COUNTERMEASURES

6. When Automatic Rotation Is Not Performed or Automatic Rotation


Does Not Change The Priorities
a) Check if the MI Terminal MT1-2t00 of the boiler No.(*)1 is set for automatic rotation(*).
Unless the rotation(*) flag is set between 1 and 7, automatic rotation(*) will not be performed in
a given period of time. If the rotation(*) flag is set to 0 or 9, automatic rotation(*) will not be
performed. Check for proper setting.

P. 32

b) Check if the rotation(*) flag of the boiler, of which priority(*) does not change, is set to 9.
Priority(*) is fixed for the boiler of which rotation(*) flag is set to 9. Check for proper setting.

P. 32

c) Check if the power supply is turned off at the rotation(*) time.


If the Pressure Controller MP1-200 or the MI Terminal MT1-200 is turned off at the rotation(*)
time, rotation(*) will not be performed. Change the rotation(*) time or do not turn off the unit.

d) Check if the cumulative combustion time is larger (or smaller) than that of other boilers.
Under the automatic rotation(*), the MI Terminal MT1-200 determines the priorities(*) of the
boilers in ascending order of the cumulative combustion time. Check the cumulative
combustion time.

P. 19

7. When the Boilers Do Not Fire According to the Priorities


In the following cases, the actual order of firing boilers is different from the priorities(*).
a) When the same priority is given to multiple boilers.
The boilers are prioritized based on larger boiler numbers(*).
Example: When three boilers are used
Boiler No.(*) Priority(*) Actual order
1 1 2
2 1 1
3 2 3

49
SECTION 4 BREAKDOWN AND COUNTERMEASURES

b) When the complete blowdown notification timer is reset


In the case where the priority combustion time after complete blowdown is set to a number
other than 0 with the MI Terminal MT1-200, the controller allows the prioritized boiler to be
fired up when the user resets the complete blowdown notification timer after complete
blowdown notification is set off.
Prioritized combustion is performed during the time period preset with the MI Terminal
MT1-200 or until the boiler starts surface blowdown.
If the complete blowdown notification timer is reset on multiple boilers at around the same
time, priorities are given in the order of resetting.

c) At backup control
In the following cases, the priorities(*) do not change.
• If any abnormality prevents the controller from controlling a boiler, the controller
does not count the boiler in the number of controlled boilers and allows the other
boilers with successive priorities(*) to fire up in order.
• The controller fires up the other boilers with lower priorities(*) temporarily during
pre-purge (especially when priority(*) is changed) to ensure stable operation.

8. Warning displayed on MI Terminal of MT1-200

When there is warning displayed on MI Terminal of MT1-200, Please see the chart below for how to
handle issues.
Pressing on the Select switch will reset the display windows.

Display Countermeasure
There is trouble in the machine. Please contact the maintenance
company.
MP1 is not functioning and the boiler operation has been switched to
manual operation.

Please contact the maintenance company. There is a warning


happening on the boiler.
MP1 is malfunctioning.
Please set Time and Date.
Auto rotation is not functioning.

50
SECTION 5 STORAGE

SECTION 5 STORAGE
1. Transfer or Resale

Ensure that the boiler is installed only in the specified condition and connected to the
specified peripheral equipment.
Failure to observe this precaution may result in injury.

When moving, reselling, or reusing the equipment, the location of installation and the facilities must
be confirmed to cause no trouble to normal operation of the equipment; contact a MIURA sales
office or your local dealer.
Inappropriate installation or unsuitable peripheral equipment may cause personal injuries. When
reselling our products, pass the operation manual and product-related documentation together on to
the next user.

51
SECTION 6 WARRANTY

SECTION 6 WARRANTY
1. Note Regarding Warranty
Miura Manufacturing America Co., Ltd., and Miura Boiler Co., Ltd., at its discretion, will repair or
replace at no charge (excluding shipping and labor charges) any Miura component, if found to be
defective in workmanship or material within twelve months from the date of commissioning or eighteen
months from the date of shipment from the factory, whichever occurs first.
All claims for the above warranty are to be presented in writing to a Miura factory or a Miura office for
review within 10 days of discovery of any defects.
The above limited warranty is given by Miura to the original purchaser only and is not assignable or
transferable to subsequent purchasers or lessees.

MIURA EXTENDS NO WARRANTY OF ANY KIND, EXPRESS OR IMPLIED, INCLUDING ANY


IMPLIED WARRANTY OF MERCHANTABILITY OR SUITABILITY FOR PURPOSE WITH RESPECT
TO THE BOILER OR ITS COMPONENTS OR WITH RESPECT TO SERVICES PROVIDED BY
MIURA. EXCEPT AS PROVIDED HEREIN, UNDER NO CIRCUMSTANCES WILL MIURA BE
LIABLE TO PURCHASER UNDER ANY TORT, NEGLEGENCE, STRICT LIABILITY, CONTRACT
OR OTHER LEGAL OR EQUITABLE THEORY, FOR ANY LOSS OF USE, LOSS OF TIME,
INCONVENIENCE, COMMERCIAL LOSS, LOST PROFITS OR SAVINGS OR OTHER INCIDENTAL,
SPECIAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OR INABILITY TO USE
SUCH BOILER OR FOR PURCHASER’S COST OF EFFECTING COVER, TO THE FULL EXTENT
SUCH MAY BE DISCLAIMED BY LAW. PURCHASER SHALL INDEMNIFY AND HOLD HARMLESS
MIURA, ITS OFFICERS, AGENTS AND EMPLOYEES FROM AND AGAINST ANY AND ALL
LIABILITIES, DAMAGES AND LOSSES, INCLUDING COSTS AND EXPENSES IN CONNECTION
THEREWITH, FOR DEATH OF, OR INJURY, TO ANY PERSONS WHOMSOEVER AND FOR THE
LOSS OF, DAMAGE TO OR DESTRUCTION OF ANY PROPERTY WHATSOEVER, CAUSED BY,
ARISING OUT OF OR IN ANY WAY CONNECTED WITH THE USE OF THE BOILER BY
PURCHASER.

2. Inquiries Regarding the Product or Operation Manual


If you have any questions regarding the product or the content of this Operation Manual, contact your
local MIURA sales office.
(A list of contact points is provided on the back cover.)

52
SECTION 7 APPENDIX

SECTION 7 APPENDIX
1. Purchasing Individual Operation Manuals
If you need the operation manual of the Pressure Controller MP1-200/MI Terminal MT1-200, contact
a MIURA sales office.
Have your operation manual code number on the cover ready when calling.

53
SECTION 7 APPENDIX

MEMO

54
MEMO

You might also like