AHU December 9, 2022

START

AUTO MODE NO MAN MODE YES

YES
NO

AHU ALARM ACTIVE

INACTIVE

SCHEDULE OFF AHU STOP

ON

AHU START

END

APPLY FOR: AHU-B1F-1


AHU-MF-01
Page 1
AHU START December 9, 2022

START

MODULATING DAMPER POSITION


CONTROLLED 100%

DELAY TIME

MODULATING DAMPER
NO
FEEDBACK > 90%

YES

SUPPLY FAN START

DELAY TIME

SUPPLY FAN STATUS OFF AHU ALARM ON

ON

MODULATING DAMPER POSITION


CONTROLLED FOLLOW PID FUNCTION

FAN SPEED CONTROLLED FOLLOW


PID FUNCTION

END

APPLY FOR: AHU-B1F-1


AHU-MF-01
Page 2
AHU STOP December 9, 2022

START

SUPPLY FAN STOP

DELAY TIME

SUPPLY FAN STATUS ON

OFF

MODULATING DAMPER
POSITION CONTROLLED CLOSE

DELAY TIME

SUPPLY FAN STATUS ON AHU ALARM ON

OFF

END

APPLY FOR: AHU-B1F-1


AHU-MF-01
Page 3
FRESH AIR MODULATING DAMPER December 9, 2022

START

AUTO MODE NO MAN MODE NO

YES

AHU COMMAND STOP

START YES

FAN STATUS OFF FAN STATUS ON

ON

MODULATING DAMPER
CO2 SENSOR OFF POSITION CONTROLLED
FOLLOW REQUEST

MODULATING DAMPER MODULATING DAMPER MODULATING DAMPER


POSITION CONTROLLED POSITION CONTROLLED POSITION CONTROLLED
FOLLOW PID FUNCTION 100% CLOSE

END

APPLY FOR: AHU-B1F-1


AHU-MF-01
Page 4
RETURN AIR MODULATING DAMPER December 9, 2022

START

AUTO MODE NO MAN MODE NO

YES

AHU COMMAND STOP

START YES

FAN STATUS OFF FAN STATUS ON

ON

MODULATING DAMPER
CO2 SENSOR OFF POSITION CONTROLLED
FOLLOW REQUEST

MODULATING DAMPER MODULATING DAMPER MODULATING DAMPER


POSITION CONTROLLED POSITION CONTROLLED POSITION CONTROLLED
FOLLOW PID FUNCTION 100% CLOSE

END

APPLY FOR: AHU-MF-01 Page 5


SUPPLY FAN December 9, 2022

APPLY FOR: AHU-B1F-1


START AHU-MF-01

AUTO MODE NO MAN MODE YES

YES
NO

AHU COMMAND STOP

START

FAN ALARM ACTIVE

INACTIVE

MODULATING DAMPER
NO
POSITION FEEDBACK > 90%

YES

FAN COMMAND START,


FAN COMMAND START FAN COMMAND STOP FAN SPEED CONTROLLED FOLLOW
REQUEST

SUPPLY PRESSURE
SENSOR

FAN SPEED CONTROLLED FOLLOW


PID FUNCTION

DELAY TIME

ON FAN STATUS

OFF

FAN ALARM

END
Page 6