Professional Documents
Culture Documents
Working Group
B1.32
April 2012
RECOMMENDATIONS FOR TESTING DC
EXTRUDED CABLE SYSTEMS FOR POWER
TRANSMISSION AT A RATED VOLTAGE
UP TO 500 kV
WG B1.32
Members
B. SANDEN, Convenor (NO), J. MATALLANA, Secretary (NO),
J.-L. PARPAL (2009) (CA), A. MACPHAIL (2009-2011) (CA), D. WALD (CH), T. KVARTS (DK),
L. BENARD (FR), E. ZACCONE (IT), S. HIRANO (JP), J.-N. KIM (KR),
R. BODEGA (NL), M. JEROENSE (SE), R. SVOMA (UK)
Corresponding members
J. FERENCZ (AU), L. COLLA (IT), S. ECKROAD (US)
Copyright © 2012
“Ownership of a CIGRE publication, whether in paper form or on electronic support only infers right
of use for personal purposes. Are prohibited, except if explicitly agreed by CIGRE, total or partial
reproduction of the publication for use other than personal and transfer to a third party; hence
circulation on any intranet or other company network is forbidden”.
Disclaimer notice
“CIGRE gives no warranty or assurance about the contents of this publication, nor does it accept
any responsibility, as to the accuracy or exhaustiveness of the information. All implied warranties
and conditions are excluded to the maximum extent permitted by law”.
ISBN : 978-2-85873-188-6
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
TABLE OF CONTENTS
1 INTRODUCTION 4
1.1 Background 4
1.2 Scope 4
1.3 Revisions 5
1.4 Summary of tests 5
1.5 Definitions 6
2 DEVELOPMENT TESTS 12
3 PREQUALIFICATION TESTS 13
3.1 Range of approval 13
3.2 Summary of prequalification tests 14
3.3 Test arrangement 14
3.4 Long duration voltage test 14
3.5 Superimposed switching impulse voltage test 15
3.6 Examination 16
3.7 Success criteria, re-testing and interruptions 16
4 TYPE TESTS 17
4.1 Range of approval 17
4.2 Test objects 17
4.3 Non-electrical type tests 18
4.4 Electrical type test 18
4.5 Return cable - type test 21
5 ROUTINE TESTS 23
5.1 Routine tests on transmission cables 23
5.2 Routine tests on cable accessories 23
5.3 Return cables or conductors 24
6 SAMPLE TESTS 25
6.1 Sample tests on transmission cables 25
6.2 Sample tests on factory joints for submarine cables 25
6.3 Sample tests on repair joints and terminations 26
6.4 Sample tests on field moulded joints 26
7 AFTER INSTALLATIONS TESTS 27
7.1 High voltage test 27
7.2 Test on polymeric sheaths 27
7.3 TDR measurement 27
REFERENCES 28
APPENDIX A: DERIVATION OF TEST PARAMETERS 30
APPENDIX B: TECHNICAL BASIS FOR THE DETAILED PREQUALIFICATION TEST SCHEMES 34
APPENDIX C: SCHEMATIC REPRESENTATION OF THE SEQUENCE OF TESTS FOR LAND AND SUBMARINE
CABLES 35
APPENDIX D: COMPARISON WITH GUIDELINES AND RECOMMENDATIONS FOR TRANSMISSION CABLE
TESTS 36
Page 3
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
1 INTRODUCTION
1.1 Background
In 2003 TB 219 “Recommendations for testing DC extruded cable systems for power transmission at a
rated voltage up to 250 kV” was issued by Cigré study committee B1 [0]. This was the first document
issuing recommendations for testing of high voltage DC extruded cable systems. The recommendation
was recognised by a large and relevant technical community and has become the reference for the user
community. In 2008 it was decided by SC B1 to launch a new working group to prepare
recommendations for testing DC extruded cables systems at a rated voltage up to 500 kV. The decision
was motivated by the fact that commercially available HVDC extruded systems above 250 kV were
emerging.
At the time of preparing this recommendation there is laboratory experience at voltages up to and
including 500 kV, but operating experience is limited to 200 kV [1]. Contracts have been awarded at a
voltage level up to 320 kV [2]. A further increase in voltage level is to be expected and this
recommendation will therefore cover voltages up to 500 kV. However, it is important to emphasise that
the lack of operational experience above 200 kV and the limited number of tests at higher voltage levels
represent an uncertainty in the preparation of this recommendation. Consequently new relevant
knowledge that emerges from increased testing and/or service experience at higher voltages may
necessitate new revisions of this recommendation in the future.
The tests in this recommendation follow the same principles as in TB 219. For completeness, the
backgrounds for the different tests are included also in this recommendation. The philosophy adopted is
that the tests recommended should apply to the complete HVDC cable system as installed and as
intended to function. Wherever possible, the tests are based on existing recommendations, standards
and practices. It must be recognised that DC extruded cables may involve the use of many different
materials such as thermoplastic or crosslinked polymers (either filled or unfilled) and differing
manufacturing processes. In consequence, the tests recommended are largely functional and not
specific to one material or manufacturing process.
1.2 Scope
This document recommends a series of tests on extruded cables for DC power transmission systems
(land or submarine cables with their accessories in fixed installations) up to and including 500 kV. Within
the scope of these recommendations “extruded” shall mean either filled (e.g. with mineral or carbon) or
unfilled and either thermoplastic (e.g. polyethylene, etc.) or thermoset (e.g. crosslinked polyethylene,
ethylene propylene rubber, etc.) insulations.
Page 4
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
1.3 Revisions
Essential in TB 219 are the principles for determination of voltage test factors and duration of the
different test sequences. The WG have had thorough discussions of this approach extended to higher
voltage levels and there is a consensus in the WG that these principles shall be adopted also for the
recommendation covering higher voltage levels. Consequently, the voltage test factors and test
sequences from TB 219 are kept in this recommendation.
The main changes made to the text of TB 219 can be summarised as follows:
- The voltage range covered is extended up to 500 kV.
- The text has been updated to take into account the latest revisions of IEC 60840 (Edition 4) [3]
and IEC 62067 (Edition 2) [4].
- The range of approval for both prequalification tests and type tests has been revised.
- For the load cycle blocks of the prequalification test, the requirement has been changed from
number of days to number of cycles.
- Recommendations for routine and sample tests on cable accessories have been included.
Development tests Tests made during the development of the cable system.
Prequalification test Test made before supplying on a general commercial basis a type of
cable system covered by this recommendation, in order to
demonstrate satisfactory long term performance of the complete
cable system.
NOTE 1: The prequalification test need only be carried out once unless there is a
substantial change in the cable system with respect to material, manufacturing
process, design or design electrical stress levels.
NOTE 2: A substantial change is defined as that which might adversely affect the
performance of the cable system. The supplier should provide a detailed case,
including test evidence, if modifications are introduced, which are claimed not to
constitute a substantial change.
Type tests Tests made before supplying on a general commercial basis a type of
cable system covered by this recommendation, in order to
demonstrate satisfactory performance characteristics to meet the
intended application.
NOTE: Once successfully completed, these tests need not be repeated, unless
changes are made in the cable or accessory with respect to materials,
manufacturing process, design or design electrical stress levels, which might
adversely change the performance characteristics.
Page 5
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Tests after Tests made to demonstrate the integrity of the cable system as
installation installed.
1.5 Definitions
Where applicable, definitions are in line with IEC 60840 [3] and IEC 62067 [4].
1.5.1 General
Cable system A cable system consists of cables with installed accessories. Cable
accessories are typically joints and terminations. There may be other
types of accessories associated with a cable system (e.g. measuring
devices or fixtures). These need only to be incorporated in the test
objects to the extent that they are deemed to have an impact on the
operational characteristics of the cable system.
Return cable A return cable is the low/medium voltage DC cable used for the
return current in monopolar operation of HVDC schemes. The return
cable can either be connected over the full length between the
converters or only be connected for part of the length connecting a
converter to an electrode station.
Transmission cable A transmission cable refers to the high voltage cable of a monopolar
or bipolar scheme. The term is used in this document where
appropriate to distinguish from the return cable.
Page 6
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Extrusion length An extrusion length is the length of cable conductor with the
insulation and semiconducting layers continuously extruded in the
same non-interrupted extrusion operation (excluding possible
scrapped sections cut off from the starting and ending sections).
Manufacturing length A manufacturing length is a whole extrusion length (or parts thereof
if cut), where construction elements (outside the outer
semiconducting layer) have been applied.
Delivery length A delivery length may be one or more manufacturing lengths joined
with factory joints. A delivery length is typically the intended
shipping length of a submarine cable or the completed cable length
on a drum for a land cable.
Page 7
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Repair joint A repair joint is a joint between two cables that are completed with
all construction elements.
Field joint A field joint is a joint between two cables that are completed with all
construction elements and in a state as installed in the field in the
actual cable system.
NOTE: Test on joints between extruded cables and other types of insulation
technology (MI or oil filled) are not covered in this document. This should be
agreed between supplier and customer. If special considerations are needed in
case of transition joints between extruded cables, detailed agreements between
supplier and customer are recommended.
U0 is the rated DC voltage between conductor and core screen for which the cable
system is designed.
UT is the DC voltage during the type test and routine test. For the scope of this
recommendation UT = 1.85 x U0.
UTP1 is the DC voltage during the prequalification test (load cycle test), type test
(polarity reversal test) and test after installation. For the scope of this
recommendation UTP1 = 1.45 x U0.
UTP2 is the DC voltage during the prequalification polarity reversal test. For the scope
of this recommendation UTP2 = 1.25 x U0.
UP1 is 1.15 x the maximum absolute peak value (Figure 2) of the lightning impulse
voltage, which the cable system can experience when the impulse has the
opposite polarity to the actual DC voltage.
UP2,S is 1.15 x the maximum absolute peak value (Figure 2) of the switching impulse
voltage, which the cable system can experience when the impulse has the same
polarity as the actual DC voltage.
UP2,O is 1.15 x the maximum absolute peak value (Figure 2) of the switching impulse
voltage which the cable system can experience when the impulse has the
opposite polarity to the actual DC voltage.
Page 8
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
URC,AC is the maximum voltage a return cable can be subjected to due to temporary
damped alternating overvoltage. This voltage is typically induced by a
commutation failure, and the value should be supported by the supplier’s system
calculations of the HVDC link. The nature of the overvoltage depends upon the
configuration of the HVDC link and needs to be calculated for each case.
NOTES:
The ripple content of the DC test voltages shall not be greater than 3 percent.
Calibration shall be according to IEC 60060-1 [8].
The basis for the selection of test factors is described in Appendix A.
kV kV
U0 U P2,S U0
t
t - U P2,O
kV kV
t U P2,O
t
- U0 - U P2,S - U0
kV kV
U P1 U0
t
t
- U0
- U P1
LCC or VSC, positive lightning impulse LCC or VSC, negative lightning impulse
Figure 2: Schematic representations of the switching impulse and lightning impulse test voltages.
Due to the constraints within the DC system design UP2,S does not necessarily equal UP2,O, i.e. the same
polarity impulse is limited by surge arresters, but the opposite polarity impulse may be limited by the
converter.
Page 9
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
∆Tmax is the maximum temperature difference over the cable insulation in steady state
(not including semiconducting screens) at which the cable is designed to operate.
This value is to be calculated and stated by the supplier, who shall also provide
evidence of the correlation between this design value and data measured during
testing.
Load Cycles (LC) Load cycles consist of both a heating period and a cooling period.
“24 hours” load cycles (for prequalification and type tests) consist of at
least 8 hours of heating followed by at least 16 hours of natural cooling.
During at least the last 2 hours of the heating period, a conductor
temperature ≥ Tcond,max and a temperature drop across the insulation ≥
∆Tmax shall be maintained.
“48 hours” load cycles (for type test only) consist of at least 24 hours of
heating followed by at least 24 hours of natural cooling. During at least the
last 18 hours of the heating period, a conductor temperature ≥ Tcond,max and
a temperature drop across the insulation ≥ ∆Tmax shall be maintained. 48
hour load cycles are only required as part of the type test procedure to
ensure that electrical stress inversion is well advanced within the cycle.
High Load (HL) High Load consists of a continuous heating period. Within the first 8 hours
of the heating period conductor temperature ≥ Tcond,max and temperature
drop across the insulation ≥ ∆Tmax shall be achieved and maintained for the
rest of the High Load test.
NOTE: If, for practical reasons, the specified temperatures can not be reached within the
first 8 hours, a longer time can be used. This additional time shall not be constituted as
being part of the test period.
Impulse Test Conductor temperature ≥ Tcond,max and temperature drop across the
insulation ≥ ∆Tmax shall be reached for a minimum 10 hours before voltage
impulses (superimposed impulse, switching, lightning) are applied and shall
be maintained throughout the duration of the test .
Page 10
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Ambient Unless otherwise specified in the details for the particular test, tests shall
temperature be carried out at an ambient temperature of (20 ± 15) °C.
NOTE: If, for practical reasons, polarity reversals cannot be achieved within 2 minutes, the duration for polarity reversals shall
be agreed between customer and supplier.
If the average thickness of the insulation does not exceed the nominal value by more than 5%, the test
voltages shall be the values specified for the rated voltage of the cable.
If the average thickness of the insulation exceeds the nominal value by more than 5% but not by more
than 15%, the test voltage shall be adjusted by considering the following coefficient α to maintain the
same level of average electric field, e.g., a 10% increase in average insulation thickness shall be
accounted for by a 10% increase in the test voltage:
t
α=
tn
t = measured average insulation thickness
tn = declared nominal thickness
The cable length used for the electrical tests shall not have an average thickness exceeding the nominal
value by more than 15%.
Page 11
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
2 DEVELOPMENT TESTS
The manufacturer should complete all analyses and development testing prior to commencing the
prequalification test. The precise nature and extent of development work and analyses shall be left to
the discretion of the manufacturer, but may include the following:
- An evaluation of the materials and processes employed. Such evaluations would normally
include electrical resistivity assessments, breakdown tests and space charge measurements.
Example of space charge measurements is shown in Figure 3.
- An analysis of the electric stress distribution within the cable system insulation for a range of
typical installation and loading conditions.
- An assessment of the long-term stability, possibly involving factory experiments to assess the
ageing effects of various parameters, e.g., electrical stress, temperature, environmental
conditions etc.
- An assessment of the sensitivity of the electric stress distribution to the expected variations in
cable dimensions, material composition and process conditions (extrusion, post extrusion
treatments and finishing).
Figure 3: Space charge measurements aiming at selecting insulating materials with advantageous
space charge accumulation properties.
Page 12
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
3 PREQUALIFICATION TESTS
NOTE: It is the opinion of the WG that the Cigré TB 303 [11] can be regarded as a relevant document to assess the need for
further prequalification testing or not. However, the HVDC extruded cable system technology is at present considered to be
too immature to include the concept of “Extension of Qualification” in this document.
The prequalification test qualifies the manufacturer as a supplier of cable systems provided that the
following conditions are fulfilled:
a) The rated voltage U0 is not more than 10% higher than that of the tested cable system.
b) The calculated average electrical stress in the insulation (given by U0 divided by the nominal
insulation thickness) is less than or equal to that of the tested system.
c) The calculated Laplace electrical stress at U0 (using nominal dimensions) at the cable insulation
screen is less than or equal to that of the tested system.
d) The maximum conductor temperature Tcond,max is less than or equal to that of the tested system.
e) The maximum temperature drop across the insulation layer ∆Tmax (excluding the
semiconducting screens) is less than or equal to that of the tested system.
f) A cable system prequalified according to this recommendation for LCC is also prequalified for
VSC. A cable system prequalified according to this recommendation for VSC is not prequalified
for LCC.
g) An unarmoured cable prequalified according to this recommendation prequalifies an armoured
cable and vice versa.
NOTE 1: For the sake of clarity the conditions for range of approval do not involve considerations of DC electrical fields. In the
design of DC cable systems, the DC electrical fields are critical design criteria. The supplier must therefore have detailed
knowledge of the DC electrical fields in the cable system (cable and accessories) under all operating conditions and should be
able to present a detailed case upon request of the customer.
NOTE 2: It is recommended to carry out a prequalification test using a cable of a large conductor cross-section in order to
cover thermo-mechanical aspects.
NOTE 3: Prequalification tests that have been successfully performed according to TB 219 are valid.
NOTE 4: At the end of a prequalification test an impulse test must be performed. The reason for this test is to verify that no
major thermo-mechanical changes have taken place during the long-term testing. This test is not intended to qualify the
system for a specific impulse level. Project-specific impulse levels should be qualified during the type test.
Page 13
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
NOTE: The main objective of the prequalification test is to satisfactorily demonstrate the insulation integrity during long time
periods under DC, given the long dielectric time constants as compared to AC. It is however recognized that other aspects of a
specific installation may be important, such as the thermo-mechanical effects due to the installation conditions. The
representation of specific installation conditions in the test set-up should be considered.
Prior to the electrical prequalification test, the insulation thickness of the cable shall be checked as
specified in § 1.5.6.3.
The sequence of tests for LCC and VSC are shown in the tables below.
+ - + - - + - UP2,O = 1.2 x U0
Test Voltage
UP1 = 2.1 x U0*
UTP1 UTP1 UTP2 UTP1 UTP1 UTP1 UTP1 UTP1 UTP2
LC=Load Cycle, HL=High Load, PR=Polarity Reversal, ZL=Zero Load, S/IMP=Superimposed Impulse Test.
* If required
Page 14
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Number of 40 40 40 40 120 40 40
Not applicable
cycles or days cycles cycles days days days cycles cycles
+ - + - - + - UP2,O = 1.2 x U0
Test Voltage
UTP1 UTP1 UTP1 UTP1 UTP1 UTP1 UTP1 UP1 = 2.1 x U0*
LC=Load Cycle, HL=High Load, ZL=Zero Load, S/IMP=Superimposed Impulse Test.
* If required
NOTE: Ambient conditions may vary during the test and this is not considered to have any major influence. In such cases, the
conductor current shall be adjusted to maintain the conductor temperature and temperature drop across the insulation within
the specified limits.
The length and sequence of the thermal conditions were selected with regard to the particular electrical
effects that can occur in extruded insulations when operated under DC voltage. The technical basis for
the test durations is given in Appendix A.
A minimum rest period of 24 hours without voltage, but with heating, is recommended between blocks
of different polarities. This does not apply to the individual polarity reversals in the PR blocks of the LCC
test scheme.
UP2,O = 1.2 x U0
UP1 = 2.1 x U0 (if required)
Project specific requirements regarding impulse levels should be covered by the electrical type test (§
4.4).
The test shall be performed according to § 1.5.6.2 on one or more cable samples, with a minimum total
active length of 30 m cut from the assembly. The temperature conditions are defined in § 1.5.5.
NOTE: As an alternative, the test may be carried out on the whole test assembly.
The cable samples shall withstand without failure 10 positive and 10 negative superimposed switching
impulses at the voltage levels UP2,O.
Page 15
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
If by agreement between supplier and customer a lightning impulse test is also to be performed, the
cable samples shall withstand without failure 10 positive and 10 negative superimposed lightning
impulses at the voltage level UP1.
3.6 Examination
Examination of the cable by dissection of a sample and, whenever possible, of the accessories by
dismantling, with normal or corrected vision without magnification, shall reveal no signs of deterioration
(e.g., electrical degradation, leakage, corrosion or harmful shrinkage) which could affect the system in
service operation.
If there is a breakdown in a test object the complete prequalification test shall be repeated for that
particular test object.
If a breakdown of a test object occurs, causing an interruption to the ongoing testing of connected test
objects, the test may be resumed after the failed test object is removed. The actual load cycle or
impulse during which the failure occurred shall be repeated for the remaining test objects. If breakdown
occurs during a constant load period the time elapsed without voltage applied shall be added to the
remaining test period.
After any interruption, for example an interruption caused by external factors the test may be resumed.
If the interruption is longer than 30 minutes, the specific lost load cycle shall be repeated. If the
interruption occurs during a constant load period and is longer than 30 minutes, the day the
interruption occurred shall be repeated.
Page 16
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
4 TYPE TESTS
a) The actual designs, materials, manufacturing processes and service conditions for the cable
system are in all essential aspects equal.
b) All service voltages, U0, UP1, UP2,S and UP2,O (URC,AC and URC,DC in case of return cable), are less
than or equal to those of the tested cable system.
c) The mechanical stresses to be applied during preconditioning are less than or equal to those of
the tested cable system.
d) The service maximum conductor temperature Tcond,max is less than or equal to that of the tested
cable system.
e) The maximum temperature drop across the insulation layer ∆Tmax (excluding the
semiconducting screens) is less than or equal to that of the tested cable system.
f) The actual conductor cross-section is not larger than that of the tested cable system.
g) The calculated average electrical stress in the insulation (given by U0 divided by the nominal
insulation thickness) is less than or equal to that of the tested system.
h) The calculated Laplace electrical stress (using nominal dimensions) at the cable conductor and
insulation screen is less than or equal to that of the tested system.
i) A cable system qualified according to this recommendation for LCC is also qualified for VSC
provided the switching impulse withstand tests at ±UP2,S voltage levels as specified in § 4.4.3.3
are carried out. A cable system qualified according to this recommendation for VSC is not
qualified for LCC.
NOTE 1: For the sake of clarity the conditions for range of approval do not involve considerations of DC electrical fields. In the
design of DC cable systems, the DC electrical fields are critical design criteria. The supplier must therefore have detailed
knowledge of the DC electrical fields in the cable system (cable and accessories) under all operating conditions and should be
able to present a detailed case upon request of the customer.
NOTE 2: Type tests which have been successfully performed according to TB 219 are valid.
The non-electrical type tests (see § 4.3) need not be carried out on samples from cables of different
voltage ratings and/or conductor cross-sectional areas unless different materials and/or different
manufacturing processes are used to produce them. However, repetition of the ageing tests on pieces of
complete cable to check compatibility of materials (see IEC 62067 [4]) may be required if the
combination of materials applied over the screened core is different from that of the cable on which
type tests have been carried out previously.
Page 17
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
By definition, an accessory includes 0.5 m of cable on each side (Figure 1), measured from the point on
the cable where no disassembling or dismantling for the purpose of installation of the accessory has
taken place. The non-interrupted cable length between accessories (Figure 1) in a test loop shall be a
minimum of 5 m. A minimum of 10 m of continuous non-interrupted cable shall be included in a test
loop.
Any non-continuous design feature (such as a metallic connection between metallic layers) shall be
included in the cable test object.
Test objects for land or submarine application shall be subjected to the appropriate mechanical
preconditioning.
Test objects for the electrical and non-electrical type tests must not necessarily be the same physical
samples unless required by the recommendation for the non-electrical test.
Cable systems intended for installation on land where water blocking is included shall be subjected to a
water penetration test as specified in IEC 62067 [4].
Cable systems intended to be installed as submarine cables shall be subjected to water integrity testing
as specified in Electra 189 [12]. This test would also qualify the cable for installation on land.
Cables with metallic earthing connections through plastic sheaths shall be subjected to the test in
Electra [9].
Prior to the electrical type test, the insulation thickness of the cable shall be checked as specified in §
1.5.6.3.
Page 18
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Cable systems intended to be installed as submarine cables shall be subjected to mechanical tests as
specified in Electra 171 [13].
4.4.2.1 General
The load cycle test shall be performed on test objects that have been subjected to the appropriate
mechanical preconditioning. Accessories in the cable system that are not relevant for mechanical
preconditioning are to be installed as test objects together with the preconditioned test objects.
If the test loop consists of cables with different designs connected with a transition joint, then each
cable design is qualified to the relevant thermal conditions (Tcond,max and ∆T) and the transition joint is
qualified to the higher temperature. (Note that this means that the cable on one side of the transition
joint under test may not have been qualified in this test to its maximum temperature in the scheme).
4.4.2.2 Load cycle test for cable system to be qualified for LCC
The test objects shall be subjected to the following conditions (definitions of “24 hours” load cycles and
“48 hours” load cycles are described in § 1.5.5):
A minimum rest period of 24 hours without voltage but with heating is recommended between blocks of
different polarities. This does not apply to the individual polarity reversals in the PR blocks.
Positive polarity was selected for the “48 hours” load cycles as this is believed to be the most stringent
condition for accessories.
4.4.2.3 Load cycle test for cable system to be qualified for VSC
The test objects shall be subjected to:
A minimum rest period of 24 hours without voltage but with heating is recommended between blocks of
different polarities.
Positive polarity was selected for the “48 hours” load cycles as this is believed to be the most stringent
condition for accessories.
Page 19
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
4.4.3.1 General
The superimposed impulse voltage test is to be performed on test objects that have successfully passed
the load cycle test.
4.4.3.2 Switching impulse withstand test for cable system to be qualified for LCC
4.4.3.3 Switching impulse withstand test for cable system to be qualified for VSC
Page 20
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
4.4.5 Examination
4.4.5.2 Cables with a longitudinally applied metal tape or foil, bonded to the oversheath
A 1 m sample shall be taken from the cable length and subjected to the tests and requirements in IEC
62067 [4].
After any interruption, for example an interruption caused by external factors the test may be resumed.
If the interruption is longer than 30 minutes, the specific lost load cycle shall be repeated. If the
interruption is longer than 24 hours, the actual test block (“24 hours” load cycles block at negative or
positive polarity, “24 hours” load cycles block with polarity reversals, “48 hours” load cycles block under
positive polarity) shall be repeated.
In case of deviations in test parameters during load cycles or superimposed impulse voltage test, the
load cycle or the superimposed impulse in question shall be repeated.
In case of a breakdown of insulation, when testing several objects simultaneously, the faulty object may
be removed and the incident treated as an interruption. The faulty object is considered to have failed
the test requirements. Any fault within any extension (0.5 m) to a test object, for example an accessory,
is considered to be associated with that test object only.
4.5.1 General
Return cables are grounded at one end and are subjected to a DC voltage determined by the cable
resistance and the current at the other end of the link. System calculations, taking into account the
different fault scenarios, should be performed by the supplier to determine the relevant temporary
over-voltages in the power frequency domain for the return cable for the actual link. In particular,
temporary over-voltages caused by commutation failure may be the criteria for dimensioning of the
return cable insulation and accessories. To verify that the cable system can withstand over-voltages
caused by commutation failure an AC voltage test at power frequency shall be performed.
If different designs (different insulation thicknesses) are used along the return path, each design shall be
considered individually.
Page 21
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Return cables may be protected by surge arresters, in which case this feature shall be taken into
consideration in the system studies and consequently in determining URC,AC.
Page 22
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
5 ROUTINE TESTS
Routine tests (which include what is in some other documents referred to as Factory Acceptance Test)
are made to demonstrate the integrity of the delivery lengths.
The experience of using DC voltage for routine testing of extruded DC cables is limited. It is the opinion
of the WG that in addition to the DC test, testing with AC voltage could be considered provided that the
insulation system and the cable design allow AC testing. Long manufacturing lengths and high voltage
levels may render AC testing impractical. In the event that AC testing is employed, the voltage level,
frequency (power or other frequencies) and time of application shall be agreed between the supplier
and customer.
If required for the particular contract or order, the oversheath may be subjected to the routine electrical
test specified in IEC 60229 [14].
Page 23
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
The AC voltage test and the partial discharge measurement may be carried out if applicable to the cable
insulation system. The procedure and requirement for these tests will be in accordance with the quality
assurance procedures of the manufacturer. X-ray inspection gives additional information regarding the
quality of interfaces and possible metallic inclusions. All joints in the complete delivery length shall be
DC voltage tested in the high voltage test described in § 5.1. However, a screening DC or AC voltage test
directly after jointing would reduce the time delay in case the joint were to fail at a later stage in the
production process. In addition, it is recommended that each welded conductor joint be checked by an
X-ray inspection. Even if each factory joint is routine tested, the joint must be installed by experienced
personnel. It is recommended that the supplier show qualification records of jointers.
Page 24
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
6 SAMPLE TESTS
Cables and certain types of cable accessories shall have tests carried out on samples.
NOTE: For materials which are not considered by IEC 60840 and IEC 62067, the test program shall be agreed between
manufacturer and customer
6.1.11 Tests on components of cables with longitudinally applied metal tape or foil, bonded to the
oversheath, if applicable
If the factory joint is type tested under the contract, the tests in § 6.2.1 to 6.2.4 may be omitted.
Page 25
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Page 26
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
The installed return cable system shall be subjected to a negative polarity DC voltage that has been
agreed between the supplier and the customer. The test duration shall be 1 hour. Negative polarity shall
be used regardless of the polarity of the pole.
If TDR equipment is to be used with the cable link it is advisable to perform a TDR measurement to
obtain a “fingerprint” of the wave propagation characteristics of the cable. The propagation of the
pulses used during TDR measurements is dependent upon resistance, capacitance and inductance of the
cable. As all electrical signals travel so as to consume a minimum of energy, the pulse propagates where
the inductance/resistance is its lowest. Submarine power cables have a metallic screen and the pulses
do not propagate outside the screen since the inductance (and impedance) would increase considerably.
Hence the pulse is not affected by the coiling on a turntable or after installation.
Figure 4: Circuit diagram for TDR testing, traditional transmission line diagram, π-model.
Page 27
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
REFERENCES
[0] Cigré TB 219, Recommendations for testing DC extruded cable Cigré TB 219
systems for power transmission at a rated voltage up to 250 kV,
Cigré WG 21-01, March 2003
[3] Power cables with extruded insulation and their accessories for IEC 60840 Ed 4
rated voltages above 30 kV (Um=36 kV) up to 150 kV (Um=170 kV) -
Test methods and requirements, 2011
[4] Power cables with extruded insulation and their accessories for IEC 62067 Ed 2
rated voltages above 150 kV (Um=170 kV) up to 500 kV (Um=550
kV) - Test methods and requirements, 2011
[5] Terminology for High Voltage Direct Current (HVDC) transmission, IEC 60633 Ed 2.1
2009
[7] Accessories for HV cables with extruded insulation, Cigré WG 26- Cigré TB 177
06, February 2001
[8] High-voltage test techniques. Part 1: General definitions and test IEC 60060-1 Ed 3
requirements, 2010
[9] Recommendations for tests of power transmission DC cables for a Electra 189
rated voltage up to 800 kV (Electra 72, 1980 - revision), April 2000
[10] Common test methods for insulating and sheathing materials of IEC 60811-1-1 Ed 2.1
electric cables and optical cables – Part 1-1: Methods for general
application – Measurement of thickness and overall dimensions –
Tests for determining the mechanical properties, 2001
Page 28
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
[12] Recommendations for testing of long AC submarine cables with Electra 189
extruded insulation for system voltage above 30 (36) to 150 (170)
kV, April 2000
[14] Tests on cable oversheaths which have a special protective IEC 60229 Ed 3
function and are applied by extrusion, 2007
[17] B. Aladenize, R.Coelho, F. Guillaumond and P. Mirebeau, “On the Journal of electrostatics,
intrinsic space charge in a DC power cable”, 1997 39, (1997) pp 235-251
Page 29
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
DC VOLTAGE FACTORS
The multiplication factors for the test voltages and periods have been determined based on
consideration of the available voltage-time (V-t) characteristics. The precise nature of the V-t
characteristic has not been determined for DC operation. However the WG was of the opinion that the
Inverse Power Law model provided a conservative basis for the work. The precise details of the
approach are shown below:
V n ×t = const
where:
V : voltage
t : time
n : life exponent from V-t characteristics
Vdc = V0 ×K1
where:
V0 : system voltage
K1 : test voltage ageing factor
t0
K1 = n
t1
where:
t0 : design life
t1 : test duration
Using the approach described above it is possible to determine the test voltage factors that are
equivalent to a prescribed system life when testing for a shorter time. In this work the WG has used a
system life of 40 years. The approach requires knowledge of the exponent “n” which is determined
empirically from endurance tests on cables. The knowledge of “n” under DC was not sufficient for the
WG to identify a precise value at the time this brochure was written. However the WG was able to
estimate a lower limit (n = 10), which was used to determine the test voltage factor.
Page 30
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
On this basis the WG identified a test factor of 1.45 as equivalent to approximately 40 years operation at
rated voltage when applied for 1 year and a test factor of 1.85 as equivalent to approximately 40 years
operation at rated voltage when applied for 30 days.
IMPULSE
In the light of the good experience which has resulted from the use of the previous Electra
recommendations within [9] [15] [16] it was decided that the same approach to selection of test factors
would be applied.
POLARITY REVERSAL
The approach for test factors is based on the principle of applying the same additional voltage for the
polarity reversal as that applied for the constant voltage test. This approach has been used in previous
DC recommendations. The table sets out previous practice relating the polarity reversal tests and the
used test factors.
For example: at a polarity reversal in real operation, the cable system experiences a voltage step of
2 x U0. Applying a test factor of 1.45 in a polarity reversal test gives that the cable system under test
experiences a voltage step of 2 x 1.45 x U0 = 2.9 x U0, i.e. 0.9 x U0 more than in real operation.
Page 31
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Additional
Voltage during
Document Condition Test Factor Test Voltage Comment
Test vs
Operation
Cigré TB 219 [0] Constant voltage 1.85 1.85 x U0 0.85 x U0 Test in Hot
Type test Polarity reversal 1.45 2 x (1.45 x U0) 0.9 x U0 Condition
Cigré TB 219 [0] Constant voltage 1.45 1.45 x U0 0.45 x U0 Test in Hot
Prequalification test Polarity reversal 1.25 2 x (1.25 x U0) 0.5 x U0 Condition
Calculations show that a time equivalent to 10 τ must pass to approach the steady state distribution of
the divergence. The table below gives the range of times to stability (10 τ) as a function of temperature
for different materials that are likely to be used for DC extruded cables. Practically, this means that the
time to achieve a stable electrical stress distribution will depend upon temperature. Thus, it is important
to select test times that permit probable insulation systems to reach a stable electrical stress
distribution. These considerations provide the foundations for the times of the Zero Load, High Load and
48 hour Load Cycle Tests in the recommendations.
Page 32
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Injection of charges from the electrodes may also occur, but the 10 τ time constant covers the time
needed for these injection processes to reach a steady state.
In addition, considering the actual usage of HVDC links, the experimentation constraints and the total
time of the tests the WG adopted the following testing times. The WG judged that they would “test” the
performance of the proposed HVDC insulation systems in a practical manner [17], [18]:
At least maximal
conductor temperature 1
48 Hour Load Cycle: 0.003<10 τ <1.8
(60°C to 90°C depending (heating period)
(Type Approval)
on manufacturer design)
It is the opinion of the WG that higher resistivity materials may be developed in the future and therefore
that it may become necessary to review the duration of the test cycles.
Page 33
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
The development of the detailed technical test schemes described in § 3.4 has been guided by the
following principles:
Page 34
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Lightning
(§ 4.4.3.4)
Subsequent DC
(§ 4.4.3.5)
Page 35
TRANSMISSION CABLE TESTS
APPENDIX D: COMPARISON WITH GUIDELINES AND RECOMMENDATIONS FOR
Cables with Extruded Rec. for Electrical Tests
Recommendations for Testing DC Recommendations for Testing of High voltage tests on cross-linked Specification for extruded
Recommendations for Tests of Insulation and Their Cables with Extruded Insulation Prequalification and Development
Extruded Cable System for Power Long AC Submarine Cables with polyethylene insulated cables and insulation power cables and
Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV
Power Transmission DC Cables for Accessories for Rated and Their Accessories for Rated on Extruded Cables and
Transmission at a rated voltage up Extruded Insulation for System their accessories for rated voltage their accessories rated
A Rated Voltage up to 800kV Voltages above 150kV Voltages above 30kV up to150kV Accessories at Voltages >150kV
to 250 kV Voltage above 30 to 150kV from 11kV up to 275 kV above 46kV to 345 kV
up to 500kV and <400kV
1.4xU0x60, every 4h, 10 l.c. Switching impulse voltage Switching impulse voltage test Load cycle test = IEC 60840
Load Cycle Test Superimposed cable, n=12 for taped joint)
Superimposed impulse test :- test Lightning impulse Partial discharge test
Lightning Impulse Test Subsequent DC
U0+1.15Imp, U0-1.15Imp Lightning impulse Ligthning Impulse test
Test
DC voltage test
(oversheath)
High Voltage Test : -1.45xU0x15min DC voltage test (oversheath) AC voltage test
After Installation AC voltage test
Test on Polymeric Sheaths : according DC voltage test : 1.4xU0, 15min. AC voltage test (insulation): U0 24h or : 1.7xU0, 90min. Not defined
Test (insulation): U0 24h or
to IEC 60229 TDR for information or voltage dependent factor 1h : 1.0xU0, 24hours
1.7xU0 1h or voltage
dependent factor 1h