You are on page 1of 1

Dat e Page

Test report 2/15/2023 1

Circuit Breaker

Circuit Breaker Data Test Data


Breaker ID1 220kv stps Test ID test1
Breaker ID2 Test date 2/26/2022
Breaker ID3 Type Overhaul test
Breaker ID4 Referen ce
Serial no. Counter
Commission date Operator TM1800
Interruping medium Plan ID Created in TM1800
Rated frequency Hz Plan description Created in TM1800
Rated voltage kV
Rated current A
Rated short-circuit breaking current kA
Rated motor voltage V
Rated supply voltage V

V CCMD1: 500 V/d iv

I CCIR1: 5 A/d iv

t CCMD1

V TCMD1: 500 V/div

I T CIR1 : 0.1 A/d iv

t TCMD1

I CIR1: 2 A/div

t A 01R

t A 01M

0.0 10. 0 20. 0 30. 0 40. 0 50. 0 60. 0 70. 0 80. 0 90. 0 100 .0 110 .0 120 .0 130 .0 140 .0 150 .0 160 .0 170 .0 180 .0 190 .0 200 .0 210 .0 220 .0 230 .0 240 .0 250 .0 260 .0 270 .0 280 .0 290 .0 300 .0 310 .0

Scale = 10.0 ms/divs

Parameters Value Unit


Close time A 01M 67.000 ms
Close time A 01R 67.000 ms
Cls df M-R A 01R 0.000 ms
Opn df M-R A 01R 0.000 ms
CO time A 279.100 ms
C contr. V CCMD1 89.5 V
O contr. V TCMD1 90.0 V
Temp. -- -- -- °C
Temp. -- -- -- °F