Test report 2/22/2023 1

Circuit Breaker

Circuit Breaker Data Test Data


Breaker ID1 100 MVA TR2 BAY 204 Test ID
Breaker ID2 Test date 2/21/2023
Breaker ID3 Type
Breaker ID4 Referen ce
Serial no. Counter
Commission date Operator TM1800
Interruping medium Plan ID Created in TM1800
Rated frequency Hz Plan description Created in TM1800
Rated voltage kV
Rated current A
Rated short-circuit breaking current kA
Rated motor voltage V
Rated supply voltage V

V CCMD1: 10 V/d iv

t CCMD1

I CIR1:t C
1 A/div
0 1R

ttCB 001
1MR

I CCIR1: 1t B
0 A/
01div
M

ttAA 01M
01R

0.0 10. 0 20. 0 30. 0 40. 0 50. 0 60. 0 70. 0 80. 0 90. 0 100 .0 110 .0 120 .0 130 .0 140 .0 150 .0 160 .0 170 .0 180 .0 190 .0 200 .0 210 .0 220 .0 230 .0 240 .0 250 .0 260 .0 270 .0 280 .0 290 .0 300 .0 310 .0

Scale = 10.0 ms/divs

Parameters Value Unit


Close time A 01M 67.000 ms
Bounce t A 01M 1.800 ms
Close time A 01R 66.800 ms
Diff M-R A 01R 0.200 ms
PIR Res. A 01R 150.5 ohm
Close time B 01M 66.700 ms
Bounce t B 01M 1.900 ms
Close time B 01R 66.700 ms
Diff M-R B 01R 0.000 ms
PIR Res. B 01R 77.0 ohm
Close time C 01M 66.600 ms
Bounce t C 01M 2.600 ms
Close time C 01R 0.200 ms
Diff M-R C 01R 66.400 ms
PIR Res. C 01R 8459.1 ohm
Close time A 67.000 ms
Close time B 66.700 ms
Close time C 66.600 ms
Close time 67.000 ms
Pk current CCIR1 7.1 A
C contr. V CCMD1 93.0 V
Dat e Page

Test report 2/22/2023 2

Circuit Breaker

Circuit Breaker Data Test Data


Breaker ID1 100 MVA TR2 BAY 204 Test ID
Breaker ID2 Test date 2/21/2023
Breaker ID3 Type
Breaker ID4 Referen ce
Serial no. Counter
Commission date Operator TM1800
Interruping medium Plan ID Created in TM1800
Rated frequency Hz Plan description Created in TM1800
Rated voltage kV
Rated current A
Rated short-circuit breaking current kA
Rated motor voltage V
Rated supply voltage V

Parameters Value Unit


Temp. -- -- -- °C
Temp. -- -- -- °F

Recording notes:

Test notes:n.a

Location Test Date Tested by Signature Approved by

2/21/2023 TM1800