You are on page 1of 30

Firestopping

Standard Details

JAN 2017
The ROCKWOOL FIREPRO® range of products provides
firestopping and fire resistance throughout the whole construction
process; intended to make buildings and their inhabitants safer in
the event of fire.

Beyond ROCKWOOL insulation’s inherent fire resistant qualities,


our specialist range of products help architects, contractors
and developers conform to current fire regulations.

Our range of fire resistance products cater for most general


purpose and specialty building applications:

Structural protection
Penetration seals
Joints
Cavity barriers
Heating, ventilation and air conditioning
Process pipes.

Interested?

For further information on ROCKWOOL FIREPRO® products


and solutions, contact the Technical Solutions Team
on 01656 862 621 or email: info@rockwool.co.uk

Visit www.rockwool.co.uk to view our


complete range of products and services
Contents

Drawing Number FirePro® Product Application Area Orientation of Use Page


SD-106-RDW 60mm Ablative Coated Batt Multi Service Penetration Vertical 4
SD-107-RDW 60mm Ablative Coated Batt Multi Service Penetration Vertical 5
SD-124-RDW 60mm Ablative Coated Batt Damper + Multi Service Penetration Horizontal 6
SD-125-RDW 60mm Ablative Coated Batt Head of Wall Vertical 7
BD-D-2-CDA-100 60mm Ablative Coated Batt Dampers Vertical 8
FP-D-2-SDA-97 60mm Ablative Coated Batt Dampers Vertical 9
BB-D-2-SDA-99 60mm Ablative Coated Batt Dampers Vertical 10
SD-111-RDW 60mm Ablative Coated Batt Face Fix Multi Service Penetration Vertical 11
SD-112-RDW 50mm Ablative Coated Batt Multi Service Penetration Vertical 12
SD-122-RDW 50mm Ablative Coated Batt Multi Service Penetration Vertical 13
SD-123-RDW 50mm Ablative Coated Batt Multi Service Penetration Horizontal 14
SD-126-RDW 50mm Ablative Coated Batt Head of Wall Vertical 15
SD-113-RDW 50mm Ablative Coated Batt Face Fix Multi Service Penetration Vertical 16
SD-118-RDW Intumescent Pipe Collars Combustible Pipes Vertical 17
SD-130-RDW Intumescent Pipe Collars Combustible Pipes Vertical 18
SD-131-RDW Intumescent Pipe Collars Combustible Pipes Horizontal 19
SD-105-RDW High Expansion Intumescent Sealant Combustible Pipes Horizontal 20
SD-128-RDW Acoustic Intumescent Sealant Cables and Non Combustible Pipes Vertical 21
SD-137-RDW Acoustic Intumescent Sealant Linear Joints Both 22
SD-132-RDW Firestop Compound Multi Service Penetration Horizontal 23
SD-114-RDW Firestop Compound Damper Horizontal 24
SD-115-RDW Firestop Compound Damper Vertical 25
SD-134-RDW Linear and Trapezoidal Firestops Head of Wall Vertical 26
SD-135-RDW Multi Cable Firestop Cables Vertical 27
SD-136-RDW Intumescent Pipe Wraps Combustible Pipes Both 28

3
4
5
6
7
Notes

1. ENSURE AREA WITHIN THE APERTURE IS FREE FROM ANY DEBRIS


M10 DROP RODS Damper type:
AND REMOVE ANY DUST SUPPORTING DAMPER Circular or Flat Oval SmokeShield PTC™ dampers
(PROTECTED AS NECESSARY) manufactured by ActionAir
2. CUT ROCKWOOL ABLATIVE COATED BATT(S) TO THE SIZE AND
SHAPE REQUIRED TO FILL THE WALL APERTURE, ENSURING THE Damper sizes for circular ductwork:
BATTS MAKE A TIGHT FIT WITH ALL EDGES OF THE APERTURE Minimum: 200mm x 200mm (to suit 100mm diameter
ductwork)
3. CUT HOLE FROM THE COATED BATT(S) TO ACCEPT DAMPER
ROCKWOOL BLOCKWORK Maximum: 1000mm x 1000mm (to suit 950mm
4. CUT THE COATED BATTS AS NECESSARY TO ALLOW FITTING INTO OR CONCRETE WALL diameter ductwork)
APERTURE AROUND DAMPER
Damper sizes for flat-oval ductwork:
5. WHERE THE COATED BATT WILL CONTACT THE SURROUNDING Minimum: 350mm x 250mm (to suit 300mm x 200mm
MASONRY, APPLY ROCKWOOL ACOUSTIC INTUMESCENT SEALANT
TO THE OUTER EDGES OF THE BATT. DO NOT APPLY TO THE ductwork)
EDGES THAT WILL BE IN CONTACT WITH THE DAMPER Maximum: 1000mm x 550mm (to suit 950mm x 500mm
6. WHERE TWO COATED BATTS WILL BE IN CONTACT, USE
ductwork)
ROCKWOOL FIREPRO GLUE AS THE JOINT ADHESIVE, 60mm ABLATIVE Damper installation:
ENSURING AN EVEN COVER IS PROVIDED OVER THE In accordance with HVCA document DW/145 and
ENTIRE THICKNESS OF BOTH BATT EDGES COATED BATT TIGHTLY securely supported from cleats either side of wall to
7. INSERT THE CUT BATT(S) AROUND THE DAMPER FITTED INTO VOID manufacturer's recommendations
AND AGAINST THE DAMPER FRONT FLANGE UNTIL Wall Construction: • 150mm thick blockwork / brickwork /
THE APERTURE IS COMPLETELY FILLED AND A
TIGHT SEAL IS ACHIEVED concrete
Aperture (seal) sizes: To suit damper sizes as follows:-
8. CUT PACKER PIECES OF COATED BATT, MINIMUM Circular ductwork: For damper sizes between 200mm
60mm x 20mm, AND LOCATE THESE AROUND
and 300mm, the width of Coated Batt between damper and
DAMPER AGAINST THE REAR SURFACE
(NON-ACCESS SIDE) OF THE MAIN COATED BATT
MINIMUM 20mm x 60mm wall/partition must be between150 and 450mm, ±5% fitting
SEAL. (IF NECESSARY, A BEAD OF SEALANT MAY INFIL PIECE OF COATED tolerance
BE USED TO HOLD THE PACKER PIECES TO THE
MAIN COATED BATT SEAL UNTIL THE RETAINING
BATT FITTED AROUND Circular ductwork: For damper sizes between 301mm
ANGLES ARE INSTALLED) DAMPER CASING, BETWEEN and 1000mm, the width of Coated Batt between damper and
MAIN COATED BATT SEAL wall/partition must be between 150 and 700mm, ± 5%
9. USING STEEL RIVETS OR SELF-TAPPING SCREWS, FIX fitting tolerance
THE REAR FLANGE COLLAR TO THE NON-ACCESS SIDE AND DAMPER REAR FLANGE Flat-Oval ductwork: Coated batt width between damper
OF THE DAMPER, TIGHT AGAINST THE EXPOSED FACES OF
THE PACKER PIECES and wall/partition must be between 150 and 750mm, ± 5%
fitting tolerance
10. APPLY BEADS OF ROCKWOOL ACOUSTIC INTUMESCENT SEALANT ACTIONAIR SMOKESHIELD Fire resistance:
TO BOTH SIDES OF THE WALL, APPROXIMATELY 15mm WIDE,
AROUND THE PERIMETER OF THE ABLATIVE COATED BATT,
PTC DAMPER Integrity - 120 minutes
ENSURING ANY GAPS BETWEEN THE BATT AND THE SURROUNDING Insulation - n/a
WALL EDGES ARE FULLY FILLED

11. REPAIR ANY DAMAGE TO THE BATT COATING WHICH MAY HAVE
OCCURRED DURING INSTALLATION AND THE EXPOSED EDGE OF
THE INFIL PACKING PIECES BY BRUSH OR SPRAY APPLYING
ROCKWOOL ABLATIVE COATING

12. ALLOW AT LEAST 12 HOURS FOR BATT PENETRATION SEAL TO ROCKWOOL LIMITED
CURE PRIOR TO REMOVING ANY LATERAL DAMPER SUPPORTS
Pencoed, Bridgend,
South Wales CF35 6NY
• 20mm THICK ABLATIVE
COATED BATT INFILL
ROCKWOOL ABLATIVE COATED
BATT PENETRATION SEAL t: 0871 222 0011
ACOUSTIC INTUMESCENT f: 0871 222 1781
• 60mm INFIL DEPTH
DAMPER SUPPORT CLEAT SEALANT BEADS APPLIED
Client
DUCT AROUND COATED BATT

Job Title

DAMPER BLADES

• 10mm DUCT SUPPORT


Drawing Title
RODS (FIRE PROTECT
AS NECESSARY) 150mm Brick / Block Wall
Circular Dampers
DAMPER CASING
DUCT SUPPORT CLEAT The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations
from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not
FIXED DAMPER CASE accept responsibility for the consequences of using Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Scale Date
FRONT FLANGE Expert advice should be sought where such applications are contemplated.
ADJUSTABLE DAMPER
CASE REAR FLANGE
The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified
solutions. The policy of Rockwool Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the
NTS October 2011
latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the Sheet Size Drawn By
information contained within this drawing may be affected by pertinent changes in the law or regulatory requirements and alterations or
NOTES:
amendments to the specification of Rockwool products. A3 Technical Graphics Ltd
1. THE DUCTWORK SYSTEM AND FIRE DAMPERS ETC. MUST BE INSTALLED AS RECOMMENDED BY THE APPROPRIATE MANUFACTURER
2. DAMPERS MUST BE INSTALLED CENTRALLY WITHIN THE WALL LINE Drawing Number Rev.
Rockwool Fire Stopping Technical Support: 0871 222 0011 BB-D-2-CDA-100 1.0

8
Notes
1. ENSURE AREA WITHIN THE APERTURE IS FREE FROM ANY DEBRIS
AND REMOVE ANY DUST
M10 DROP RODS Damper type:
SUPPORTING DAMPER Rectangular SmokeShield PTC™ dampers manufactured
2. CUT ROCKWOOL ABLATIVE COATED BATT(S) TO THE SIZE AND by ActionAir
SHAPE REQUIRED TO FILL THE WALL APERTURE, ENSURING THE (PROTECTED AS NECESSARY)
BATTS MAKE A TIGHT FIT WITH ALL EDGES OF THE APERTURE Damper sizes:
Minimum: 100mm x 100mm
3. CUT HOLE FROM THE COATED BATT(S) TO ACCEPT DAMPER
ROCKWOOL STONE WOOL Maximum: 1000mm x 1000mm
4. CUT THE COATED BATTS AS NECESSARY TO ALLOW FITTING INTO SLAB INSULATION Damper installation:
APERTURE AROUND DAMPER In accordance with HVCA document DW/145 and
RECOMMENDED IN PARTITION
5. WHERE THE COATED BATT WILL CONTACT THE SURROUNDING securely supported from cleats either side of wall to
PLASTERBOARD, APPLY ROCKWOOL ACOUSTIC INTUMESCENT manufacturer's recommendations
SEALANT OR ROCKWOOL FIREPRO GLUE TO THE OUTER EDGES
OF THE BATT. DO NOT APPLY TO THE EDGES THAT WILL BE IN CONTACT 2 HOUR FIRE RATED Wall Construction: 2 hour fire resistant plasterboard /
WITH THE DAMPER PLASTERBOARD WALL steel studs
Aperture (seal) sizes: To suit damper sizes as follows:-
6. WHERE TWO COATED BATTS WILL BE IN CONTACT, USE
ROCKWOOL FIREPRO GLUE AS THE JOINT ADHESIVE, For damper size ranges between 100 x 100mm and 300 x
ENSURING AN EVEN COVER IS PROVIDED OVER THE 60mm ABLATIVE 300mm, the width of Coated Batt between damper and wall
ENTIRE THICKNESS OF BOTH BATT EDGES must be between 150 and 450mm, ±5% fitting tolerance
COATED BATT TIGHTLY For damper size ranges between 301 x 301mm and 1000 x
7. INSERT THE CUT BATT(S) AROUND THE DAMPER
AND AGAINST THE DAMPER FRONT FLANGE UNTIL FITTED INTO VOID 1000mm, the width of Coated Batt between damper and wall
THE APERTURE IS COMPLETELY FILLED AND A must be between 150 and 700mm, ±5% fitting tolerance
TIGHT SEAL IS ACHIEVED
Fire resistance:
8. CUT PACKER PIECES OF COATED BATT, MINIMUM Integrity - 120 minutes
60mm x 20mm, AND LOCATE THESE AROUND Insulation - n/a
DAMPER AGAINST THE REAR SURFACE
(NON-ACCESS SIDE) OF THE MAIN COATED BATT
MINIMUM 20mm x 60mm
SEAL. (IF NECESSARY, A BEAD OF SEALANT MAY INFIL PIECE OF COATED
BE USED TO HOLD THE PACKER PIECES TO THE
MAIN COATED BATT SEAL UNTIL THE RETAINING
BATT FITTED AROUND
ANGLES ARE INSTALLED) DAMPER CASING, BETWEEN
9. USING STEEL RIVETS OR SELF-TAPPING SCREWS, FIX
MAIN COATED BATT SEAL
THE 4 REAR FLANGE ANGLES TO THE NON-ACCESS SIDE AND DAMPER REAR FLANGE
OF THE DAMPER, TIGHT AGAINST THE EXPOSED FACES OF
THE PACKER PIECES

10. APPLY BEADS OF ROCKWOOL ACOUSTIC INTUMESCENT SEALANT ACTIONAIR SMOKESHIELD


TO BOTH SIDES OF THE WALL, APPROXIMATELY 15mm WIDE,
AROUND THE PERIMETER OF THE ABLATIVE COATED BATT,
PTC MULTI-BLADE DAMPER
ENSURING ANY GAPS BETWEEN THE BATT AND THE SURROUNDING
WALL EDGES ARE FULLY FILLED

11. REPAIR ANY DAMAGE TO THE BATT COATING WHICH MAY HAVE
OCCURRED DURING INSTALLATION AND THE EXPOSED EDGE OF
THE INFIL PACKING PIECES BY BRUSH OR SPRAY APPLYING
ROCKWOOL ABLATIVE COATING

12. ALLOW AT LEAST 12 HOURS FOR BATT PENETRATION SEAL TO ROCKWOOL LIMITED
CURE PRIOR TO REMOVING ANY LATERAL DAMPER SUPPORTS
Pencoed, Bridgend,
South Wales CF35 6NY
• 20mm THICK ABLATIVE
COATED BATT INFILL
ROCKWOOL ABLATIVE COATED
BATT PENETRATION SEAL t: 0871 222 0011
ACOUSTIC INTUMESCENT f: 0871 222 1781
• 60mm INFIL DEPTH
DAMPER SUPPORT CLEAT SEALANT BEADS APPLIED
Client
DUCT AROUND COATED BATT

Job Title

DAMPER BLADES

• 10mm DUCT SUPPORT


Drawing Title
RODS (FIRE PROTECT
AS NECESSARY) 2 hour Flexible Wall
Square Dampers
DAMPER CASING
DUCT SUPPORT CLEAT The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations
from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not
FIXED DAMPER CASE accept responsibility for the consequences of using Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Scale Date
FRONT FLANGE Expert advice should be sought where such applications are contemplated.
ADJUSTABLE DAMPER
CASE REAR FLANGE
The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified
solutions. The policy of Rockwool Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the
NTS October 2011
latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the Sheet Size Drawn By
information contained within this drawing may be affected by pertinent changes in the law or regulatory requirements and alterations or
NOTES:
amendments to the specification of Rockwool products. A3 Technical Graphics Ltd
1. THE DUCTWORK SYSTEM AND FIRE DAMPERS ETC. MUST BE INSTALLED AS RECOMMENDED BY THE APPROPRIATE MANUFACTURER
2. DAMPERS MUST BE INSTALLED CENTRALLY WITHIN THE WALL LINE Drawing Number Rev.
Rockwool Fire Stopping Technical Support: 0871 222 0011 FP-D-2-SDA-97 1.0

9
Notes

1. ENSURE AREA WITHIN THE APERTURE IS FREE FROM ANY DEBRIS


M10 DROP RODS Damper type:
AND REMOVE ANY DUST SUPPORTING DAMPER Rectangular SmokeShield PTC ™ dampers manufactured
(PROTECTED AS NECESSARY) by ActionAir
2. CUT ROCKWOOL ABLATIVE COATED BATT(S) TO THE SIZE AND
SHAPE REQUIRED TO FILL THE WALL APERTURE, ENSURING THE Damper sizes:
BATTS MAKE A TIGHT FIT WITH ALL EDGES OF THE APERTURE Minimum: 100mm x 100mm
Maximum: 1000mm x 1000mm
3. CUT HOLE FROM THE COATED BATT(S) TO ACCEPT DAMPER 150mm BLOCKWORK Damper installation:
4. CUT THE COATED BATTS AS NECESSARY TO ALLOW FITTING INTO OR CONCRETE WALL In accordance with HVCA document DW/145 and
APERTURE AROUND DAMPER
securely supported from cleats either side of wall to
5. WHERE THE COATED BATT WILL CONTACT THE SURROUNDING manufacturer's recommendations
MASONRY, APPLY ROCKWOOL ACOUSTIC INTUMESCENT SEALANT
TO THE OUTER EDGES OF THE BATT. DO NOT APPLY TO THE Wall Construction: • 150mm thick blockwork / brickwork /
EDGES THAT WILL BE IN CONTACT WITH THE DAMPER concrete
Aperture (seal) sizes: To suit damper sizes as follows:-
6. WHERE TWO COATED BATTS WILL BE IN CONTACT, USE
ROCKWOOL FIREPRO GLUE AS THE JOINT ADHESIVE, For damper size ranges between 100 x 100mm and 300 x
ENSURING AN EVEN COVER IS PROVIDED OVER THE 60mm ABLATIVE 300mm, the width of Coated Batt between damper and wall
ENTIRE THICKNESS OF BOTH BATT EDGES
COATED BATT TIGHTLY must be between 150 and 450mm, ±5% fitting tolerance
For damper size ranges between 301 x 301mm and 1000 x
7. INSERT THE CUT BATT(S) AROUND THE DAMPER
AND AGAINST THE DAMPER FRONT FLANGE UNTIL
FITTED INTO VOID 1000mm, the width of Coated Batt between damper and wall
THE APERTURE IS COMPLETELY FILLED AND A must be between 150 and 700mm, ±5% fitting tolerance
TIGHT SEAL IS ACHIEVED
Fire resistance:
8. CUT PACKER PIECES OF COATED BATT, MINIMUM Integrity - 120 minutes
60mm x 20mm, AND LOCATE THESE AROUND Insulation - n/a
DAMPER AGAINST THE REAR SURFACE
(NON-ACCESS SIDE) OF THE MAIN COATED BATT
MINIMUM 20mm x 60mm
SEAL. (IF NECESSARY, A BEAD OF SEALANT MAY INFIL PIECE OF COATED
BE USED TO HOLD THE PACKER PIECES TO THE
MAIN COATED BATT SEAL UNTIL THE RETAINING
BATT FITTED AROUND
ANGLES ARE INSTALLED) DAMPER CASING, BETWEEN
9. USING STEEL RIVETS OR SELF-TAPPING SCREWS, FIX
MAIN COATED BATT SEAL
THE 4 REAR FLANGE ANGLES TO THE NON-ACCESS SIDE AND DAMPER REAR FLANGE
OF THE DAMPER, TIGHT AGAINST THE EXPOSED FACES OF
THE PACKER PIECES

10. APPLY BEADS OF ROCKWOOL ACOUSTIC INTUMESCENT SEALANT


TO BOTH SIDES OF THE WALL, APPROXIMATELY 15mm WIDE, ACTIONAIR SMOKESHIELD
AROUND THE PERIMETER OF THE ABLATIVE COATED BATT, PTC MULTI-BLADE DAMPER
ENSURING ANY GAPS BETWEEN THE BATT AND THE SURROUNDING
WALL EDGES ARE FULLY FILLED

11. REPAIR ANY DAMAGE TO THE BATT COATING WHICH MAY HAVE
OCCURRED DURING INSTALLATION AND THE EXPOSED EDGE OF
THE INFIL PACKING PIECES BY BRUSH OR SPRAY APPLYING
ROCKWOOL ABLATIVE COATING

12. ALLOW AT LEAST 12 HOURS FOR BATT PENETRATION SEAL TO ROCKWOOL LIMITED
CURE PRIOR TO REMOVING ANY LATERAL DAMPER SUPPORTS
Pencoed, Bridgend,
South Wales CF35 6NY
• 20mm THICK ABLATIVE
COATED BATT INFILL
ROCKWOOL ABLATIVE COATED
BATT PENETRATION SEAL t: 0871 222 0011
ACOUSTIC INTUMESCENT f: 0871 222 1781
• 60mm INFIL DEPTH
DAMPER SUPPORT CLEAT SEALANT BEADS APPLIED
Client
DUCT AROUND COATED BATT

Job Title

DAMPER BLADES

• 10mm DUCT SUPPORT


Drawing Title
RODS (FIRE PROTECT
AS NECESSARY) 150mm Brick / Block Wall
Square Dampers
DAMPER CASING
DUCT SUPPORT CLEAT The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations
from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not
FIXED DAMPER CASE accept responsibility for the consequences of using Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Scale Date
FRONT FLANGE Expert advice should be sought where such applications are contemplated.
ADJUSTABLE DAMPER
CASE REAR FLANGE
The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified
solutions. The policy of Rockwool Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the
NTS October 2011
latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the Sheet Size Drawn By
information contained within this drawing may be affected by pertinent changes in the law or regulatory requirements and alterations or
NOTES:
amendments to the specification of Rockwool products. A3 Technical Graphics Ltd
1. THE DUCTWORK SYSTEM AND FIRE DAMPERS ETC. MUST BE INSTALLED AS RECOMMENDED BY THE APPROPRIATE MANUFACTURER
2. DAMPERS MUST BE INSTALLED CENTRALLY WITHIN THE WALL LINE Drawing Number Rev.
Rockwool Fire Stopping Technical Support: 0871 222 0011 BB-D-2-SDA-99 1.0

10
11
12
13
14
15
16
17
18
19
20
INSTALLATION NOTES

1. Make sure that the area within the aperture is


clean of any debris and remove any dust from The supporting construction must be capable of
the edges. achieving the required fire rating of the proposed
Firestop.
2. Ensure that the surface is free from any bond
breaking contaminants prior to application of Flexible wall construction must be installed in
sealant. Non-combustible pipe accordance with the manufacturer's guidelines. The
Max Ø159mm Wall construction should be of a minimum thickness of
3. Install the backing material around the service 120 mm.
item to allow for the minimum allowable seal
depth. The backing material can consist of either All service items should be adequately supported
stone wool packed around the service or a PE either side of the Firestop to ensure that no load is
backing rod. transferred onto the coated batt.

4. Install the Rockwool Acoustic Intumescent Non-combustible pipe Backing material to control depth of sealant can be
Sealant to the required depth ensuring a smooth Max Ø159mm Rockwool acoustic either a PE backing rod or Rockwool insulation packed
tight finish with both the service item and the intumescent sealant into the annular space.
substrate. Drywall Construction
Block Wall Construction Where insulation is required from metallic pipes then
5. Repeat step 3 and 4 on the other side of the the service item will need to be lagged with Rockwool
wall. Fire Tube or H&V Section. Please contact Rockwool
technical for further details.
Pipe Integrity
Performance

Up to 120 Minutes

Cable Integrity Cable Integrity


Performance Performance

Up to 120 Minutes Up to 120 Minutes


(21-50mm Cables 90 Minutes) (21-50mm Cables 60 Minutes)

Cable trays up to 450 mm


wide x 25 mm deep. TECHNICAL SOLUTIONS
Max 21mm cables
Pencoed, Bridgend,
South Wales CF35 6NY
t: 01656 862621
email: technical.solutions@rockwool.co.uk
Rockwool RW4 backing
Client
Rockwool acoustic
intumescent sealant
Project Title

Cables upto 50mm Drawing Title

Scale Date

Drywall/Block Wall
Sheet Size Drawn By

The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not accept responsibility for the consequences of
using Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Expert advice should be sought where such applications are contemplated.The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified solutions. The policy Drawing Number Rev.
of Rockwool Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the information contained within this drawing may be affected by pertinent
changes in the law or regulatory requirements and alterations or amendments to the specification of Rockwool products.

21
22
23
24
25
26
27
28
Notes

29
ROCKWOOL Limited
Pencoed
Bridgend
CF35 6NY

26 - 28 Hammersmith Grove
Hammersmith
London
W6 7HA

Technical Solutions Team


01656 862621

info@rockwool.co.uk
www.rockwool.co.uk